Automatic Operation - Daikin FTX20JV1B Service Manual

Inverter pair wall mounted type j-series
Hide thumbs Also See for FTX20JV1B:
Table of Contents
SiBE041010EA
1.6

Automatic Operation

Outline
Automatic Cooling / Heating Function
When the automatic operation is selected with the remote controller, the microcomputer
automatically determines the operation mode as cooling or heating according to the room
temperature and the set temperature at start-up.
The unit automatically switches the operation mode to maintain the room temperature at the set
temperature.
Detail
1. The set temperature determines the target temperature.
2. The target temperature is calculated as;
3. The thermostat ON/OFF point and operation mode switching point are as follows.
4. During initial operation
Ex: When the target temperature is 25°C
Function and Control
Ts: set temperature (set by remote controller)
Tt: target temperature (determined by microcomputer)
Tr: room thermistor temperature (detected by room temperature thermistor)
C: correction value
Ts = 18 ~ 30°C
Tt = Ts + C
where C = 0°C
(1) Heating → Cooling switching point:
Tr ≥ Tt + 2.5°C
(2) Cooling → Heating switching point:
Tr < Tt – 2.5°C
(3) The thermostat ON/OFF point is the same as the ON/OFF point of cooling or heating
operation.
Tr ≥ Ts : Cooling operation
Tr < Ts : Heating operation
Target temperature – 2.0˚C
= Thermostat OFF
Target temperature – 2.5˚C
Cooling → 23°C: Thermostat OFF
Heating → 26.5°C: Thermostat OFF → 27.5°C: Switch to cooling
Cooling Operation
Target temperature + 2.5˚C
Target temperature + 1.5˚C
= Thermostat OFF
Heating Operation
→ 22°C: Switch to heating
Main Functions
(R11893)
24