Compressor Sensor System Abnormality - Daikin CTXU25G2V1B Service Manual

Inverter multi system with humidifying g-series
Hide thumbs Also See for CTXU25G2V1B:
Table of Contents
Troubleshooting
2.23

Compressor Sensor System Abnormality

H0
Remote
Controller Display
Outdoor Unit LED
A5
Display
Method of
Fault condition is identified by DC current which is detected before compressor startup.
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Replace the outdoor unit PCB.
134
55 ( - )
When the DC voltage is 50 V or less.
Defective PCB
Harness disconnection / defective connection
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
SiBE12-908
Service Diagnosis