Honeywell T8011R Installation Instructions Manual
Honeywell T8011R Installation Instructions Manual

Honeywell T8011R Installation Instructions Manual

Programmable heat pump thermostat
Hide thumbs Also See for T8011R:
Programmable Heat Pump Thermostat
APPLICATION
The T8011R Heat Pump Thermostat provides 24 Vac
control of a two-stage heating and one-stage cooling heat
pump system with manual changeover from heat to cool.
First stage heating and cooling cycle rates are fixed at 3
cph. Second stage heating cycle rate is selectable at
3, 4, 5, 6, 9 or 12 cph. Temperature indication can be set
for °F or °C.
The T8011R Heat Pump Thermostat is powered directly
from the system transformer. Setpoints are held perma-
nently in memory and retained during power outages.
The T8011R TRADELINE® model includes a thermostat,
wallplate and owner's guide. A 7 3/8 in. (188 mm) x 5 3/4
in. (146 mm) decorator cover plate (for covering wall
marks) is available separately. Order Honeywell part no.
209649A (taupe) or part no. 209649B (white).
MERCURY NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash. Dispose of it properly.
Contact your local waste management authority for
instructions regarding recycling and the proper
disposal of a control.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
Model
System
T8011R
Heat Pump
®U.S. Registered Trademark
Copyright © 2002 Honeywell •
Table 1. Description of T8011R Thermostats.
Changeover
System Selection
Manual
Cool-Off-Heat-Em. Ht.
• All Rights Reserved
INSTALLATION INSTRUCTIONS
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
CAUTION
Hazardous Voltage
Can damage heating/cooling system.
Disconnect power at furnace or main breaker/fuse
box.
Location
Install the thermostat about 5 ft (1.5m) above the floor in
an area with good air circulation at average temperature.
See Fig. 1. Do not install the thermostat where it can be
affected by:
— drafts or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from the sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
Mounting Wallplate to Wall
IMPORTANT
Level for appearance only. The thermostat
functions normally even when not level.
Mount wallplate and the T8011R with the screws provided
(see Fig. 2) as follows:
1. Place the wallplate at the desired location on the
wall.
2. Pull the thermostat wire through the wallplate
entrance hole.
3. Fasten the wallplate to the wall using the anchors
and screws provided.
4. After wiring the wallplate, plug the hole with non-
flammable insulation to prevent drafts from affecting
the thermostat; see Wiring section.
Fan Selection
Auto-On
X-XX UL
T8011R
Powering Method
Hardwired
69-1435-1
loading

Summary of Contents for Honeywell T8011R

  • Page 1: Mounting

    Level for appearance only. The thermostat functions normally even when not level. Mount wallplate and the T8011R with the screws provided INSTALLATION (see Fig. 2) as follows: 1. Place the wallplate at the desired location on the When Installing this Product…...
  • Page 2: Wiring

    T8011R PROGRAMMABLE HEAT PUMP THERMOSTAT 5 FEET [1.5 METERS] M11338 Fig. 1. Typical location of thermostat. FOR STRAIGHT INSERTION STRIP 5/16 IN. (8 MM) TERMINAL WALL SCREW FOR WRAPAROUND WALL STRIP 7/16 IN. (11 MM) ANCHORS (2) MOUNTING WALLPLATE SCREWS (2) M12202 Fig.
  • Page 3 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. M11333 REMOVE JUMPER, WHEN SUPPLIED, FOR SYSTEMS WITH SEPARATE HEATING COMPRESSOR CONTACTOR (W1 SEPARATE FROM Y). Fig. 5. T8011R two stage heat, one stage cool wiring diagram with manual changeover. 69-1435–1...
  • Page 4: Mounting Thermostat To Wallplate

    T8011R PROGRAMMABLE HEAT PUMP THERMOSTAT NOTE: All four steps must be completed to save Mounting Thermostat To Wallplate changes to the °F/°C indication and the heat cycle rate. 1. Slide SYSTEM switch to the Off position. 2. Engage the tabs at the top of the thermostat and 1.
  • Page 5: Operation

    T8011R PROGRAMMABLE HEAT PUMP THERMOSTAT 3. Setting Heat Cycle Rate (see Table 2 for cycle rate OPERATION options and equipment). Press the ▲ key to display the current Setting FAN and SYSTEM Switches heat cycle rate setting of 3, 4, 5, 6, Fan and system settings are controlled manually by using 9 or 12 cph.
  • Page 6: Setting Current Time And Day

    T8011R PROGRAMMABLE HEAT PUMP THERMOSTAT Setting Current Time and Day CHECKOUT 1. To Set Current Time. CAUTION Press Select twice. Damage To Compressor Possible. Operating at too low of an outdoor temperature may cause compressor damage. M12591A Do not operate cooling if outdoor temperature is Press ▲...