Mitsubishi Electric PUHZ-RP200 Installation Manual

Hide thumbs Also See for PUHZ-RP200:

Quick Links

Air-Conditioners
PUHZ-RP200, 250YHA2

INSTALLATION MANUAL

For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner
unit.
INSTALLATIONSHANDBUCH
Zum sicheren und ordnungsgemäßen Gebrauch der Klimaanlage das Installationshandbuch gründlich durch-
lesen.
MANUEL D'INSTALLATION
Veuillez lire le manuel d'installation en entier avant d'installer ce climatiseur pour éviter tout accident et vous as-
surer d'une utilisation correcte.
INSTALLATIEHANDLEIDING
Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner
installeert.
MANUAL DE INSTALACIÓN
Para un uso seguro y correcto, lea detalladamente este manual de instalación antes de montar la unidad de
aire acondicionado.
MANUALE DI INSTALLAZIONE
Per un uso sicuro e corretto, leggere attentamente questo manuale di installazione prima di installare il con-
dizionatore d'aria.
EΓXEIPIΔIO OΔHΓIΩN EΓKATAΣTAΣHΣ
Για ασφάλεια και σωστή χρήση, παρακαλείστε διαβάσετε προσεχτικά αυτό το εγχειρίδιο εγκατάστασης πριν
αρχίσετε την εγκατάσταση της μονάδας κλιματισμού.
MANUAL DE INSTALAÇÃO
Para segurança e utilização correctas, leia atentamente este manual de instalação antes de instalar a unidade
de ar condicionado.
INSTALLATIONSMANUAL
Læs venligst denne installationsmanual grundigt, før De installerer airconditionanlægget, af hensyn til sikker og
korrekt anvendelse.
INSTALLATIONSMANUAL
Läs denna installationsmanual noga för säkert och korrekt bruk innan luftkonditioneringen installeras.
MONTAJ ELKİTABI
Emniyetli ve doğru biçimde nasıl kullanılacağını öğrenmek için lütfen klima cihazını monte etmeden önce bu
elkitabını dikkatle okuyunuz.
РУКОВОДСТВО ПО УСТАНОВКЕ
Для осторожного и правильного использования прибора необходимо тщательно ознакомиться с
данным руководством по установке до выполнения установки кондиционера.
FOR INSTALLER
FÜR INSTALLATEURE
POUR L'INSTALLATEUR
VOOR DE INSTALLATEUR
PARA EL INSTALADOR
PER L'INSTALLATORE
ΓΙΑ ΑΥΤΟΝ ΠΟΥ ΚΑΝΕΙ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ
PARA O INSTALADOR
TIL INSTALLATØREN
FÖR INSTALLATÖREN
MONTÖR İÇİN
ДЛЯ УСТАНОВИТЕЛЯ
English
Deutsch
Français
Nederlands
Español
Italiano
Ελληνικά
Português
Dansk
Svenska
Türkçe
Русский
Table of Contents
loading

Summary of Contents for Mitsubishi Electric PUHZ-RP200

  • Page 1: Installation Manual

    Air-Conditioners PUHZ-RP200, 250YHA2 INSTALLATION MANUAL FOR INSTALLER English For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit. INSTALLATIONSHANDBUCH FÜR INSTALLATEURE Deutsch Zum sicheren und ordnungsgemäßen Gebrauch der Klimaanlage das Installationshandbuch gründlich durch- lesen.
  • Page 2: Table Of Contents

    • The unit must be securely installed on a structure that can sustain its • Use only accessories authorized by Mitsubishi Electric and ask a dealer weight. If the unit is mounted on an unstable structure, it may fall down and or an authorized technician to install them. If accessories are incorrectly cause damage or injuries.
  • Page 3: Installation Location

