ABB -i-Bus-KNX Millenium Technical Reference Manual

Room temperature controller
Hide thumbs Also See for ABB-i-Bus-KNX Millenium:
Table of Contents

Quick Links

1473-1-7819 │ Rev. 01 │ 12.2012
KNX Technical Reference Manual
®
ABB-i-Bus
-KNX Millenium
Room temperature
controller incl. BAU 

6124/20-981-500
AMD70053-AN
Table of Contents
loading

Summary of Contents for ABB ABB-i-Bus-KNX Millenium

  • Page 1 1473-1-7819 │ Rev. 01 │ 12.2012 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Room temperature controller incl. BAU 
 6124/20-981-500 AMD70053-AN...
  • Page 2: Table Of Contents

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Information on the manual ............................4 General information..........................4 Structure of the manual ........................... 4 Symbols in the manual ..........................5 Safety ..................................6 Intended use ............................6 Improper use ............................6 Target groups and qualifications ......................
  • Page 3 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium 11.3.2 Parameters for "Control function = Heating" ..................30 11.3.3 Parameters for "Control function = Cooling" ..................36 11.3.4 Parameters for "Control function = Heating and cooling" ..............42 11.3.5 Parameters for "Control function = Cooling and heating" ..............51 11.4...
  • Page 4: Information On The Manual

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Information on the manual Information on the manual General information Please read this manual through carefully and adhere to the information listed. This will ensure reliable operation and long service life of your product.
  • Page 5: Symbols In The Manual

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Information on the manual Symbols in the manual Danger - danger to life This symbol in connection with the signal word "Danger" indicates dangerous situations which could lead to immediate death or to serious injury.
  • Page 6: Safety

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Safety Safety Warning Electric voltage! Risk of death and fire due to electrical voltage of 230 V. – Work on the 230V supply system may only be performed by authorised electricians! –...
  • Page 7: Target Groups And Qualifications

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Safety Target groups and qualifications Installation, commissioning and maintenance of the product must only be carried out by trained and properly qualified electrical installers. The electrical installers must have read and understood the manual and follow the instructions provided.
  • Page 8: Setup And Function

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Setup and function Setup and function Features of function and equipment The room temperature controller is part of the "Millenium" KNX sensor program. It is a monoblock application module which is suitable for installation in flush-mounted boxes according to BS 4662:2006+A1:2009. The device is equipped with an integrated bus coupler.
  • Page 9: Overview Of Devices

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Setup and function Overview of devices 3.2.1 Front Position Function Push-buttons Rotary control element Display 3.2.2 Rear Position Function KNX connection Note Observe the special mounting instructions in paragraphs "Electrical connection" and "Mounting".
  • Page 10: Cover Frame And Support Ring

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Setup and function Cover frame and support ring Note A cover frame and a support ring from the "Millenium" program are additionally required (see the following illustration). These must be ordered separately.
  • Page 11: Technical Data

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Technical data Technical data Designation Value Power supply 24 V DC (via KNX bus line) Bus subscribers 1 (12 mA) KNX connection Bus connecting terminal, screwless Protection type IP20 according to DIN EN 60529 Ambient temperature range -5 …...
  • Page 12: Installation And Electrical Connection

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Installation and electrical connection Installation and electrical connection Warning Electric voltage! Risk of death due to electrical voltage of 230 V during short-circuit in the low-voltage line. – Low-voltage and 230 V lines must not be installed together in a flush-mounted socket!
  • Page 13: Selection Of Installation Site

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Installation and electrical connection Selection of installation site For proper commissioning please observe the following steps: The room temperature controller should be installed at a height of approximately 150 cm from the floor and 50 cm from a door frame.
  • Page 14 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Installation and electrical connection Wetting the room temperature controller with fluids is to be avoided. Just as heat radiated from electric loads can impair the temperature regulation, so can direct sunlight on the room temperature controller.
  • Page 15: Mounting

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Installation and electrical connection Mounting 6.3.1 Installing the unit The devices with integrated bus coupler have been prepared for installing in flush-mounted boxes according to BS 4662:2006+A1:2009 in connection with the corresponding support ring and cover frame (see also chapter "Cover frame and support ring", on page 10).
  • Page 16: Electrical Connection

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Installation and electrical connection Then plug the cover frame onto the support ring. – Separate order, see also chapter "Cover frame and support ring", on page 10. Fig. 6: Attaching the cover frame Electrical connection Fig.
  • Page 17: Commissioning

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Commissioning Commissioning Software Note The devices are products of the KNX system and meet KNX guidelines. Detailed expert knowledge by means of KNX training sessions for a better understanding is assumed. To start the device a physical address must be assigned first. The physical address is assigned and the parameters are set with the Engineering Tool Software ETS (from version ETS 3.0 f).
  • Page 18: Assigning The Group Address(Es)

