Emerson Liebert Xtreme Density Design Manual

Emerson Liebert Xtreme Density Design Manual

Xtreme density series
Table of Contents
Liebert
Xtreme Density
®
System Design Manual
Precision Cooling
For Business-Critical Continuity™
Table of Contents
loading

Summary of Contents for Emerson Liebert Xtreme Density

  • Page 1 Liebert Xtreme Density ® System Design Manual ™ Precision Cooling For Business-Critical Continuity™...
  • Page 3: Table Of Contents

    YSTEM ESCRIPTION European Union Fluorinated Greenhouse Gas Requirements ......2 Direct and Indirect System Configurations ........2 Liebert XDO—Overhead Cooling Module .
  • Page 4 3.20 Display Panel and Remote Temperature/Humidity Sensor Locations ....29 XD C IEBERT OOLING XDCF ..........30 IEBERT Liebert XDO Standard Features .
  • Page 5 Figure 24 Hydraulic diagram ............. . 24 Figure 25 Bypass flow controller details, dimensions .
  • Page 6 Table 1 Liebert XD field-installed port kits header connection size ......10 Table 2 Maximum and minimum modules supported by a Liebert XDP or Liebert XDC .
  • Page 7: System Description

    YSTEM ESCRIPTION The Liebert XD™ family of cooling units delivers efficient, sensible cooling to high-heat environ- ments. Liebert XD systems are designed to cool computer racks and hot zones in a data center or com- puter room without taking up expensive floor space for cooling components. The Liebert XD family includes: •...
  • Page 8: European Union Fluorinated Greenhouse Gas Requirements

    European Union Fluorinated Greenhouse Gas Requirements Stationary air conditioning, refrigeration, heat pump equipments and stationary fire protection sys- tems in the European Community market and operating with fluorinated greenhouse gases (f-gas), such as R407C, R134a, R410A, must comply with the F-Gas Regulation: (EC) No. 842/2006 (F-gas). The regulation prohibits, among other actions, venting fluorinated greenhouse gases to the atmo- sphere.
  • Page 9: Liebert Xdo-Overhead Cooling Module

    Liebert XDO—Overhead Cooling Module The Liebert XDO ceiling-mounted cooling module draws in hot air rising from densely populated cab- inets, passes it over the Liebert XDO’s coils and exhausts cooled air downward into the cold aisle. The unit is available with optional, flexible metal pipes with quick-connect couplings at each end for easy connection to the refrigerant distribution pipes.
  • Page 10: Liebert Xdv-Vertical, Above-Cabinet Cooling Module

    Liebert XDV—Vertical, Above-Cabinet Cooling Module The Liebert XDV is installed on top of or above a rack enclosure. It is available with optional flexible metal pipes with automatic shutoff with quick-connect couplings at the ends for easy connection to the refrigerant distribution pipes. The Liebert XDV may be set up in either of two ways: •...
  • Page 11: Liebert Xdh-Horizontal Cooling Module

    Liebert XDH—Horizontal Cooling Module The Liebert XDH cooling module is designed to be placed within a row of server enclosures in a hot aisle-cold aisle arrangement. The Liebert XDH has dual refrigeration circuits and is available in a half-rack-width unit. The Liebert XDH is intended for use with a Liebert XD pumped refrigerant cool- ing system, supplied by either a Liebert XDP or Liebert XDC.
  • Page 12: Liebert Xdcf

    Liebert XDCF The Liebert XDCF is a self-contained module designed to cool Egenera’s BladeFrame EX cabinets and equipment without exhausting heat into the room. Two modules (top and bottom) may be mounted on the rear of a BladeFrame cabinet. CF modules consist of a sheet-metal frame, coil and filter dryer. It has no moving parts and needs no electricity.
  • Page 13: Liebert Xda-Air Flow Enhancer

    Liebert XDA—Air Flow Enhancer The Liebert XDA is a fan unit that boosts the airflow through densely populated enclosures, removing hot spots from within the racks. One or two units can be mounted on the rear of most rack enclosures. Figure 9 Liebert XDA—air flow enhancer—on Liebert Foundation enclosure System Description...
  • Page 14: Liebert Xdp-Pumping Unit

