Sleep Mode Operation - Toshiba RAS-M10PKVP-E Service Manual

Split type
Hide thumbs Also See for RAS-M10PKVP-E:
Table of Contents
Item
10. SLEEP MODE
When pushing [SLEEP MODE] button on the remote
operation
controller, a quiet and mild operation is performed by
reducing the fan speed and the compressor speed.
This function operates the air conditioner with the differ-
ence between the set and the room temperature as shown
in the following figure.
The time correction is performed for 8 minutes each.
TA-Tsc
[˚C]
+6.5
+6.0
+5.5
+5.0
+4.5
+4.0
+3.5
+3.0
+2.5
+2.0
+1.5
+1.0
+0.5
0.0
–0.5
–1.0
–1.5
–2.0
1H
TA-Tsc
[˚C]
0
A
–0.5
–1.0
–1.5
B
–2.0
–2.5
–3.0
–4.0
–5.0
–6.0
–7.0
–8.0
C
–9.0
–10.0
–11.0
Operation flow and applicable data, etc.
2H
3H
4H
30 minutes
A
B
C
Fan
Time
speed
correction
W6
W5
+ 1
zone
W4
W3
± 0
–1
zone
(min 1)
time
→ Time Compressor
speed
0Hz
A zone
B zone
C zone
– 63 –
Description
1) The indoor fan speed is controlled
between W6 and W3.
The compressor speed in control
as shown in the left figure.
2) The set temperature increased
0.5°C per hour up to 2°C starting
from the set temperature when
SLEEP MODE has been received.
1) The indoor fan speed is controlled
within (W7) as maximum value.
2) The louver position is set
horizontally (Standard cooling
position) when the room
temperature comes close to the
set temperature or when 25
minutes passed after starting

SLEEP MODE operation.