User Address
unusedF1
Future use.
unusedF2
Future use.
tTuncos
The time until the next occupancy state in minutes.
tUserState
The thermostat internal user state flag. Some of the values are listed in hexadecimal; 01 = Normal operating
state.
tValidDuctTemp
Status of thermostat duct temperature sensor. True = valid; False = invalid.
tValidLocalTemp
Status of thermostat internal space temperature sensor. True = valid; False = invalid.
tValidRemoteTemp
Status of thermostat remote space temperature sensor. True = valid; False = invalid.
UnitCool
UnitCool reports the current percentage of cooling stages turned on in Cool mode. If cooling is not configured,
UnitCool is invalid.
UnitEcon
If an economizer is configured, UnitEcon reports the percentage that the economizer damper is open. If no
economizer is configured, UnitEcon reports invalid.
UnitFan
Unit Fan reports the fan speed in percentage of full speed. If the fan is off, UnitFan reports zero.
UnitHeat
UnitHeat reports the current percentage of heating stages turned on in Heat mode. If heating is not configured,
UnitHeat is invalid.
UnitSecHeat
UnitSecHeat reports the current percentage of emergency heating stages turned on when emergency heating
is configured in a heat pump application. If emergency heating is not configured, UnitSecHeat is invalid.