Advanced Setup - RBI Futera III Manual

Finned copper tube gas boilers & water heaters 500 to 4,000 btuh input
Table of Contents
7
Control menus and adjustments
Table 8

ADVANCED SETUP

To enter Setup: From STANDBY, hold
Then press
with cursor on SETUP.
Make sure there is no call for heat at the boiler before attempting to perform setup adjustments.
To return to STANDBY, press/release
Level 1
Level 2
next item
next item
to select
to select
back one level
DISTRIBUTED CTRL
CONTROL
H-NET MASTER
H-NET ADDRESS
MODBUS ADDRESS
MODULAR BOILER SET
ADD BOILER DELAY
SHED BOILER DELAY
MODULATE DELAY TIME
MOD MAX - LAST FIRE
ADAPTIVE MOD
MOD MODE
DROP DOWN
DELAY RELEASE
PID (FACTORY)
FIRING MODE
FIRING MODE
MASTER FIRST
SENSORS
SENSOR #
TYPE
CALIBRATE
CALIBRATE
P/N HN-IOM-1 82-0331 Copyright 2009 Mestek, Inc.
Finned copper tube gas boilers & water heaters – Control manual
menus (see Table 9, page 35 for explanations)
for 5 seconds. (If SKIP PASSWORD is set to OFF, you will have to enter the password.)
until the display returns to standby, or turn boiler ON/OFF switch off, then on.
Level 3
Default {Range}
next item
to accept value and return to previous menu level
to select
back one level
HNET
YES (Display only, not changeable here) (MEMBER boilers will show NO, and
addresses must be set from 2 to 16.)
Master default = 255 (not changeable); Member default = 2 (Range = 2 to 16)
Default = 1; Range = 1 to 247
10 minutes {0 to 15 minutes}
2 minutes {0 to 15 minutes}
10 seconds {0 to 60 minutes}
50% {25 to 100%}
ADAPTIVE {ADAPTIVE or ORIG KN}
ON PILOT {ON PILOT or IMMEDIATELY}
0 seconds {0 to 600 seconds}
Factory set, not adjustable
TRUE ROTATION {TRUE ROTATION, LAST ON FIRST OFF, FIRST ON FIRST OFF}
OFF {ON or OFF}
OUTSIDE {OUTSIDE, SUPPLY, RETURN, HEADER, 5, 6}
TYPE Z {TYPE Z (10K), ON/OFF, NONE}
NO {YES or NO}
If YES is selected:
(See explanation, Table 9, page 35)
(continued)
to change value
Typical line
(Display shows four lines at a
time; cursor indicates active
line)
CONTROL
H-NET
H-NET MASTER
YES
LOCAL ADDRESS
255
MODBUS ADDRESS
1
ADD DELAY TIME
10 MINUTES
0 SECONDS
SHED DELAY TIME
2 MINUTES
0 SECONDS
MODULATE DELAY TIME
0 MINUTES
10 SECONDS
STOP MOD MAX
% 50
PID (FACTORY)
FIRING MODE
TRUE ROTATION
MASTER FIRST
OFF
SENSOR ASSIGNMENTS
SENSOR #
OUTSIDE
TYPE
TYPEZ
CALIBRATE?
NO
PLACE A PRECISION
1K OR 10K RESISTOR
ON CHANNEL # 1
TRIM OHMS =
120
33