INSTRUCTIONS FOR INSTALLATION AND SERVICING TURBOmax VUW 242/1 E TURBOmax VUW 282/1 E Wall hung room sealed fan assisted combination boilers HEATING, CONTROLS, HOT WATER.
1. Introduction The TURBOmax range consists of Note: This boiler must be installed models with outputs for domestic hot and serviced by a competent person water of 24 and 28 kW. The boiler is in accordance with the Gas Safety easily sited on any internal wall and (Installation and Use) Regulations can be installed with either a horizontal...
2. Boiler specification 2.1 Technical data TURBOmax VUW 242/1 E VUW 282/1 E units Countries of Destination GB, IE Maximum CH heat input 29.3 34.2 (100,000) (116,600) (Btu/h) CH heat output range 9.6-24.0 11.2-28.0 (32,800-81,900) (38,200-95,500) (Btu/h) Maximum DHW heat input 29.3 34.2 (100,000)
2.2 Dimensions (All dimensions in mm) max. 995 * 1a Air/flue duct to the rear max. 995* 1b Air/flue duct to the side Appliance bracket Heating system return (22 mm) Cold water connection (15 mm) Gas connection (15 mm) Hot water connection (15 mm) Heating system flow (22 mm) Pressure relief valve outlet in BSP)
2.4 Function diagram 1 Air duct 2 Air pressure switch 3 Combustion chamber 4 Temperature sensor (NTC) 5 Ignition electrodes 6 Modulating burner 7 Overheat thermostat 8 Fully modulating automatic gas valve 9 DHW heat exchanger υ 10 Indicator lights (LED’s) 11 Maximum radiator temperature control 12 Maximum hot water temperature...
3. General requirements 3.1 Related documents 3.2 Boiler location The installation of the boiler must be The location chosen for the boiler must in accordance with the relevant permit the provision of a satisfactory requirements of Gas Safety (Installation flue termination. The location must and Use) Regulations 1994, Health also provide adequate space for and Safety Document No.
3.3 Gas supply The gas supplier should ensure the availability of an adequate supply of gas. A gas meter may only be connected to the service pipe by the supplier of gas or their contractor. An existing meter should be checked to ensure that it is capable of passing the rate of gas supply required.
Page 9
3.4.1 Flue Termination 1. The terminal must be positioned such that the combustion products can disperse freely at all times. 2. In certain weather conditions a plume of water vapour may be visible from the flue terminal. Positions where this could be a nuisance should be avoided.
3.5 Air supply 3.6 Electricity supply 3.7 Guide to system requirements Detailed recommendations for air A 230 V~ 50Hz single phase supply are given in BS 5440: Part 2. electricity supply fused to 3 amps must 3.7.1 Water circulation system be provided in accordance with the It is not necessary to have an air vent Detailed recommendations for the...
Page 11
3.7.2 Filling and make up Heating The system should be filled with water circuit via a separate filling point fitted at a Mains Double check return convenient position on the heating Hose water valve assembly circuit. Where local Water Authority unions supply Regulation allows, a temporary...
Page 12
A DHW expansion vessel kit (Art. No. 8070) is available as an optional 800 1000 1200 1400 1600 accessory from Vaillant Ltd. This fig. 8 expansion vessel kit should be fitted to the boiler whenever either a stop valve of the loose jumper type or a...
4. Boiler installation sequence 4.1 General The boiler should be mounted on a flat and vertical area of wall of sufficient area for the boiler plus the required minimum clearances for installation and servicing (fig. 10). These are shown on the installation template supplied with the boiler and are: 5 mm either side of the boiler...
4.4 Installing the flue system Note: To allow fitting of the bottom boiler cover, the left hand tab (2, fig. At this stage install the flue system 16) should be folded upwards where (refer to separate installation pipes are fitted in the left hand void. instructions supplied).
4.5.3.4 Gas supply The boiler is supplied with a 20 x 15 mm gas service valve (10, fig. 14). Fit the 20 mm compression fitting to the boiler gas inlet (11, fig. 14) and tighten. Install a gas supply pipe not less than 15 mm diameter and connect to the gas service valve.
