Messages List - GE Digital Energy LP 33 Series Operating Manual

50 & 60 kva
Hide thumbs Also See for Digital Energy LP 33 Series:
Table of Contents
6.2.2

Messages list

Are defined messages:
Code
Message
RECTIFIER
4111
MAINS OK
UPS SHUTDOWN
4114
(LOW BATT VOLTAGE)
BATTERY TEST
4119
STARTED
BATTERY TEST
4120
STOPPED
ISMAX DETECTION
4141
BOOSTER
RECTIFIER
4161
ON
RECTIFIER
4162
OFF
GENERATOR
4163
ON
GENERATOR
4164
OFF
INVERTER
4302
CANNOT BE
TURNED ON
INVERTER
4303
CANNOT BE
TURNED OFF
INVERTER
4361
ON
Modifications reserved
OPM_LPS_3UO_50K_60K_0US_V010.doc
all the recorded events which are referred to the operation status coherent
with the normal situation of the UPS.
Rectifier input mains is again within the admitted tolerance
(voltage, frequency and phase).
The UPS is in Load OFF status, resulting in Battery supply for
the power supply.
Should the Battery voltage decrease to a value below of the
one set in a parameter, then power supply will shutdown to
avoid damage to the Battery
Start of manual or automatic battery test.
Rectifier output voltage is decreased to the value defined by
respective parameter.
End battery test.
End of manual or automatic battery test.
Rectifier output voltage is restored to floating voltage.
Detection of persistent booster (Is) current limitation.
Rectifier received the command to switch ON.
Rectifier received the command to switch OFF for:
input mains out of tolerance / EPO / UDC max.
Customer Interface (X1 / 11, 22) received a Gen set ON
signaling.
Operating
parameters.
Customer Interface (X1 / 11, 22) received a Gen set OFF
signaling.
Function bypass enabled dependent on setting of respective
parameter.
Inverter cannot be switched on because one of the following
conditions are still present:
• Overtemperature;
• Low battery voltage;
• Inverter fuses;
• Overload;
• K7 opening failure;
• High battery voltage;
• DC low;
• EPO (Emergency Power Off).
Inverter cannot be switched OFF, because the load cannot be
transferred
synchronizing, bypass blocked).
The command to start the inverter has been activated on the
control panel.
Meaning
mode
dependent
on
on mains (voltage out of tolerance, not
setting
of
respective
Page 26/57
Operating Manual LP 33 Series 50 & 60 kVA
Table of Contents