Summary of Contents for Fujitsu aoyg30lat4

  • Page 1: Air Conditioner

    AIR CONDITIONER OUTDOOR UNIT INSTALLATION MANUAL For authorized personnel only. INSTALLATIONSANLEITUNG Nur für autorisiertes Personal. MANUEL D'INSTALLATION Pour le personnel agréé uniquement. MANUAL DE INSTALACIÓN Solo para personal autorizado. MANUALE D'INSTALLAZIONE Ad uso esclusivo del personale autorizzato. ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις. MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados.
  • Page 2: Table Of Contents

    INSTALLATION MANUAL Using the same vacuum pump for different refrigerants may damage the vacuum pump or the unit. PART NO. 9374872121-03 Use a clean gauge manifold and charging hose for R410A exclusively. Contents During the pump-down operation, make sure that the compressor is turned off before SAFETY PRECAUTIONS ………………………………………………………………...
  • Page 3: Special Tools For R410A

    21 41 11 CONNECTABLE INDOOR UNIT CAPACITY TYPE 21 21 Special tools for R410A CAUTION Tool name Contents of change The total capacity of the indoor units connected must be between 27,000 and 49,000BTU. Pressure is high and cannot be measured with a conventional gauge.
  • Page 4: Installation Work

    21 41 41 HEAT INSULATION AROUND CONNECTION PIPES REQUIREMENTS CAUTION CAUTION If children under 10 years old may approach the unit, take preventive measures so that they cannot reach the unit. Install heat insulation around both the gas and liquid pipes. Failure to do so may cause Keep the length of the piping of the indoor and outdoor units within the allowable range.
  • Page 5: Transportation Of The Unit

    21 21 11 Single outdoor unit installation • Be sure to hold the handles on the sides of the unit. Otherwise, holding the suction grille on the sides of the unit may cause deformation. When the upward area is open Handle •...
  • Page 6: Electrical Wiring

    Dimension A (mm) CAUTION Pipe outside Dimension B [mm] Flare tool for R410A, - 014 diameter [mm (in.)] Hold the torque wrench at its grip, keeping it in a right angle with the pipe, in order to clutch type tighten the flare nut correctly. 6.35 (1/4) •...
  • Page 7: Electrical Requirement

    Strip : 10mm Crimp-type CAUTION terminal The static electricity that is charged to the human body can damage the control PC Board when handling the control PC Board for address setting, etc. Please keep caution to the following points. Sleeve Provide the grounding of Indoor unit, Outdoor unit and Option equipment.
  • Page 8: Pipe Installation I I

    Tightening torque Be sure to seal the holes Putty 6.35 mm (1/4 in.) 20 to 25 N·m (200 to 250 kgf·cm) when applying the putty. 9.52 mm (3/8 in.) 20 to 25 N·m (200 to 250 kgf·cm) Place the cables side by side.
  • Page 9: Power

    POWER Error contents LED 1 LED 2 LED 3 LED 4 Trip terminal L error ●14 times WARNING Outdoor unit fan motor error ●15 times Always use a special branch circuit and install a special receptacle to supply power to Outdoor unit PCB microcomputer ●17 times communication error...