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Commissioning 7.1.3 Assigning the group address(es) The group addresses are assigned in connection with the ETS. 7.1.4 Selecting the application program Please contact our Internet support unit (www.Busch-Jaeger.com). The application is loaded into the device via the ETS.
  • Page 19: Operation

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Operation Operation Overview of control elements Fig. 9: Control and display elements Position Control / display elements Button for selecting the fan speed level Rotary control element Button for adjusting the set value Button for activating the ECO mode (e.g.
  • Page 20: Indications In The Display

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Operation Indications in the display Display Indication Action of the device Set-point temperature / room temperature controller – activated No adjustment required • White: Set-point temperature = actual temperature Reduce set-point temperature •...
  • Page 21: Display

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Operation 8.3.3 Display The graphics display has RGB backlighting. The backlighting can be adjusted darker or brighter via a parameter setting in Power-Tool. Display Indication Action of the device White Temperature / controller on –...
  • Page 22: Deactivation

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Operation 8.5.2 Deactivation 1. Press the "On/Off" button (6). 2. ´The device switches to the "Off" state. All buttons are no longer backlit. Fig. 11: The device is deactivated Note All buttons are deactivated.
  • Page 23: Setting The Fan Speed Level (Fan Coil) Or The Operating Status

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Operation Setting the fan speed level (fan coil) or the operating status To adjust the fan speed levels or the operating status, carry out the following steps: 1. Press the "Fan speed levels" button (1).
  • Page 24: Change Into Eco Mode

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Operation Change into ECO mode This mode can be used to automatically set a preset temperature. This means that during absence, for example, the temperature is adjusted downward. 1. Press the "ECO mode" button (4).
  • Page 25: Cleaning

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Cleaning Cleaning Dirty units can be cleaned with a dry cloth. If this is not sufficient, a cloth slightly moistened with a soap solution can be used. Caustic cleaning agents or solvents must not be used.
  • Page 26: Description Of Applications / Objects

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Variante:Power-Tool Description of applications / objects 11.1 Overview of applications The application program for the room temperature controller contains the applications listed in the following: KNX application...
  • Page 27: Application "Temperature Reading

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects 11.2 Application "Temperature reading" With the "Temperaturerfassung" application the measured temperature value can be sent on the bus via a 2-byte communication object. The temperature value can be evaluated by a room temperature controller or displayed on a display for example.
  • Page 28 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Objects Object name Data type Flags Output 2 Byte EIS5 / DPT 9.001 C, T Alarm 1 Bit EIS1 / DPT 1.005 C, T KNX Technical Reference Manual | 1473-1-7819...
  • Page 29: Application "Rtc Settings

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects 11.3 Application "RTC settings" Default settings for the internal room temperature controller can be made with the "Operating mode settings" application. The room temperature controller can be utilised for "Heating", "Cooling", "Heating and cooling" or for "Cooling and heating".
  • Page 30: Parameters For "Control Function = Heating

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects 11.3.2 Parameters for "Control function = Heating" General parameters for "Control Settings Comments function = Heating" Additional heating stage • deactivated – • activated Parameters for "Setting operating...
  • Page 31 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Parameters for "Set values manual" Settings Comments Area for manual set value setting deactivated – +/-1 K +/-2 K +/-3 K +/-4 K +/-5 K +/-6 K...
  • Page 32 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Note The following parameters are available only when parameter "Control type heating" is set on "PI continuous", "PI PWM (1-bit)" or on "FanCoil". General parameters for "Control...
  • Page 33 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Note The following parameters are available only when parameter "Control type heating" is set on "PI continuous", or on "FanCoil". Additional parameters for "Control Settings Comments function = Heating"...
  • Page 34 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Note The following parameters are available only when parameter "Control type heating" is set on "FanCoil". Additional parameters for "Control Settings Comments function = Heating" send automatic switch-off •...
  • Page 35 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Note The following parameters are available only when parameter "Additional heating stage" is set on "activated". Additional parameters for "Control Settings Comments function = Heating" Output additional stage heating •...
  • Page 36: Parameters For "Control Function = Cooling

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects 11.3.3 Parameters for "Control function = Cooling" General parameters for Settings Comments "Reglerfunktion = Kühlen" Additional cooling stage • deactivated – • activated Parameters for "Setting operating...
  • Page 37 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Parameters for "Set values manual" Settings Comments Area for manual set value setting deactivated – +/-1 K +/-2 K +/-3 K +/-4 K +/-5 K +/-6 K...
  • Page 38 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Note The following parameters are available only when parameter "Control type cooling" is set on "PI continuous", "PI PWM (1-bit)" or on "FanCoil". General parameters for "Control...
  • Page 39 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Note The following parameters are available only when parameter "Control type cooling" is set on "PI continuous", or on "FanCoil". Additional parameters for "Control Settings Comments function = Cooling"...
  • Page 40 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Note The following parameters are available only when parameter "Control type cooling" is set on "FanCoil". Additional parameters for "Control Settings Comments function = Cooling" send automatic switch-off •...
  • Page 41 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Note The following parameters are available only when parameter "Additional cooling stage" is set on "activated". Additional parameters for "Control Settings Comments function = Cooling" Output additional stage cooling •...
  • Page 42: Parameters For "Control Function = Heating And Cooling

