Emerson Liebert FPC User Manual

15 kva - 300kva, 3 phase, 50 & 60 hz
Table of Contents

Quick Links

Liebert FPC
User Manual - 15 kVA - 300kVA, 3 Phase, 50 & 60 Hz
AC Power
For Business-Critical Continuity™
Table of Contents
loading

Summary of Contents for Emerson Liebert FPC

  • Page 1 Liebert FPC ™ User Manual - 15 kVA - 300kVA, 3 Phase, 50 & 60 Hz AC Power For Business-Critical Continuity™...
  • Page 3: Table Of Contents

    NSTALLATION NSTRUCTIONS Unpacking and Installation ........... . 2 1.1.1 Unpacking and Preliminary Inspection .
  • Page 4 Figure 13 Typical Liebert FPC equipment arrangement ........
  • Page 5 Electrical safety precautions must be followed throughout inspection and startup. Only qualified service personnel should perform maintenance on the Liebert FPC system. All voltage sources to the unit must be disconnected before inspecting or cleaning within the cabinet.
  • Page 6: Installation Instructions

    The Liebert FPC and cable reels are furnished with casters to allow the unit to be rolled into place after it has been unbolted from the pallet. The FPC should be kept on the shipping pallet until it has been moved by forklift as close as practical to its installation location.
  • Page 7: Figure 1 Typical Cabinet And Floor Planning Dimension Data, 23" (584Mm) Cabinet, 15-125 Kva

    Figure 1 Typical cabinet and floor planning dimension data, 23" (584mm) cabinet, 15-125 kVA Overall Dim. 39-1/2" (1003mm) Including hinge and bezel projection Overhead clearance of 18" (457mm) recommended for cooling airflow Minimum side clearance of 42" (1067mm) recommended for service access if unit is equipped with distribution monitoring option Shaded areas indicate...
  • Page 8: Figure 2 Typical Cabinet And Floor Planning Dimension Data, 47" (1194Mm) Cabinet 50-300Kva

    Figure 2 Typical cabinet and floor planning dimension data, 47" (1194mm) cabinet 50-300kVA Overall Dim. 39-1/2" (1003mm) Including hinge and bezel projection Overhead clearance of 18" (457mm) recommended for cooling airflow Minimum side clearance of 42" (1067mm) recommended for service access if unit is equipped with distribution monitoring option Shaded areas indicate...
  • Page 9: Unit Preparation

    The Liebert FPC may be easily removed from the shipping pallet and installed by customer person- nel. A typical procedure is as follows: 1. Set the palletized assembly in a level area where there is enough room to roll the Liebert FPC and entire cable assembly off the pallet onto the floor.
  • Page 10: Figure 3 Recommended Minimum Service And Ventilation Clearances

    2. Service access clearance dimensions: 36" (914mm) for units up to 150V to ground. 42" (1067mm) for units over 150V to ground. 3. Service access is required on the left side, if unit is equipped with Liebert Distribution Monitoring Option. Table 3 Liebert FPC heat output Full Load Heat Output Unit kVA BTU/Hr (kW) 2,500 (0.73)
  • Page 11: Floor Pedestal Installation

    1.1.5 Floor Pedestal Installation Floor pedestals are optional equipment that provide clearance for bottom cable entry or exit for FPC units not installed on raised flooring. The pedestals are adjustable over a limited range (approxi- mately 3-1/2" [89mm]) to allow leveling the FPC and minor adjustments in the unit’s installed height. CAUTION Floor pedestals may be reverse-assembled for shipping.
  • Page 12: Additional Distribution Mounting & Wiring

    Additional Distribution Mounting & Wiring For Liebert FPCs with more than four panelboards, the additional panelboards are furnished in Lie- bert FDC enclosures, which are shipped separately from the Liebert FPC. 1.2.1 Liebert FDC Distribution Mounting The Liebert FDC distribution cabinet has the same base dimensions as a 23" (584mm) cabinet FPC (23-1/2"...
  • Page 13: Figure 5 Electrical Connection Location For 23" (584Mm) Cabinet

    Installation Instructions To minimize disturbances from other loads in the building, the 3-phase power input to the FPC should be supplied directly from the service entrance or other power source (a dedicated power feeder). The input feeder circuit should be sized in accordance with the NEC and any local building codes to ensure the feeder’s ability to safely carry the system’s full load current, including losses.
  • Page 14: Figure 6 Electrical Connection Location For 47" (1194Mm) Cabinet-Front View