    Liebert XDP—Pumping Unit The Liebert XDP isolates the building’s chilled water circuit from the pumped refrigerant circuit. The Liebert XDP circulates refrigerant to Liebert XDCF, Liebert XDH, Liebert XDO or Liebert XDV mod- ules while preventing condensation by maintaining the refrigerant’s temperature above the dew point.
  • Page 15: Liebert Xdc-Refrigerant Chiller

    Liebert XDC—Refrigerant Chiller The Liebert XDC is an indoor chiller that connects directly to the Liebert XD cooling modules and pro- vides refrigerant circulation and control. The Liebert XDC keeps the refrigerant temperature above the dew point and eliminates the need for a separate pumping unit in the direct system configuration. The Liebert XDC employs two sets (for redundancy) of remote sensors to determine the temperature and humidity in the air and instantly adjusts refrigerant supply temperature to compensate for changing conditions.
  • Page 16: Liebert Xd Piping

    Connection to the prefabricated piping assembly is a threaded coupler. For information on acquiring the correct kit for your installation refer to DPN000780_Rev1, available by calling 1-800-LIEBERT and from your local Emerson Network Power representative. Prefabricated Headers Field piping kits are available in several versions •...
  • Page 17: Starting A New Equipment Cooling Project

    TARTING A Determining Cooling Equipment Needs Is adequate space available for a Liebert XD installation? Is the hot aisle/cold aisle approach being utilized for this room design or can it be utilized in this room design? Is redundant cooling equipment required? Are there access considerations for all components (possible rigging problems) What heat load growth is anticipated over the next few years? How are the cabinets going to be populated (density of heat generation)?
  • Page 18: Implementing A Hot-Aisle/Cold Aisle Design

    Implementing a Hot-Aisle/Cold Aisle Design A best practice is to use rows of equipment racks in an alternating arrangement of cold aisles and hot aisles. This is best accomplished when the layout of the file-server farm area is first being planned, and it is exceedingly more difficult to accomplish when the computer room is already populated with operating hardware.
  • Page 19: Designing A Liebert Lxd Solution

    ESIGNING A IEBERT Liebert XD systems are intended for use with precision air conditioning equipment, such as the Lie- bert Deluxe System/3 and Liebert DS. The precision air conditioning equipment is required to control the room’s humidity and to filter the air. The Liebert XD systems provide efficient, highly effective heat removal (sensible cooling only), and provide no dehumidification.
  • Page 20: Selecting Liebert Xd Cooling Modules

    Selecting Liebert XD Cooling Modules The next step is to select the Liebert XD cooling modules to be configured into the solution. Liebert XD modules that use pumped refrigerant can be connected to the same Liebert XDP/Liebert XDC pip- ing circuit. This includes the Liebert XDCF, Liebert XDH, Liebert XDO and Liebert XDV. Generally, the Liebert XDO is selected for use in new installations or renovations where the unit can be installed on the ceiling or in the overhead space.
  • Page 21: Liebert Xdo Placement

    (1.8m), overall performance of the system may be negatively affected and gaps in cooling may occur. Emerson recommends installing one Liebert XDO at the end of each aisle being cooled and to space the remainder between these end units in pairs as shown in Figure 15. This layout will block the incursion of hot air around the side of the end cabinets.
  • Page 22: Determining Vertical Placement Of Liebert Xdos Above The Cold Aisle

    3.6.2 Determining Vertical Placement of Liebert XDOs Above the Cold Aisle In the maximum density configuration, Emerson recommends placing the Liebert XDOs between 18 and 24 inches (457-609mm) above the equipment cabinets. In some cases where the required density is less, the front-to-rear spacing of Liebert XDOs in a row will be increased. To ensure coverage of the wider spaces between the Liebert XDO units, the vertical distance between the cabinets and the Lie- bert XDOs should be increased.
  • Page 23: Liebert Xdv Unit Placement