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects 11.3.4 Parameters for "Control function = Heating and cooling" General parameters for "Control function Settings Comments = Heating and cooling" Switchover heating/cooling • automatic – • via object Output control value heating and cooling •...
  • Page 43 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects General parameters for "Set values" Settings Comments Send current set value • cyclical and for a change – • only cyclical cyclical sending of the current setpoint 1 …...
  • Page 44 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Parameters for "Set values heating" Settings Comments Base setpoint heating (°C) 10 … 40 – Setpoint standby heating, setting 0 … 15 – dependent (K) Setpoint temperature ECO heating, setting 0 …...
  • Page 45 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Note The following parameters are available only when parameter "Control type heating" or "Control type cooling" is set on "PI continuous", "PI PWM (1-bit)" or "FanCoil". General parameters for "Control...
  • Page 46 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Additional parameters for "Control Settings Comments function = Heating" Control parameter • via system type – • Free paramaterization Type of heating system For "PI continuous" • Hot-water heating Type of heating system and "PI PWM (1-bit)"...
  • Page 47 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Note The following parameters are available only when parameter "Control type heating" or "Control type cooling" is set on "PI continuous", or "PI PWM (1-bit)". Additional parameters for "Control...
  • Page 48 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Note The following parameters are available only when parameter "Control type heating" or "Control type cooling" is set on "FanCoil". Additional parameters for "Control Settings Comments function = Heating"...
  • Page 49 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Additional parameters for "Control Settings Comments function = Cooling" send automatic switch-off • deactivated – • activated Manual operation of fan stage • Automatic On / Off –...
  • Page 50 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Note The following parameters are available only when parameter "Additional heating stage" or "Additional cooling stage" is set on "activated". Additional parameters for "Control Settings Comments function = Heating"...
  • Page 51: Parameters For "Control Function = Cooling And Heating

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects 11.3.5 Parameters for "Control function = Cooling and heating" General parameters for "Control function Settings Comments = "Cooling and heating" Switchover heating/cooling • automatic – • via object Output control value heating and cooling •...
  • Page 52 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects General parameters for "Set values" Settings Comments Send current set value • cyclical and for a change – • only cyclical cyclical sending of the current setpoint 1 …...
  • Page 53 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Parameters for "Set values heating" Settings Comments Setpoint standby heating, setting 0 … 15 – dependent (K) Setpoint temperature ECO heating, setting 0 … 15 – dependent (K) Setpoint frost (°C)
  • Page 54 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Note The following parameters are available only when parameter "Control type heating" or "Control type cooling" is set on "PI continuous", "PI PWM (1-bit)" or "FanCoil". General parameters for "Control...
  • Page 55 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Additional parameters for "Control Settings Comments function = Heating" Control parameter • via system type – • Free paramaterization P amount heating (1/10 K) 10 … 100 Only available when parameter "Control...
  • Page 56 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Note The following parameters are available only when parameter "Control type heating" or "Control type cooling" is set on "PI continuous", or "PI PWM (1-bit)". Additional parameters for "Control...
  • Page 57 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Note The following parameters are available only when parameter "Control type heating" or "Control type cooling" is set on "FanCoil". Additional parameters for "Control Settings Comments function = Heating"...
  • Page 58 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Additional parameters for "Control Settings Comments function = Cooling" send automatic switch-off • deactivated – • activated Manual operation of fan stage • Automatic On / Off –...
  • Page 59 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Note The following parameters are available only when parameter "Additional heating stage" or "Additional cooling stage" is set on "activated". Additional parameters for "Control Settings Comments function = Heating"...
  • Page 60 KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects Objects Object name Data type Flags Control On/Off 1 Bit EIS1 / DPT 1.001 C, W ,T ,U Operating mode 1 Byte EIS6 / DPT 20.102 C, W ,T ,U Superimposed operating mode 1 Byte EIS6 / DPT 20.102...
  • Page 61: Application "Operating Mode Settings

    KNX Technical Reference Manual ® ABB-i-Bus -KNX Millenium Description of applications / objects 11.4 Application "Operating mode settings" With application "Operating mode settings" manual operation can be influenced. Also various indications and forms of display of the device can be specified with it.
  • Page 62 PO box contents of this document without prior notice. 58505 Lüdenscheid The detailed specifications agreed to at the time of ordering apply to all orders. ABB accepts no Freisenbergstraße 2 responsibility for possible errors or 58513 Lüdenscheid incompleteness in this document.

Table of Contents