    Figure 6 Electrical connection location for 47" (1194mm) cabinet—Front view FPC15000 Rev. 0 Figure 7 Electrical connection location for 47" (1194mm) cabinet—Rear view FPC15000 Rev. 0 Installation Instructions...
  • Page 15: Figure 8 Electrical Connection Location For 47" Cabinet With Sqd I-Line Panelboard-Front View

    Figure 8 Electrical connection location for 47" cabinet with SqD I-Line panelboard—Front view Figure 9 Electrical connection location for 47" cabinet with SqD I-Line panelboard—Rear view Square “D” I-Line Panelboard FPC15002 Rev. 0 1.75" (44.4mm) .88" 3.28" (83mm) (22mm) 1.75" (44.4mm) .88"...
  • Page 16: Table 4 Suggested Minimum Input Wire Size Data

    Table 4 Suggested minimum input wire size data Units with Transformers Input Input Input Voltage Transformerless Units Suggested Feeder Full Load MIB Trip Wire Size (AWG) Amps Amps #6 AWG #8 AWG #10 AWG #10 AWG #10 AWG #10 AWG #12 AWG #2 AWG #2 AWG...
  • Page 17: Table 5 Main Input Circuit Breaker Interrupting Rating

    Table 4 Suggested minimum input wire size data (continued) Units with Transformers Input Input Input Voltage * Parallel feeders per NEC 300-20 and 310-4 FLA = Full Load Amps of Power Center OPD = Overcurrent Protection Device inside FPC Wire sizes based on NEC 2005, Table 310-16, using 75°C copper conductor 1.
  • Page 18: Junction Box Installation

    1.3.2 Junction Box Installation Main input (power) and low-voltage (control) junction boxes are available for the Liebert FPC to sim- plify customer connections. The junction boxes, if used, can either be shipped with the system or can be advance-shipped for installation during the roughing-in stage of new construction.
  • Page 19: System Grounding

    System Grounding The performance and safety of any power conditioning system depend on proper grounding. Figure 12 shows the typical grounding arrangements for the Liebert FPC. Equipment Grounding Equipment grounding is primarily for safety. Correct implementation of grounding also enhances equipment performance.
  • Page 20: Grounding Electrode Conductor For Fpcs With Transformer

    1.3.4 Grounding Electrode Conductor for FPCs With Transformer Required by code - The Liebert FPC with transformer must be grounded according to the safety practices of NEC 250-26. A local grounding electrode conductor is recommended in addition to the equipment safety ground which is normally run with the input power conductors. (See Figures 5 through 8.)
  • Page 21: Figure 12 Typical Grounding Arrangements

    Input J-box (if used) Local grounding electrode conductor per NEC 250-28 Typical Liebert FPC Input J-box (without transformer ) (if used) Typical Liebert FPC Installation Instructions Liebert FPC (with transformer) Signal reference grid (if used)
  • Page 22: Output Power Connections

    For best performance, the Liebert FPC should be installed as close as practical to the load. Initial system output loading should be between 50% and 75% of rated capacity. This allows the addi- tion of loads without immediately investing in another power conditioner.
  • Page 23: Figure 13 Typical Liebert Fpc Equipment Arrangement

    Figure 13 Typical Liebert FPC equipment arrangement Liebert FPC Ground electrode conductor (not by Liebert ) required per NEC for units with transformer Main input power to unit (not by Liebert ) 3-phase , 3-wire plus ground for units with transformer...
  • Page 24: Control Wiring Connections

    When more than one power center is installed by the user, a typical requirement is that actuation of a single device (REPO for example) must shut down all power centers. The low-voltage control circuits of all standard Liebert FPC systems are designed to meet this requirement. External Control Wiring Connections External control wiring connections for remote shutdown, alarm, and/or monitoring are made to the low-voltage junction box (if used) or to the low-voltage control terminal strip located inside the unit.
  • Page 25: Figure 15 Typical Control Wiring For Units Without Monitoring

    Figure 15 Typical control wiring for units without monitoring Low Voltage Terminal Strip Overtemp Alarm N.O. W208 Overtemp Alarm N.C. W207 Alarm Com. W206 N.O. REPO W205 REPO Com. W203 N.C. REPO Building Interface Relay NOTES 1. All switching devices are to be suitable for switching low current 24VDC. Minimum recommended wire size is 18AWG stranded copper with 300V insulation.
  • Page 26: Figure 16 Typical Control Wiring For Units With Monitoring