    Liebert XDV Unit Placement Liebert XDV units should be placed on top of the cabinets that generate the greatest amount of heat. If heat loads are dispersed evenly throughout the room, the Liebert XDV modules may be spread out accordingly. The Liebert XDV must be placed toward the front of the equipment cabinet, so that its front bottom edge is flush with the front top edge of the cabinet.
  • Page 24: Liebert Xdcf Placement

    Liebert XDCF Placement The Liebert XDCF is a self-contained module designed to cool Egenera’s BladeFrame EX cabinets and equipment. Liebert XDCF modules attach to the rear of the Egenera BladeFrame EX cabinet, beside the power modules (see Figure 17). No cutting or drilling is required to attach the modules; all mounting holes, slots and pins required are fabricated at the factory.
  • Page 25: Liebert Xdh Placement

    Liebert XDH Placement The free-standing Liebert XDH cooling unit is best placed among the equipment cabinets in a hot aisle-cold aisle arrangement (see Figure 18). The Liebert XDH draws in air from the hot aisle, cools it and discharges the cooled air into the cold aisle where it is drawn into the equipment cabinets. Reg- ular spacing aids in optimizing cooling.
  • Page 26: Examples Of Expansion And Interlaced Connection Of Liebert Xd Cooling Modules

    3.11 Examples of Expansion and Interlaced Connection of Liebert XD Cooling Modules Figure 19 Liebert XDV units mounted on racks emitting 3kW of heat, top view Downflow Cooling Unit XDVs Mounted on Equipment Racks Figure 20 Liebert XDV units mounted on racks emitting 5kW of heat, top view Downflow Cooling Unit...
  • Page 27: Figure 21 Liebert Xdv Units Mounted On Racks Emitting 8Kw Of Heat Top View

    Figure 21 Liebert XDV units mounted on racks emitting 8kW of heat top view Downflow Cooling Unit XDVs Mounted on Equipment Racks Interlaced piping arrangement for enhanced protection Figure 22 Liebert XDV units mounted on racks emitting 16kW of heat top view Downflow Cooling Unit...
  • Page 28: Liebert Xd Refrigerant

    3.12 Liebert XD Refrigerant The refrigerant used in the Liebert XD system is HFC-134a (1,1,1,2-tetrafluoroethane), made by a number of manufacturers. The amount of refrigerant used by the Liebert XD system may be signifi- cantly higher than in typical DX cooling systems. CAUTION Risk of improper oil use.
  • Page 29: Figure 23 Piping For Liebert Xdp/Liebert Xdc Used With Liebert Xd Cooling Units

    Figure 23 Piping for Liebert XDP/Liebert XDC used with Liebert XD cooling units 20ft. 9ft. (6.7m) (2.7m) max. max. Liebert XDP/ Liebert XDC SLOPE—The main supply and return lines to and from the Liebert XDP/Liebert XDC must be sloped downward toward the Liebert XDP/Liebert XDC at a rate of 1-2" per 20 feet (25.4-51mm per 6m) of pipe run.
  • Page 30: Liebert Xd Piping Slope

    Figure 24 Hydraulic diagram Liebert Liebert XDP Liebert Liebert XDP 3.14 Liebert XD Piping Slope The main supply and return lines to and from the XDP/XDC must be sloped downward toward the XDP/XDC at a rate of 1-2" per 20 feet (25-51mm per 6m) of pipe run. Horizontal connector lines should also be sloped downward from the cooling modules toward the main supply and return lines.
  • Page 31: Figure 25 Bypass Flow Controller Details, Dimensions

    Figure 25 Bypass flow controller details, dimensions 7/8 " (2.2mm) ID Figure 26 Bypass flow controller arrangement Supply Main Figure 27 Bypass flow controller piping Bypass Flow Controllers Coolant Return Liebert XDP Liebert XDC 4 " (102mm) 7/8" Refrigerant Grade Full Port Ball Valve Field-Supplied and Field-Installed Flow Direction...
  • Page 32: Determining Refrigerant Volume

