Indoor unit : 12,000Btu
z
„
(°FDB)
(°FWB)
5
3
12.55
14
12
14.28
23
19
15.06
32
28
15.94
41
37
18.06
47
43
19.26
50
47
19.40
59
50
19.59
68
59
19.21
75
65
16.21
TC : Total Capacity (kBtu/h)
IP : Input Power (kW)
(°CDB)
(°CWB)
-15.0
-16.1
-10.0
-11.1
-5.0
-7.2
0.0
-2.2
5.0
2.8
8.3
6.1
10.0
8.3
15.0
10.0
20.0
15.0
23.9
18.3
TC : Total Capacity (kW)
IP : Input Power (kW)
Indoor temperature
60°FDB
65°FDB
TC
IP
TC
IP
1.69
12.15
1.74
11.74
1.81
13.83
1.86
13.36
1.78
14.58
1.83
14.09
1.69
15.44
1.74
14.92
1.58
17.49
1.63
16.89
1.60
18.65
1.64
18.02
1.61
18.79
1.66
18.15
1.62
18.97
1.66
18.33
1.37
18.60
1.41
17.97
0.95
15.70
0.98
15.16
Indoor temperature
15.6°CDB
18.3°CDB
TC
IP
TC
IP
3.68
1.69
3.56
1.74
4.18
1.81
4.05
1.86
4.41
1.78
4.27
1.83
4.67
1.69
4.53
1.74
5.29
1.58
5.12
1.63
5.64
1.60
5.47
1.64
5.69
1.61
5.51
1.66
5.74
1.62
5.56
1.66
5.63
1.37
5.45
1.41
4.75
0.95
4.60
0.98
- (02 - 13) -
70°FDB
75°FDB
TC
IP
TC
IP
1.79
11.33
1.84
11.08
1.92
12.89
1.97
12.61
1.88
13.59
1.93
13.29
1.79
14.40
1.84
14.08
1.67
16.30
1.72
15.94
1.69
17.39
1.74
17.00
1.71
17.52
1.76
1.71
17.69
1.76
17.30
1.45
17.34
1.49
16.96
1.00
14.63
1.03
14.31
21.1°CDB
23.9°CDB
TC
IP
TC
IP
3.44
1.79
3.32
1.84
3.92
1.92
3.78
1.97
4.13
1.88
3.98
1.93
4.37
1.79
4.22
1.84
4.95
1.67
4.78
1.72
5.28
1.69
5.10
1.74
5.32
1.71
5.13
1.76
5.37
1.71
5.18
1.76
5.27
1.45
5.08
1.49
4.44
1.00
4.29
1.03
78°FDB
TC
IP
1.87
2.00
1.96
1.87
1.75
1.76
17.13
1.78
1.79
1.52
1.05
25.6°CDB
TC
IP
3.25
1.87
3.70
2.00
3.90
1.96
4.13
1.87
4.67
1.75
4.98
1.76
5.02
1.78
5.07
1.79
4.97
1.52
4.19
1.05
Table of Contents