Page 18
Loosen screws on the 95 mm diameter Loosen the screws of the 95 mm x 55 mm wide clamp (6, fig. 21) and diameter x 55 mm wide clamp (1, fig. push over the air duct. 22) and push over the air duct of the Remove screws and sealing washer air/flue duct assembly.
IMPORTANT Ensure that all cords Drill two holes 3 mm diameter pass through the terminal box entrance through the air duct clamp (2. Fig 24) grommets and are securely fixed by ensuring that the drill does not pene- the cable clamps. Ensure that the trate the flue duct.
If a frost thermostat is to be fitted it should be connected in parallel across DO NOT USE! MAINS terminals 3 and 4. SUPPLY 230 V 4.8.2.3 Vaillant optional Plug-in timer ROOM SWITCH 50 Hz 3 A FUSE Accessories THERMOSTAT...
Page 21
4.8.3 Thermostatic radiator valves The boiler has a built-in automatic bypass valve making it ideal for use in systems with thermostatic radiator valves (no separate system bypass is required). For optimum fuel economy it is recommended that where TRVs are used they are used in conjunction with a programmable roomstat or separate timer and room thermostat to ensure...
5. Commissioning 5.1 Preliminary electrical checks Check the electrical installation by carrying out short circuit, earth continuity and resistance to earth tests and a check for correct polarity. 5.2 Gas supply The complete gas installation including the gas meter must be inspected, tested for soundness and purged in accordance with BS 6891.
5.4 Filling the heating system The boiler primary circuit and the heating system should be filled using a filling method as described in Section 3.7.2. Ensure that the boiler CH service valves (3, fig. 31) are open. Partially open the filling valve and allow water to enter the system.
5.6 Initial lighting • Check that the boiler combustion chamber (5, fig. 33) is correctly fitted. • Ensure the cold water shut-off valve (4, fig. 34) is open by turning anti-clockwise. • Open the gas service valve (2, fig. • Check that the CH service valves (1 and 5, fig.
At this point the preset maximum tolerance shown, contact Vaillant Ltd. Technical Department). domestic hot water flow rate can be • Turn off the hot tap. adjusted if required. • Remove U gauge. Tighten the sea- Note: The water flow limiter built ling screw (1, fig.
Page 26
5.9 Adjusting the central heating output (range rating) The TURBOmax is fully modulating for central heating, and it is therefore not necessary to range rate the central heating. However, if desired, it is possible to range rate the boiler, as follows: •...
5.10 Functional Checks 5.10.1 Introduction The Vaillant TURBOmax is equipped with a set of diagnostic indicator lights to show the operational status of the boiler. A functional check of DHW and CH operation can be made using these indicator lights (fig. 41).
5.11 Checking flame 5.13 Fitting case supervision device Attach top door panel by slotting side clips (1, fig. 42) into holes in side Operate the boiler and turn off the panel and sliding panel down to gas supply at the boiler gas service secure.
(7, fig. made for a Maintenance Agreement. 44). A suitable combustion analyser Please contact Vaillant Service can be connected to this point to Solutions (0870 6060 777) for further establish the combustion performance details.
6.2 Routine maintenance 6.2.1 Remove front case Remove bottom hinge screw (1, fig. 46) and pull lower door panel forward and down to release it from the top hinge pin (2, fig. 46). Slide the top panel up to release retaining clips (1, fig.
6.2.5 Inspect burner With the combustion chamber front cover and heat exchanger front panel removed it is possible to inspect the burner. Any deposits should be removed with a soft brush. Check the condition of the ignition and monitoring electrodes. 6.2.6.
7. Parts replacement 7.1.2 Releasing CH water pressure and draining the boiler (fig. 50) • Isolate electrical supply to boiler. IMPORTANT: • Before starting any maintenance Remove combustion chamber cover work: as in section 7.1.5. • Turn off boiler CH service valves •...
Page 33
7.1.3 Removal of front casing 7.1.7 Removal of heat exchanger front panel. 7.1.3.1 Door (fig. 52) • Remove bottom hinge screw (1) • Remove the five screws (1 and 3, and pull the bottom door panel fig. 47) securing the heat exchanger forwards and down to release it and remove the panel by gently from top hinge pin (2).