    3.16 Determining Refrigerant Volume After the preliminary system design is completed, Tables 7, through 15 may be used to determine the amount of refrigerant required. Perform the calculation below for each Liebert XD system being configured. NOTE All lengths in Tables 7, 8, 9 and 10, are actual pipe lengths, not equivalent pipe lengths. 3.16.1 Liebert XDP/Liebert XDC Pumped R-134a Circuit Volume NOTE System refrigerant volume calculations in Tables 7, 8, 9 and 10, are based on a fully loaded...
  • Page 33: Table 10 R-134A Refrigerant Charge For Flex Pipe Connector Lines To And From Any Model

    Table 10 R-134a refrigerant charge for Flex Pipe connector lines to and from any model Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF Refrigerant Charge, lb. (kg) Metal Flex Pipe Connector Length Supply Line Diameter 1/2" 0.3 lb. (0.14) 4 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply 0.5 lb.
  • Page 34: Calculating Refrigerant Charge-Example

    3.16.2 Calculating Refrigerant Charge—Example Using Tables 7, 8, 9 and 10, calculate the refrigerant charge of the individual sections of your Liebert XD system. Add the calculated charge amounts to determine the amount of R-134a refrigerant required for one system combining a Liebert XDP with Liebert XD cooling modules (Liebert XDCF, Liebert XDH, Liebert XDO and Liebert XDV).
  • Page 35: Chilled Water Piping

    Table 14 Outdoor condenser charge—R-407c Model Charge / Circuit, lb (kg) CDL830 CSL616 254 (115.2) CSL415 Table 15 Air cooled systems - liquid line charge - R-407c refrigerant per 100 ft (30 m) of Type "L" copper tube O.D., Liquid Line, inches lb (kg) 3.7 (1.7)
  • Page 36: Liebert Xd Cooling Modules -Liebert Xdo, Liebert Xdv, Liebert Xdh And Liebert Xdcf

    90 degrees. Connection to the prefabricated piping assembly is with a threaded coupler. For information on acquiring the correct kit for your instal- lation, refer to DPN000780, available by calling 1-800-LIEBERT and from your local Emerson Network Power representative.
  • Page 37: Figure 28 Dimensional Data-Liebert Xdo Hard-Piped Units

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Figure 28 Dimensional data—Liebert XDO hard-piped units LEFT SIDE OF XDO 24-1/8" (613mm) FRONT OF XDO Do Not Lift Here Figure 29 Dimensional data—Liebert XDO with pre-charged option Left Side 24-1/8"...
  • Page 38: Figure 30 Liebert Xdo Internal Mounting Location

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Figure 30 Liebert XDO internal mounting location 26-3/4" (679mm) REAR OF XDO 26-3/4" (679mm) 18-1/2" (470mm) TOP VIEW 7/8" (22mm) diameter mounting FRONT OF XDO holes 7/8" (22mm) diameter mounting holes 1"...
  • Page 39: Liebert Xdv Standard Features

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Figure 31 Liebert XDO top and front electrical access points Mounting Hole Knockouts for High-Voltage Wiring FRONT OF XDO The low-voltage connection is present only if the Liebert XDO is equipped with the optional condensation detection system.
  • Page 40: Optional Features-Liebert Xdv

    For information on acquiring the correct kit for your instal- lation, refer to DPN000781_Rev1, available from Liebert by calling 1-800-LIEBERT and from your local Emerson Network Power representative. • Condensate Detection—The Liebert XDV unit is available with factory-installed condensate detection.
  • Page 41: Figure 33 Liebert Xdv Dimensions With One-Shot Connection

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Figure 33 Liebert XDV dimensions with one-shot connection Supply Connection 1/2" Detail “A” Return Connection 5/8" TOP VIEW OF LIEBERT XDV Detail Area “A”...
  • Page 42: Figure 34 Liebert Xdv Electrical Connections For Ce Approved Units

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Figure 34 Liebert XDV electrical connections for CE approved units 60Hz MODELS ONLY. FIELD WIRING CONNECTIONS AT TERMINAL STRIP TO BE N.E.C. CLASS 2 USE SWITCH CONTACTS WITH 75 V.A. MINIMUM 50Hz MODELS ONLY.
  • Page 43: Figure 35 Liebert Xdv Electrical Connections For Csa-Approved Units

