4.11.3 Input compensation of multi-speed and remote setting (Pr. 28)

By inputting the frequency setting compensation signal (terminal 1, 2), the speed (frequency) can be
compensated for relative to the multi-speed setting or the speed setting by remote setting function.
Parameter
Name
Number
Multi-speed input
28
compensation selection
REMARKS
⋅ Select the terminal (terminal 1, 2) used for compensation input voltage (0 to ±5V, 0 to ±10) using Pr. 73 Analog input selection.
⋅ When using terminal 1 for compensation input, set "0" (initial value) in Pr. 868 Terminal 1 function assignment.
♦ Parameters referred to ♦
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239 (multi-speed operation)
Pr. 73 Analog input selection
Pr. 59 Remote function selection
Pr. 868 Terminal 1 function assignment

4.11.4 Remote setting function (Pr. 59)

Even if the operation panel is located away from the enclosure, you can use contact signals to perform
continuous variable-speed operation, without using analog signals.
By simply setting this parameter, you can use the acceleration, deceleration and setting clear functions of the
motorized speed setter (FR-FK).
Parameter
Name
Number
59
Remote function selection
Inverter
Forward
rotation
STF
Acceleration
RH
Deceleration
RM
10
Clear
RL
2
SD
5
Connection
diagram for remote setting
Initial Value
0
Refer to page 286
Refer to page 169
Refer to page 285
Initial
Value
0
*
0Hz
ON
Acceleration
ON
(RH)
Deceleration
(RM)
Clear (RL)
Forward
ON
rotation (STF)
Power supply
* External operation frequency (other than multi-speed) or PU running frequency
Frequency setting by external terminals
Setting Range
0
Without compensation
1
With compensation
Refer to page 165
Setting
RH, RM, RL signal
Range
function
0
Multi-speed setting
1
Remote setting
2
Remote setting
3
Remote setting
When Pr. 59 = 1, 2
When Pr. 59 = 3
ON
ON
ON
ON
Description
Description
Frequency setting
storage function
Yes
No
No
(Turning STF/STR OFF clears
remotely- set frequency.)
When Pr. 59 = 1
When Pr. 59 = 2, 3
Time
ON
ON
ON
ON
4
169