    Figure 16 Typical control wiring for units with monitoring Comm Cable+(RED) Comm Cable-(BLK) RS-232 RXD (WHT) RS-232 TXD (RED) RS-232 COM (BLK) 5th Customer Alarm W214 4th Customer Alarm W213 3nd Customer Alarm W212 2nd Customer Alarm W211 1st Customer Alarm W210 Summary Alarm N.O.
  • Page 27: Equipment Inspection And Startup

    Verify that all incoming line voltage (power) and low-voltage (control) circuits are de-energized and locked out before performing the internal inspection. Open the unit - Gain access to the internal components of the Liebert FPC unit by removing the exterior panels and internal accent panels.
  • Page 28: Table 11 Panelboard Main Circuit Breaker Torque Specifications

    Table 11 Torque specifications, general Electrical connections with 1 Belleville washer Torque lb-in Bolt shaft size, in./mm 1/4 / M6 5/16 / M8 3/8 / M10 13.6 1/2 / M12 54.3 Input and output breakers Up to 150 amp 175 - 500A 13.6 Table 12 Panelboard main circuit breaker torque specifications...
  • Page 29: Inspection And Startup Checklist

    NSPECTION AND TARTUP Unit Serial Number Unit Model Number Date Inspection WARNING All equipment inspection procedures are to be performed with power to the unit turned off and locked out. ___ 1. Confirm that the exterior of unit is undamaged (including cables and receptacles, if furnished).
  • Page 30: Startup

    Startup WARNING Startup procedures should be performed only by qualified personnel. Hazardous voltages are present in the equipment throughout the majority of the start-up procedure. Use proper safety equipment. proceed with caution. When opening the main input circuit breaker wait a minimum of one minute before reclosing. 1.
  • Page 31: Monitoring System Check-Out

    NOTE The Liebert FPC transformer has input voltage taps for each input phase. The taps are arranged in 2-1/2% or 5% intervals ranging from -10% to nominal to +5%. This permits the transformer to provide the proper output voltage for a range of input voltages. Should it be necessary, the tap arrangement may be changed to match the input voltage: •...
  • Page 32: Equipment Connection Check-Out Of Units With Distribution Cables

    Customer Alarms If customer alarms are provided: ___ 1. With the FPC ON, simulate alarm operation by jumpering the appropriate low-voltage control terminals. (Refer to the control wiring installation drawing furnished with the unit.) ___ 2. Verify correct alarm annunciation by the Power Monitor Panel and/or by the Centralized Monitoring System.
  • Page 33: Operating Instructions

    PERATING NSTRUCTIONS Startup Procedures Before the unit is placed into service after initial installation, after equipment relocation, or after equipment has been de-energized for an extended period of time, perform equipment inspection and start-up procedures as detailed in 2.0 - Equipment Inspection and Startup and 3.0 - Inspection and Startup Checklist.
  • Page 34: Basic Monitor Panel (Units Without Monitoring)

    After correction of the alarm condition, the alarm will automatically reset. Figure 17 Basic monitoring panel Liebert FPC Power Monitor Panel Monitored Parameters - A 4 x 20 character LCD is provided to indicate the input voltages (line-to-...
  • Page 35 Alarms - Upon occurrence of any of the following alarms, the alarm message appears on the LCD dis- play, the Alarm Present/Silence switch is illuminated, and the audible alarm is activated. Pressing the “Alarm Present/Silence” switch silences the audible alarm. After the alarm condition is corrected, the alarm can be reset by pressing the “Alarm Present/Silence”...
  • Page 36: Table 15 Ascii Interface Default Parameters

    To Set Unit Clock - To set the clock from the unit front panel, simultaneously press the Scan and Hold membrane switches while the time and date screen is displayed on the LCD. A cursor should appear on the selected time and date field. Use the Scan switch to increment the highlighted field and the Hold switch to decrement the highlighted field.
  • Page 37: Table 17 Monitored Parameters Data Definitions

    Table 17 Monitored parameters data definitions Field # Data item Input Voltage A-B Input Voltage B-C Input Voltage C-A Output Voltage X-Y Output Voltage Y-Z Output Voltage Z-A Output Voltage X-N Output Voltage Y-N Output Voltage Z-N Output Current X Output Current Y Output Current Z Neutral Current...
  • Page 38: Maintenance

    Annual general system inspections, cleaning, and operation checks are recommended to ensure sys- tem performance and long service life. WARNING Only qualified service personnel should perform maintenance on the Liebert FPC system. All voltage sources to the unit must be disconnected before inspecting or cleaning within the cabinet.
  • Page 40 Embedded Computing Connectivity Embedded Power DC Power Monitoring Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2007 Emerson Electric Co. Technical Support / Service [email protected] Outside the US: 614-841-6755 [email protected]...