    1. Safety precautions 1.3. Before electric work Caution: • Be sure to install circuit breakers. If not installed, electric shock may result. • Be sure to ground the unit. Do not connect the ground wire to gas or water • For the power lines, use standard cables of sufficient capacity. Otherwise, pipes, lighting rods, or telephone grounding lines. If the unit is not properly a short circuit, overheating, or fire may result. grounded, electric shock may result. • When installing the power lines, do not apply tension to the cables. If the • Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and connections are loosened, the cables can snap or break and overheating molded case circuit breaker) with the specified capacity. If the circuit breaker or fire may result. capacity is larger than the specified capacity, breakdown or fire may result. 1.4. Before starting the test run Caution: • Do not touch any switch with wet hands. Electric shock may result. • Turn on the main power switch more than 12 hours before starting opera- • Do not touch the refrigerant pipes with bare hands during operation. The tion. Starting operation just after turning on the power switch can severely refrigerant pipes are hot or cold depending on the condition of the flowing damage the internal parts. Keep the main power switch turned on during...
  • Page 4: Installing The Outdoor Unit

    2. Installation location 2.4.2. When installing a single outdoor unit (Refer to the last page) Minimum dimensions are as follows, except for Max., meaning Maximum dimen- sions, indicated. 1 Obstacles at rear only (Fig. 2-6) 2 Obstacles at rear and above only (Fig. 2-7) 3 Obstacles at rear and sides only (Fig. 2-8) 4 Obstacles at front only (Fig. 2-9) Fig. 2-3 * When using an optional air outlet guide, the clearance is 500 mm or more. 5 Obstacles at front and rear only (Fig. 2-10) * When using an optional air outlet guide, the clearance is 500 mm or more. 6 Obstacles at rear, sides, and above only (Fig. 2-11) • Do not install the optional air outlet guides for upward airflow. 2.4.3. When installing multiple outdoor units (Refer to the last page) Fig. 2-4 Leave 10 mm space or more between the units.
  • Page 5: Installing The Refrigerant Piping

    4. Installing the refrigerant piping 4.1. Precautions for devices that use R410A refrigerant • Refer to page 3 for precautions not included below on using air condition- ers with R410A refrigerant. • Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil applied to the flared sections. • Use C1220 copper phosphorus, for copper and copper alloy seamless pipes, to connect the refrigerant pipes. Use refrigerant pipes with the thick- nesses specified in the table to the below. Make sure the insides of the pipes are clean and do not contain any harmful contaminants such as sul- furic compounds, oxidants, debris, or dust. Always apply no-oxidation brazing when brazing the pipes, otherwise, the compressor will the damaged. Warning: When installing or moving the air conditioner, use only the specified refriger- ant (R410A) to charge the refrigerant lines. Do not mix it with any other re-...
  • Page 6 4. Installing the refrigerant piping 4.3. Refrigerant piping (Fig. 4-4) Remove the service panel D (three screws) and the front piping cover A (two screws) and rear piping cover B (two screws). 1 Perform refrigerant piping connections for the indoor/outdoor unit when the out- door unit’s stop valve is completely closed. 2 Vacuum-purge air from the indoor unit and the connection piping. 3 After connecting the refrigerant pipes, check the connected pipes and the in- door unit for gas leaks. (Refer to 4.4 Refrigerant pipe airtight testing method) 4 A high-performance vacuum pump is used at the stop valve service port to maintain a vacuum for an adequate time (at least one hour after reaching –...
  • Page 7 4. Installing the refrigerant piping A+B+C+D At time of shipping Outdoor unit Amount of additional refrigerant charge (kg) (kg) 30 m and less 31-40 m and less 41-50 m and less 51-60 m and less 61-70 m and less 71-120 m and less Calculate the RP200 0.9 kg 1.8 kg 2.7 kg 3.6 kg amount of additional No additional refrigerant charge charge necessary using formula pro- RP250 1.2 kg 2.4 kg 3.6 kg 4.8 kg vided below. When length exceeds 70 m When the total length of the piping exceeds 70 m, calculate the amount of additional charge based on the following requirements. Note: If the calculation produces a negative number (i.e. a “minus” charge), of if calculation results in an amount that is less than the “Additional charge amount for 70 m”, perform the additional charge using the amount shown in “Additional charge amount for 70 m”. Main piping: Main piping: Branch piping: Branch piping: Amount of additional Liquid line size Liquid line size Liquid line size...
  • Page 8: Drainage Piping Work