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Figure 35 Liebert XDV electrical connections for CSA-approved units 60Hz MODELS ONLY. FIELD WIRING CONNECTIONS AT TERMINAL STRIP TO BE N.E.C. CLASS 2 USE SWITCH CONTACTS WITH 75 V.A. MINIMUM 50Hz MODELS ONLY.
  • Page 44: Figure 36 Suspending Single Liebert Xdv From Unistruts

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Figure 36 Suspending single Liebert XDV from Unistruts Figure 37 Suspending single Liebert XDV from the roof structure Hanging XDV unit To prevent bypass air from recirculating through the XDV without it passing through the cabinet, this space between the hanging...
  • Page 45: Figure 38 Alternative Mounting Methods-Mounting Multiple Liebert Xdv Units

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Figure 38 Alternative mounting methods—mounting multiple Liebert XDV units Attach hanger brackets to each corner of each XDV. This arrangement permits mounting from either Unistruts or from overhead structure. Unistrut field-supplied upper XDV: 1 Bolt 3/8"- 16,...
  • Page 46: Liebert Xdcf Standard Features

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Liebert XDCF Standard Features The Liebert XDCF is a self-contained module designed to cool Egenera’s BladeFrame EX cabinets and equipment without exhausting heat into the room. Upper and lower modules may be mounted on the rear of an Egenera BladeFrame. Liebert XDCF modules use R-134a refrigerant.
  • Page 47: Liebert Xdcf Mechanical Considerations

    (37mm) Upper unit shown; both upper and lower units have same dimensions RIGHT Piping is not load-bearing and should never be used to lift or move the Liebert XDCF 31-3/8" (797mm) 3-9/16" (90mm) Return Pipe EMERSON NETWORK POWER Liebert SIDE...
  • Page 48: Liebert Xdcf Installation Considerations

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Liebert XDCF Installation Considerations No cutting or drilling is required to attach the modules to the rear of the Egenera BladeFrame cabi- net. All mounting holes, slots and pins required are fabricated at the factory. Liebert XDCF modules attach beside the power modules on the rear of the Egenera BladeFrame (see Figure 41).
  • Page 49: Header System

    90 degrees. Connection to the prefabricated piping assembly is with a threaded coupler. For information on acquiring the correct kit for your instal- lation, refer to DPN000780, available by calling 1-800-LIEBERT and from your local Emerson Network Power representative.
  • Page 50: Figure 43 Liebert Xdh Dimensions

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Figure 43 Liebert XDH dimensions 12" (305mm) FRONT Figure 44 Supply and return piping connections Top of Liebert XDH Detail “A” Rear of Liebert 80" (2032mm) 78" (1981mm) 1/2"...
  • Page 51: Piping Connections To Liebert Xdp Or Liebert Xdc

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF 4.7.2 Piping Connections to Liebert XDP or Liebert XDC Piping Installation for Hard Piped System The assembly and connection means for piping in the Liebert XD system are similar to those used for conventional refrigeration systems.
  • Page 52: Liebert Xd Flex Pipe Kit

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Liebert XD Flex Pipe Kit Flex Pipe kits are available in lengths of 4, 6, 8 and 10 feet (1.2, 1.8,2.4 and 3 meters). Connection style to the unit end may be straight or 90 degrees. Connection to the prefab piping assembly is a threaded coupler.
  • Page 53: Liebert Xd Piping Dimensions And Features

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Liebert XD Piping Dimensions and Features 4.9.1 Piping Installation Method prefabricated headers The assembly and connection means used for piping in the Liebert XD system are similar to those used for conventional refrigeration systems.
  • Page 54: Figure 47 Four-Port Prefabricated Piping For Liebert Xd Cooling Modules

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Figure 47 Four-port prefabricated piping for Liebert XD cooling modules 28-9/16" Ref. (725mm) 19-7/16" Ref. (494mm) Table 19 Four-port prefabricated piping legend Branch Piping Four Port Outside Diameter (ODS) Supply Height (H) inch (mm)
  • Page 55: Figure 48 Five-Port Prefabricated Piping For Liebert Xd Cooling Modules

