Toshiba Compliant Manager BMS-CM1280TLE Installation Manual page 11

Compliant manager bms-cm1280tle
Table of Contents
Compliant Manager
<1> Compliant Manager main/sub selection
OFF: Main
ON: Sub
Normally, this bit is set to OFF.
When two Compliant Manager units are used as a main unit and a sub
unit with the same mode setting, set this bit to OFF (Main) for one unit
and to ON (Sub) for the other unit.
<2> to <5> Control group selection
Control group selection
All groups
Group 1 ~ 16
Group 17 ~ 32
Group 33 ~ 48
Group 49 ~ 64
These bits specify a group range used in the control group selection.
The Compliant Manager for which control group selection is set controls
only groups within the set group range.
* To use the control group selection, set SW1-<2> to <5> and SW2-<5>
to <6>.
<6> Central control/remote controller mode selection
OFF: Central control mode
ON: Remote controller mode
Central control mode:
Remote controller mode: Setting by Compliant Manager is inhibited by
<7> Central control Main/Sub selection
OFF: Main
ON: Sub
This setting is required when multiple Compliant Manager units are
used or another central control unit is used.
(1) Set this bit to OFF when one Compliant Manager unit is used.
(2) When multiple central control units are used as a main unit and sub
units, set to OFF (Main) for one unit and set to ON (Sub) for other
units.
* It is recommended that the "All groups" (control group selection
setting) be set for the central control main unit.
SW2-<6>
OFF
ON
ON
ON
ON
Individual setting by remote controller can be
inhibited by Compliant Manager.
other centra control equipments.
SW1
-
<2> ON
<3> ON
<4> ON
<5> ON
– 11 –
Installation Manual
Factory setting: All OFF
DIP-SW1
1
2 3 4 5 6 7 8
ON
OFF
<8> Central button enable/
disable
OFF:
button operation is
permitted
ON:
button operation is
inhibited
* The
button is disabled in
the remote controller mode
regardless of this setting.
10-EN