External Signal Output Functions - Mitsubishi Electric PAC-SF44SRA Instruction Book

Air conditioning control system
Hide thumbs Also See for PAC-SF44SRA:
Table of Contents
(A) Level signal cases
External input
Contact operation
OFF
ON
ON
OFF
(B) Pulse signal cases
1. Operation will start with the operation signal input, and will stop with the stop signal input.
(This applies to prohibit and permit.)
2. When manual remote control is set to prohibit, the on/off, operation mode, set temperature
and filter reset operations using the manual remote control will be prohibited.
3. Set the pulse duration (contact ON period) to 0.5 sec or more.
1. Level signal
• All operations using this controller and the local remote control are prohibited when
the emergency stop contact is ON.
2. Pulse signal
• All units will continue running even if the ON signal is input. (This also applies to OFF,
prohibit and permit.)

9-2. External signal output functions

• In order to use external signal output, use the 4 wires external output cable that comes with the
unit.
(1) External output
In the case when one or more units are running "ON" and an error occurs in one or more units,
a signal indicating that an error is occurring is output.
(2) External output specifications
CN3
Lead wires (4wires, with black tube)
No.1
No.2
No.3
No.4
1. "ON " is output even when there is "Error ".
Operation status
Emergency stop/Normal
Normal
Emergency stop
Emergency stop
Normal
Yellow
Orange
Red
Brown
ON/OFF
OFF
ON
ON
OFF
Details of each terminal
ON/OFF
Error/Normal
31
Table of Contents
loading

Table of Contents