7.2 Replacement of fan (fig. 55) • Isolate the boiler from the electrical supply. • Remove front casing as in section 7.1.3, and remove combustion chamber cover as in section 7.1.5. • Disconnect the electrical connections from the fan. • Remove the 2 fan securing screws (4) and remove fan.
7.4 Replacement of burner fig. 57 • Isolate the boiler from the electrical supply. • Remove front casing as in section 7.1.3. • Remove combustion chamber cover as in section 7.1.5 • Disconnect the ignition and flame sensing electrode leads (1, fig. 57). •...
7.6 Replacement of NTC temperature sensor Note: The NTC temperature sensor is an extremely reliable component and as such is unlikely to fail. Before changing the NTC please check that it is defective - see section 8 - fault finding. •...
7.7.1 Replacement of modulating 7.8 Replacement of main heat regulator exchanger • • Isolate the boiler from the electrical Turn off the boiler as in section 7.1.1. supply. • • Remove front casing as in section Remove front casing as in section 7.1.3 and remove combustion 7.1.3 .
7.9 Replacement of CH 7.9.2 Boiler installed with air flue duct to the rear, or vertical flue expansion vessel installation (where less than In the unlikely event of a failure of the 300mm vertical clearance exists CH expansion vessel follow procedure above the boiler) 7.9.1 or 7.9.2 depending upon the EITHER...
• Pull pump forward to remove. 7.10 Replacement of • Fit new '0' rings (supplied with transformer pump) to pump connections. • Isolate boiler from the electricity • Re-assemble in reverse order. supply. • Carry out electrical checks • Remove front casing as in section (see section 5.1).
7.13 Replacement of automatic 7.15 Replacement of diverter air release valve • • Turn off boiler as in section 7.1.1. Turn off boiler as in section 7.1.1. • • Remove front casing as in section Remove front casing as in section 7.1.3.
7.15.1 Replacement of water section diaphragm (fig. 72). • Turn off boiler as in Section 7.1.1. • Remove bottom cover as in section 7.1.3.3. • Open hot water taps. • Remove clip (2), undo union (3) • Remove 6 screws (4). •...
7.18 Replacement of DHW microswitch. • Isolate appliance from electricity supply. • Remove front casing as in section 7.1.3. • Lower front control panel as in section 7.1.6. • Lift off microswitch retaining ’bow’ spring, • Pull microswitch forward to remove from mounting bracket and disconnect wires.
7.20 Removal of printed circuit boards (PCBs) Before commencing work on PCB replacements carry out the following:- Diagnose that the boards require changing using the fault finding guide (see section 8: Fault finding). • Turn off the boiler as in section 7.1.1.
8. Fault finding Flame indicator (yellow) 4) Ensure the heating system is full of Illuminates when flame is recognised water and charged to approx. by the flame monitoring system. 1 bar. If not refill the system and 8.1 Introduction vent (see section 5.4: Filling the (A flashing indicator shows that the The TURBOmax has built in diagnostic NTC sensor is broken, not connected...
9 Electrical diagrams 9.1 Functional Flow diagram: VUW 242/1 E, 282/1 E CONTROL BOX MAIN SWITCH MAIN MAIN SWITCHBOARD TRANSFORMER OVERHEAT POWER SUPPLY THERMOSTAT PRESSURE CONTROL BOARD SWITCH plug in connector FAN- CONTROL IGNITION IGNITION ELECTRODES TRANSFORMER plug in connector PUMP WATER-PUMP SELECTOR...
Page 59
11. Supplementary L.P.G. Appliances: information for VUW 242/1 EB TURBOmax VUW 282/1 EB The appliance delivered is designed Related documents to be for use with LPG. supplemented by: Please read the instructions for BS 5482: CP for domestic butane installation therefore as follows: and propane gas burning installations Part 1:...
Page 60
HEATING, CONTROLS, HOT WATER Head Office Sales 01634 292310 Vaillant Ltd., Vaillant House, Service Solutions 0870 6060 777 Medway City Estate, Trident Close, Technical Advice 01634 292392 Training 01634 292370 Rochester, Kent ME 2 4 EZ...