2-9. EXPANSION VALVE CONTROL (LEV CONTROL)

(1) Outline of LEV control
The LEV basic control is comprised of setting LEV opening degree to the standard opening degrees set for each opera-
tional frequency of the compressor. However, when any change in indoor/outdoor temperatures or other factors cause
air conditioning load fluctuation, the LEV control also works to correct LEV opening degree based on discharge tempera-
ture (Shell temperature) of the compressor, developing the unit's performance.
Control range
Actuating speed
Opening degree adjustment
Unit OFF
Remote controller ON
During 1 to 15 minutes after compressor
starts
More than about 15 minutes have passed
since compressor start-up
Thermostat OFF
Thermostat ON
Defrosting in HEAT mode
(2) Time chart
Minimum: 33 pulses (MUZ-A09/12/15/17 MUY-A15/17)
Maximum: 500 pulses
Open: 40 pulses/second
Close: 90 pulses/second
LEV opening degree is always adjusted in opening direction. (When reduc-
ing the opening degree, LEV is once over-closed, and then adjusted to the
proper degree by opening.
LEV remains at maximum opening degree (reaches maximum opening
degree approximate in 15 minutes after compressor stops)
LEV is positioned. (First full-closed at zero pulses and then positioned.)
LEV is fixed to standard opening degree according to operational frequen-
cy of compressor.
LEV opening degree is corrected to get target discharge temperature of
compressor.
(For lower discharge temperature than target temperature, LEV is correct-
ed in closing direction.)
(For higher discharge temperature than target temperature, LEV is cor-
rected in opening direction.)
It may take more than 30 minutes to reach target temperature, depend-
ing on operating conditions.
LEV is adjusted to exclusive opening degree for thermostat OFF.
LEV is controlled in the same way as that after the compressor has started
up.
LEV is adjusted to open 500 pulses
Air conditioner ON
Positioning
Opening degree is
corrected according
to discharge
temperature.
Standard
(Refer to (3))
opening
degree
About 15 minutes
ON
59 pulses (MUZ-A24 MUY-A24 MUZ-GA MUY-GA)
54 pulses (MUZ-FD MUZ-FE MUZ-GE MUY-GE)
58 pulses (MUZ-D MUY-D)
Air conditioner OFF
(thermostat off)
Commanded
to open
Time
OFF Time