    4. Installing the refrigerant piping 4.8. For twin/triple/quadruple combination (Fig. 4-9) • When this unit is used as a FREE COMPO MULTI unit, install the refrigerant piping with the restrictions indicated in the drawing on the left. In addition, if the restrictions are going to be exceeded, or if there are going to be combinations of indoor and outdoor units, refer to installation instructions for the indoor unit for details about the installation. A Indoor unit Permissible total A+B or A+C...
  • Page 9 6. Electrical work * In case of PEA-400, 500 (No.1 Outdoor) A Power supply PUHZ-200, 250 PEA-400, 500 B Earth leakage breaker ( TB4-1) (TB4-2) C Circuit breaker or local switch D LCD remote controller E Outdoor unit F Indoor unit G Power cable wiring H Indoor/Outdoor connection wiring I Grounding (No.2 Outdoor) PUHZ-200, 250 * In case of PEA-200, 250 * In case of PEA-400, 500 A Outdoor unit B Indoor unit...
  • Page 10: Test Run

    6. Electrical work Warning: In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between pow- er line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when the power is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-poles type. WIRING SPECIFICATIONS FOR 220-240 V 50 Hz (INDOOR-OUTDOOR CONNECTING CABLE) Cross section of cable Wire size (mm Number of wires Polarity L (m)*6 Round Clockwise : S1-S2-S3 (30) * Pay attention to stripe of yellow and green Flat Not applicable Not applicable (Because center wire has no cover finish) Flat From left to right : S1-Open-S2-S3 (18) Round Clockwise : S1-S2-S3-Open (30) *Connect S1 and S3 to the opposite angle *1 : Power supply cords of appliances shall not be lighter than design 60245 IEC or (3C Flat cable × 2) 227 IEC. *2 : In case that cable with stripe of yellow and green is available. *3 : In case of regular polarity connection (S1-S2-S3), wire size is 1.5 mm *4 : In case of regular polarity connection (S1-S2-S3). *6 : Mentioned cable length is just a reference value.
  • Page 11: Special Functions

    7. Test run 7.2. Unit replacement operation ► When reusing existing pipes that carried R22 refrigerant, replacement op- (1) Set SW8-2 from ON to OFF (when ending a replacement operation of less eration must be performed before performing a test run. than 2 hours). • If new pipes are used, these procedures are not necessary. • Because the replacement operation restarts each time SW8-2 is set from Replacement operation procedures OFF to ON, always perform the replacement operation for longer than the 1 Supply power. stipulated time. 2 Set DIP switch SW8-2 on the control board of the outdoor unit to ON to start Required replacement operation times replacement operation. Pipe Length Replacement Operation Time * The replacement operation is performed using the cooling system. Cool air 0 to 20 meters 30 minutes or more will flow from the indoor unit during the replacement operation. 21 to 30 meters 45 minutes or more * During the replacement operation,...
  • Page 12: System Control

    8. Special Functions 8.3. Refrigerant collecting (pump down) Perform the following procedures to collect the refrigerant when moving the indoor 3 Because the unit automatically stops in about two to three minutes after the unit or the outdoor unit. refrigerant collecting operation (LED1 and LED2 are lit), be sure to quickly 1 Supply power (circuit breaker). close the gas stop valve. When LED1 and LED2 are lit and the outdoor unit is * When power is supplied, make sure that “CENTRALLY CONTROLLED” is not stopped, open the liquid stop valve completely, and then repeat step 2 after displayed on the remote controller. If “CENTRALLY CONTROLLED” is dis- three minutes have passed.
  • Page 13 This product is designed and intended for use in the residential, commercial and light-industrial environment. The product at hand is • Low Voltage Directive 2006/95/ EC based on the following • Electromagnetic Compatibility Directive 89/336/ EU regulations: Please be sure to put the contact address/telephone number on this manual before handing it to the customer.