en | Advanced Features
10

Advanced Features

This chapter details advanced user commands, which are more complicated than those in
Section 9 Common User Commands (unlocked), page 45.
10.1

Alarm Rules

The camera features a powerful alarm rule engine. In its simplest form, an alarm rule defines
those inputs that activate specific outputs. In its more complex form, a rule can be
programmed to take any combination of inputs and keyboard commands to perform a camera
function. There are numerous combinations of alarm inputs and outputs that can be
programmed into twelve (12) alarm rules.
10.1.1

Controlling Alarm Rules

The AUX 69 command allows a user to enable or disable all alarm rules. By default, alarm rules
are enabled until the OFF-69-ENTER command is issued from a keyboard (there is no
corresponding menu item for this command). Disabling alarms rules does not erase the rule,
the camera preserves the user-defined settings and the rule data is restored when the ON-69-
ENTER command is issued.
The OFF-69-ENTER command performs the following actions:
10.1.2

Alarm Rule Examples

Following are two examples for setting up alarm rules.
Example 1: Basic Alarm Rule
Scenario: We want a door alarm contact to:
1.
2.
3.
The sequence to program the above alarm rule example is as follows:
1.
2.
3.
4.
5.
F.01U.276.622 | 1.0 | 2012.09
Disables all alarm rules
Displays the message "Ack and Reset Alarms" if an alarm-rule triggered alarm is active
when the camera receives the disable command. You must acknowledge the alarm before
the rule is disabled.
Prevents the modification of an alarm rule while disabled.
Flash an OSD message (***ALARM 1***) on the display when the alarm is triggered.
Move the camera to a saved position. (For this example, Shot 7.)
Transmit a Bilinx signal over the coax cable to the headend system, such as an Allegiant,
to trigger an alarm response.
Wire the door contact to Input 1 in the camera. This circuit is normally open.
Define the Alarm Input(s): From the Inputs Setup menu, ensure that Alarm Input 1 is set
to N.O. (the default setting for Input 1).
Define the Alarm Outputs:
a.
From the Outputs Setup menu, ensure that Output 5 is set to OSD (the default
setting for Output 5).
b.
Set Output 6 to Shot 7.
c.
Set Output 7 to Transmit (a Bilinx signal to the head end).
Set up the Alarm Rule by selecting the Inputs and Outputs from the Rule Setup menu:
a.
Select Rule 1.
b.
Set the first input to Alarm Input 1.
c.
Set the first output to OSD.
d.
Set the second output to Shot 7.
e.
Set the third output to Transmit.
Enable the Alarm Rule: Highlight Enabled and select YES.
Installation and User Manual
MIC Series 550 Classic Camera