Honeywell TH8320ZW Installation Manual

Honeywell TH8320ZW Installation Manual

Hide thumbs Also See for TH8320ZW:
TH8320ZW
Touch-screen Thermostat
This manual covers the TH8320ZW.
System Types
• Gas, oil, or electric heat with air
conditioning
• Warm air, hot water, high
efficiency furnaces, heat
pumps, steam, gravity
• Heat only — including power to open
and close zone valves (Series 20), and
normally open zone valves
This thermostat contains a Lithium battery which may contain Perchlorate material.
Perchlorate Material—special handling may apply.
See www.dtsc.ca.gov/hazardouswaste/perchlorate
For assistance with this product please visit http://customer.honeywell.com
or call Honeywell Customer Care toll-free at 1-800-468-1502
® U.S. Registered Trademark.
US Patent No. 6,574,581, 6,975,958, 7,114,554,
7,346,467, 7,636,604, 7,693,582, 7,788,936,
7,845,576, and other patents pending.
Copyright © 2013 Honeywell International Inc.
All rights reserved.
• Heat only with fan
• Cool only
• 750 mV heating systems
Need Help?
Installation
Guide
69-2486-07
Table of Contents
loading

Summary of Contents for Honeywell TH8320ZW

  • Page 1 This thermostat contains a Lithium battery which may contain Perchlorate material. Perchlorate Material—special handling may apply. See www.dtsc.ca.gov/hazardouswaste/perchlorate Need Help? For assistance with this product please visit http://customer.honeywell.com or call Honeywell Customer Care toll-free at 1-800-468-1502 ® U.S. Registered Trademark. US Patent No. 6,574,581, 6,975,958, 7,114,554, 7,346,467, 7,636,604, 7,693,582, 7,788,936, 7,845,576, and other patents pending.
  • Page 2 Installation Guide Wallplate installation 1. Separate wallplate from thermostat. Grasp top and bottom of wallplate 2. Mount wallplate as shown below. and pull to remove from thermostat. Drill 3/16” holes for drywall. Drill 7/32” holes for plaster. M29480 Wire hole Mounting screws Wall anchors M29481 Must be installed by a trained, experienced technician • Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition.
  • Page 3 TH8320ZW Power Requirements HEAT PUMP Remove tab. CONVENTIONAL M32429 The thermostat is shipped from the factory Connect the common side of the M32428A with the coin cell installed. To keep the bat- transformer to “C” terminal. This tery from discharging during shipment and connection is mandatory.
  • Page 4: Terminal Designations

    Installation Guide Wiring Terminal Designations Conventional Terminal Letters: Heat Pump Terminal Letters: Heating power. Connect to secondary Heating power. Connect to secondary side of heating system transformer. side of heating system transformer. Cooling power. Connect to secondary Cooling power. Connect to secondary side of cooling system transformer.
  • Page 5 TH8320ZW Wiring Wiring guide—heat pump systems 1H/1C Heat Pump (no auxiliary heat) 1H/1C System (2 transformers) Power [1] Power (cooling transformer) [1, 2] [R+Rc joined by jumper] Power (heating transformer) [1, 2] Changeover valve [5] Heat relay Compressor relay Compressor contactor...
  • Page 6 Installation Guide Mount thermostat Align pins on back of thermostat with slots in wallplate, then push gently until thermostat snaps into place. M32435 Set date and time Press st Press st to set date to set time Press st to set month Press st to set year 2006...
  • Page 7 TH8320ZW Installer setup Function Setting 0120 0120 DONE DONE M32427 Press DONE to exit & save settings. Press st to Press st to select function change setting Setup functions Settings & Options (factory default in bold) 0120 Year 20 (2000-2078)
  • Page 8 Installation Guide Installer setup Setup functions Settings & Options (factory default in bold) 0250 2nd stage heat Electric furnaces cycle rate (CPH) Steam or gravity systems Hot water systems & furnaces of 90%+ efficiency Gas or oil furnaces of less than 90% efficiency [Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH] 0260 3rd stage heat cycle Electric furnaces...
  • Page 9 TH8320ZW Installer setup Setup functions Settings & Options (factory default in bold 0540 Program periods 4 program periods (Wake, Leave, Return, Sleep) 2 program periods (Wake, Sleep) 0580 Compressor 5 minute compressor off time protection [Other options: 0, 1, 2, 3 or 4-minute off time]...
  • Page 10 Em Heat and fan turn on Second stage heat turns on (Auxiliary heat) CAUTION: EQUIPMENT DAMAGE HAZARD. Compressor protection is bypassed dur- ing testing. To prevent equipment damage, avoid cycling the compressor quickly. Z-Wave enrollment The TH8320ZW is powered by Z-Wave technology so it is compatible with Z-Wave enabled devices from other manufacturers. To join a Z-Wave...
  • Page 11 TH8320ZW Z-Wave enrollment Wait M32422 To remove the thermostat from the Z-Wave network select 0. DONE M32424A M32425 69-2486—07...
  • Page 12 Installation Guide Z-Wave enrollment To share the thermostat Node information with additional Z-Wave devices select 1. DONE M32421 Z-Wave messages Add/ Remove The thermostat can be included or excluded from the Z-Wave network. This action requires the controller set in inclusion mode. The device is included to the Z-Wave network after sending the node information to the controller. The controller is responsible for assigning the home ID and device ID to the included device. The thermostat can also act as a repeater to forward messages to other devices in the Z-Wave network. Repeating messages allows communication of devices that are not in the direct reach of Z-wave protocol.
  • Page 13 TH8320ZW Z-Wave messages received, the fan mode is changed to the desired value (if this value is possible). For the thermostat the possible values are On, Auto and Circ. Indoor Temperature The thermostat sends the indoor temperature using the Multilevel Sensor command class.
  • Page 14 Installation Guide Special functions Auto Changeover (Setup Function 0300): When set to Auto, the thermostat automatically selects heat- ing or cooling depending on the indoor temperature. Heat and cool settings must be at least 2 degrees apart. Adaptive Intelligent Recovery (Setup Function 0530): Allows the thermostat to “learn” how long the furnace and air conditioner take to reach programmed temperature settings, so the temperature is reached at the scheduled time.
  • Page 15 TH8320ZW Regulatory information FCC Compliance Statement (Part 15.19) (USA only) This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: 1) This device may not cause harmful interference, and 2) This device must accept any interference received, including interference that may cause undesired operation.
  • Page 16 Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 http://customer.honeywell.com ® U.S. Registered Trademark US Patent No. 6,574,581, 6,975,958, 7,114,554, 7,346,467, 7,636,604, 7,693,582, 7,788,936, 7,845,576, and other patents pending. © 2013 Honeywell International Inc. 69-2486—07 M.S. Rev. 01-13 Printed in United States...