Suggestions For Transmitter Location; General Piping Guidelines; Procedure To Install Flange Adapters; Table 6 - Suggested Connection Locations - Honeywell SmartLine ST 800 User Manual

Pressure transmitters
Table of Contents

3.5.2 Suggestions for Transmitter Location

Suggests connections based on what is being processed by the system.
Process
Gases
Above the gas line.
Liquids
Below but near the elevation of the
process connection.
Level with or above the process
connection.
1. For liquid or steam, the piping should slope a minimum of 25.4 mm (1 inch) per 305 mm (1 foot).
2. Slope the piping down toward the transmitter if it is below the process connection to allow the
bubbles to rise back into the piping through the liquid.
3. If the transmitter is located above the process connection, the piping should rise vertically above
the transmitter. In this case, slope down toward the flow line with a vent valve at the high point.
4. For gas measurement, use a condensate leg and drain at the low point (freeze protection may be
required here).
ATTENTION Care must be taken when installing transmitters on hot processes.
The operating temperature limits for the device (as outlined in Table 5) must not be exceeded.
Impulse piping may be used to reduce the temperature of the process that comes into contact
with the transmitter meter body. As a general rule there is a 56  C drop (100  F) in the
temperature of the process for every foot of ½ inch uninsulated piping.

3.5.3 General Piping Guidelines

When measuring fluids that contain suspended solids, install permanent valves at regular intervals
to blow-down piping.
Blow-down all lines on new installations with compressed air or steam and flush them with process
fluids (where possible) before connecting these lines to the transmitter meter body.
Verify that the valves in the blow-down lines are closed tightly after the initial blow-down
procedure and each maintenance procedure thereafter.

3.5.4 Procedure to Install Flange Adapters

The following procedure provides the steps for removing and replacing an optional flange adapter on the
process head.
This procedure does not require that the meter body be removed from the electronics
housing. If flange adapters are being replaced with parts from other kits (for example, process
heads), follow the procedures for the kits and incorporate the following procedure.
NOTE: The threaded hole in each flange adapter is offset from center. To ensure proper
orientation for re-assembly, note the orientation of the offset relative to each process head
before removing any adapter.
15
Table 6 – Suggested Connection Locations
Suggested Location
ST 800 Pressure Transmitter User's Manual
Description
The condensate drains away from the transmitter.
This minimizes that static head effect of the condensate.
This requires a siphon to protect the transmitter from process
steam. The siphon retains water as a fill fluid.