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Figure 48 Five-port prefabricated piping for Liebert XD cooling modules (211mm) Ref. Typ. Table 20 Five-port prefabricated piping legend Branch Piping Five Port Outside Diameter (ODS) Supply Height (H) inch (mm) Length (L) Outside Diameter (ODR)
  • Page 56: Figure 49 Ten-Port Prefabricated Piping For Liebert Xd Cooling Modules

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Figure 49 Ten-port prefabricated piping for Liebert XD cooling modules 7-7/16" Ref. Typ. (189mm) 9-1/16" (230mm) Ref. Typ. Table 21 Ten-port prefabricated piping legend Branch Piping Ten Port Outside Diameter (ODS) Supply Height (H)
  • Page 57: Liebert Xdp Standard Features

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF 4.10 Liebert XDP Standard Features • Heat Exchanger—Brazed plate design with interwoven circuiting constructed of stainless steel plates, copper brazed. • Pumps—Centrifugal type, end suction, internally cooled, canned rotor design. •...
  • Page 58: Figure 51 Liebert Xdp Piping Access Points And External Features

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Figure 51 Liebert XDP piping access points and external features To first cooling module or bypass flow controller ** A - Return From Cooling Modules 17-1/4" (438mm) 10" (254mm) 19"...
  • Page 59: Figure 52 Front View Of Liebert Xdp And Electrical Enclosure

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Figure 52 Front view of Liebert XDP and electrical enclosure Disconnect Switch Front of Liebert XDP Figure 53 Liebert XDP electrical enclosure knockout locations for field wiring User Interface (Wall Box) Wiring Temperature/Humidity Sensor Wiring...
  • Page 60: Figure 54 Liebert Xdp 60Hz High Voltage Connections

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Figure 54 Liebert XDP 60Hz high voltage connections Customer Power Connection Ground Lug Disconnect Switch Pump Fuse Blocks Pump Contactors Figure 55 Liebert XDP 50Hz high voltage connections Customer Power Connection Ground Lug...
  • Page 61: Liebert Xdc Standard Features

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF 4.11 Liebert XDC Standard Features • Compressors—Scroll with a suction gas cooled motor, vibration isolators, thermal overloads, man- ual reset high-pressure switch and pump down low-pressure switch. • Refrigeration System—Dual refrigeration circuits each including liquid line filter dryers, refriger- ant sight glass with moisture indicator, electronic control valve, adjustable externally equalized expansion valves and liquid line solenoid valves.
  • Page 62: Figure 57 Liebert Xdc Piping Locations

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Figure 57 Liebert XDC piping locations 6" (152mm) 23" (584.2mm) Dimensions are approximate and subject to change without notice. * Allow 8" (204mm) of clearance for filter replacement ** To ensure all refrigerant flow is filtered, install the filter dryer assembly between the discharge line of the XDC and the first bypass flow controller or the first cooling module.
  • Page 63: Figure 58 Positioning A Water/Glycol Liebert Xdc For Placement On A Floor Stand

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Figure 58 Positioning a water/glycol Liebert XDC for placement on a floor stand 47" (1194mm) 6" (153mm) 23" (584mm) C - Hot Gas Refrigerant Lines D - Liquid Refrigerant Lines E - Threaded Female...
  • Page 64: Figure 59 Piping Locations-Floor Stand And Valve Assembly

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Figure 59 Piping locations—floor stand and valve assembly 24" Nominal (609mm) TOP VIEW OF FLOOR STAND Hot Gas 1 Hot Gas 2 Outlet Circuit 1 Inlet FLOOR STAND CONNECTIONS 72"...
  • Page 65: Figure 60 Front View Of Liebert Xdc And Electrical Enclosures

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Figure 60 Front view of Liebert XDC and electrical enclosures Enclosure Cover Latch SECONDARY ELECTRICAL ENCLOSURE COMPRESSOR SECTION Figure 61 Liebert XDC electrical enclosure knockout locations for field wiring Secondary Primary Disconnect...
  • Page 66: Figure 62 Liebert Xdc High Voltage Connections-Primary Disconnect Switch, 60Hz Models

