Haier HSM09HEK03 Installation Manual
Haier HSM09HEK03 Installation Manual

Haier HSM09HEK03 Installation Manual

Wall mounted type

ROOM AIR CONDITIONER

WALL MOUNTED TYPE
HSM 09HEK03/R2(DB)
HSM 12HEK03/R2(DB)
HUM 09HA03/R2(DB)
HUM 12HA03/R2(DB)
Read this manual before installation
Explain sufficiently the operating means to the user according to this manual.
NO.001051

INSTALLATION MANUAL

Table of Contents
loading

Summary of Contents for Haier HSM09HEK03

  • Page 1: Installation Manual

    INSTALLATION MANUAL ROOM AIR CONDITIONER WALL MOUNTED TYPE HSM 09HEK03/R2(DB) HSM 12HEK03/R2(DB) HUM 09HA03/R2(DB) HUM 12HA03/R2(DB) Read this manual before installation Explain sufficiently the operating means to the user according to this manual. NO.001051...
  • Page 2: Necessary Tools For Installation

    Drain hose Heating insulating material Piping hole cover The marks from in the figure are the parts numbers. Note:Cooling only units don't have Drain-elbow The distance between the indoor unit and the floor should be more than 2m.
  • Page 3: Selection Of Installation Place

    Before inserting power plug into receptacle, check the voltage without fail. The power source is the same as the corresponding name plate. Install an exclusive branch circuit of the power. A receptacle shall be set up in a distance where the power cable can be reached. Do not extend the cable by cutting it. Selection of pipe To this unit, both liquid and gas pipes shall be insulated as they become Iow temperature in operation.
  • Page 4: Installation Of The Indoor Unit

    In case of left side piping, cut away, with a nipper, the lid for left piping. In case of left-rear piping, bend the pipes according to the piping direction to the mark of hole for left-rear piping which is marked on heat insulation materials.
  • Page 5: Fixing The Indoor Unit Body

    Indoor unit 1. Insert the drain hose into the dent of heat insulation materials of indoor unit. 2. Insert the indoor/outdoor electric cable from backside of indoor unit, and pull it out on the front side, then connect them. 3. Coat the flaring seal face with refrigerant oil and connect pipes.
  • Page 6: Connecting The Indoor/Outdoor Electric Cable

    1. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person. The type of connecting wire is H05/07RN-F or 245IEC57(YZW).
  • Page 7: Installation Of Outdoor Unit

    Be careful that matters, such as wastes of sands, etc. shall not enter the pipe. 3.Connection Use the same method on indoor unit. Loosen the screws on terminal block and insert the plugs fully into terminal block, then tighten the screws.
  • Page 8: Purging Method

    Max.Elevation:5m Oil trap shoud be installed every 5~7m no more gas if the length of connecting pipe is less than 7m( 9K) or 10m(12K). The height difference between any two indoor or outdoor units can not be more than 5m.
  • Page 9 Please pour water in the drain pan of the indoor unit, and confirm that drainage is carried out surely to outdoor. In case that the attached drain hose is in a room, please apply heat insulation to it without fail.