Specifications - 4 Pipe System - Sakura SFP-KM-DLY Series Installation Manual

Hydronic cassette sfp-km-dly series;
Table of Contents
DLY (DELUXE) SERIES HYDRONIC CASSETTE
Model
Total capacity
(H/M/L)
Sensible capacity
Chilled Water Cooling
(H/M/L)
Water flow rate
Pressure drop
Capacity
(H/M/L)
Hot Water Heating
Water flow rate
Pressure drop
Chilled water content
Evaparator Coil
Hot water content
Type
Fan Blower
Size (Dia.)
No. of fan
Power supply
Electric Power
Power input
Running current
Air Flow (H/M/L)
Sound Pressure (1m,H/M/L)
Operation Control
Unit Dimensions (LxWxH)
Panel Dimensions
Net Weight
Method
Water Connection
In
Out
Cooling: Entering air temperature: Dry bulb 27ºC, Wet bulb 19ºC;
Inlet water temp. 7ºC; Outlet water temp. 12ºC;
Heating: Entering air temperature: 20ºC;
Inlet water temp. 70ºC; Outlet water temp. 60ºC;
SAKURA - Total Air Conditioning Solution
SPECIFICATIONS – 4 PIPE SYSTEM
(4-WAY DISCHARGE SINGLE FAN)
SFP-68KM4-P/DLY
kW
3.0/2.6/2.35
kW
2.4/2.2/1.7
L/h
490
kPa
10.5
kW
6.1/4.7/3.6
L/h
530
kPa
4.5
L
0.93
L
0.47
mm
315
1
V/Ph/Hz
W
58
A
0.27
3
680/520/400
m
/h
dB(A)
39/33/29
581x581x290
mm
680x680x30
mm
kg
25
mm(in)
mm(in)
SFP-80KM4-P/DLY
SFP-85KM4-P/DLY
3.2/2.8/2.4
4.1/3.4/2.6
2.6/2.3/1.75
3.1/2.6/1.9
530
690
11
10
6.3/5.0/3.7
7.6/6.0/4.6
550
660
5
9
0.93
1.23
0.47
0.61
Centrifugal type fan blower
315
380
1
1
220~240 / 1 / 50 (60)
64
71
0.29
0.33
800/630/470
850/700/530
43/37/31
39/32/29
Wireless remote controller and/or Wired wall pad
Socket (Threaded Female)
19.05(3/4")
19.05(3/4")
SFP-102KM4-P/DLY
SFP-136KM4-P/DLY
4.6/3.5/2.7
5.3/3.9/3.0
3.6/2.7/2.1
4.3/3.2/2.3
770
950
11
14
8.0/6.1/4.7
8.6/6.4/4.9
690
740
10
11
1.23
1.23
0.61
0.61
380
380
1
1
84
127
0.38
0.58
1020/770/600
1360/1010/780
42/36/33
50/40/33
701x701x290
830x830x30
29.5
.
11

Hide quick links:

Table of Contents
loading

Table of Contents