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Figure 62 Liebert XDC high voltage connections—primary disconnect switch, 60Hz models Transformer Fuse Block Compressor Fuse Blocks Compressor Contactors Figure 63 Liebert XDC high voltage connections—primary disconnect switch, 50Hz models Compressor Circuit Breakers Busbar...
  • Page 67: Figure 64 Liebert Xdc High Voltage Connections-Secondary Disconnect Switch, 60Hz Models

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Figure 64 Liebert XDC high voltage connections—secondary disconnect switch, 60Hz models Power Connection From Primary Power Block Ground Lug Secondary Disconnect Switch Pump Circuit Breakers Pump Contactors Figure 65 Liebert XDC high voltage connections—secondary disconnect switch, 50Hz models Power Connection From Primary Power Block...
  • Page 68: Figure 66 Liebert Xdc Heat Rejection Electrical Connection Points

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Figure 66 Liebert XDC heat rejection electrical connection points HEAT REJECTION ELECTRICAL CONNECTION POINTS Field-supplied 24V. Class 1 wiring to interlock heat rejection from pigtails: 70A and 71A - Compressor 1 circuit 70B and 71B - Compressor 2 circuit 70C and 71C - Dual Source relay (optional) Electrical handy box,...
  • Page 69: Figure 68 Liebert Xdc Extra Low Voltage Field Connections Points

    Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF Figure 68 Liebert XDC Extra Low Voltage field connections points Control Display Panel Four thermostatic wires to be connected toTB3 Control wiring must be Class 2 and installed in accordance with the National Electrical Code (NEC) Requires shielded cable Temperature/Humidity Sensor...
  • Page 70: Specifications

    PECIFICATIONS Table 27 Liebert XDC160 specifications Models Cooling Capacity, tons (kW) Minimum Load Electrical Requirements Minimum supply wire sizing ampacity Maximum fuse or circuit breaker size Dimensions, inches (mm) Height - Main unit only Height - Main unit only, as shipped Height - Water / Glycol cooled condenser stand Width - Water / Glycol cooled condenser stand Depth - Water / Glycol cooled condenser stand...
  • Page 71: Table 28 Floor Stand Specifications-Water-Cooled Liebert Xdc

    Table 28 Floor stand specifications—water-cooled Liebert XDC Models - 60 Hz Entering Fluid Temp °F (C) Performance Data Cooling capacity, tons (kW) Flow, GPM Pressure Drop, psi (Ft Water) Heat Rejection Equipment Water regulating valve size Piping Connections Water / glycol supply and return lines Table 29 Floor stand specifications—Liebert XDC with 40% propylene glycol Models - 60 Hz...
  • Page 72: Table 30 Floor Stand Specifications-Liebert Xdc With 40% Ethylene Glycol

    Table 30 Floor stand specifications—Liebert XDC with 40% ethylene glycol Models - 60 Hz Outside Ambient °F (°C) Entering Fluid Temp °F (°C) Performance Data Cooling capacity, tons (kW) Total Heat Rejection, (kW) Pressure Drop, psi (ft water) Heat Rejection Equipment Drycooler Pressure Drop, psi (ft water) Glycol pump package - 10HP Pump Control Package - 208V...
  • Page 73: Table 31 Liebert Xdp160 Specifications

    Table 31 Liebert XDP160 specifications Models Cooling Capacity, Nominal Minimum Load Electrical Requirements Input Full Load Amps Dimensions, inches (mm) Height – Unit only Height – As shipped Width Depth Weight, lb (kg) Unit only Shipping weight Installed, with refrigerant and chilled water Pipe Connections Refrigerant supply to Liebert XD...
  • Page 74: Table 32 Liebert Xdo16 Specifications

    Table 32 Liebert XDO16 specifications Models Cooling Capacity Conditions Capacity rating is @ 55°F (13°C) Entering Fluid Temperature and 50ºF or lower dew point Electrical Requirements Input Voltage Input Power Connections Full Load Amps Wire Size Amps Overcurrent Protection Device Power consumption, nominal, watts Dimensions, inches (mm)
  • Page 75: Table 33 Liebert Xdo20 Specifications

    Table 33 Liebert XDO20 specifications XDO20DK--*; XDO20BKP-* XDO20DKP-*; XDO20BK-E* XDO20DK-E*; XDO20BKPE* Models Cooling Capacity Conditions Electrical Requirements Input Voltage Input Power Connections Full Load Amps Wire Size Amps Overcurrent Protection Device Power consumption, nominal, watts Dimensions, inches (mm) Length Width Height Weight, lb (kg) Unit only...
  • Page 76: Table 34 Liebert Xdo20 Dimensions-Domestic And Export

    Table 34 Liebert XDO20 dimensions—domestic and export Shipping Dimensions, inches (mm) Domestic Model Length Width All Models (2134) (762) * Includes piping connections Table 35 Liebert XDO16 dimensions—domestic and export Shipping Dimensions, inches (mm) Domestic Model Length Width All Models (2134) (762) * Includes piping connections...
  • Page 77: Table 36 Liebert Xdv8 Specifications

    Table 36 Liebert XDV8 specifications XDV8BK--*; XDV8DK--* XDV8BKP-*; XDV8DKP-* XDV8BK-E*; XDV8DK-E* XDV8BKPE*; XDV8DKPE* XDV8BKR-*; XDV8BKRE* XDV8DKR-*; XDV8DKRE* Models 60 Hz Nominal (98°F [37°C] EAT): 8.8kW / 2.5 Tons Cooling Capacity Maximum (95°F [35°C] EAT): 8.8kW / 2.5 Tons Conditions Electrical Requirements Input 120V model: 1ph-60 Hz Input power connections...
  • Page 78: Table 37 Liebert Xdv10 Specifications

    Table 37 Liebert XDV10 specifications XDV10BK--*; XDV10DK--* XDV10BKP-*; XDV10DKP-* XDV10BK-E*; XDV10DK-E* XDV10BKPE*; XDV10DKPE* XDV10BKR-*; XDV10BKRE* XDV10DKR-*; XDV10DKRE* Models Nominal (98ºF [37ºC] EAT): 10kW / 2.8 Tons Cooling Capacity Maximum (106ºF [41ºC] EAT): 11.8kW/3.4 Tons Conditions Electrical Requirements Input 120V model: 1ph-60 Hz Input power connections Full Load Amps 120V model: 2.0A...
  • Page 79: Table 38 Liebert Xdv8 Dimensions-Domestic And Export

    Table 38 Liebert XDV8 dimensions—domestic and export Shipping Dimensions Length x Width x Height inches (mm) Model Domestic 48 x 40 x 24-1/4 All Models (1219 x 1016 x 616) Table 39 Liebert XDV10 dimensions—domestic and export Shipping Dimensions Length x Width x Height inches (mm) Model Domestic...
  • Page 80: Table 41 Liebert Xdh Specifications

    Table 41 Liebert XDH specifications XDH20DKP-0 XDH20DK--0 XDH20BKP-0 XDH20BK--0 XDH20DKPE0 XDH20DK-E0 XDH20BKPE0 XDH20BK-E0 Models XDH20, 60Hz Nominal (98ºF [37°C] EAT): 22kW/6.3 Tons XDH20, 60Hz Maximum(105ºF [40°C] EAT): 25.5kW/7.3 Tons XDH20, 50Hz Nominal (98ºF [37°C] EAT): 19kW / 5.4 Tons XDH20, 50Hz Maximum(116ºF [47°C] EAT): 25.5kW/7.3 Tons Cooling Capacity XDH32, 60Hz Nominal (98ºF [37°C] EAT): 30kW/8.5 Tons XDH32, 60Hz Maximum(105ºF [40°C] EAT): 34.5kW/7.3 Tons...
  • Page 81 Specifications Notes...
  • Page 82 Specifications...
  • Page 84 Embedded Computing Connectivity Embedded Power DC Power Monitoring Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2007 Emerson Electric Co. Technical Support / Service [email protected] Outside the US: 614-841-6755 [email protected]...