GE Multilin D20E Installation And Maintenance Manual

Ethernet i/o module
Table of Contents

Quick Links

GE
Grid Solutions
Multilin
D20E
TM
Ethernet I/O Module
Installation and Maintenance Guide
994-0145
Version 1.00 Revision 4
DAPserver Studio Version: 6.2.0-4
GE Information
Table of Contents
loading

Summary of Contents for GE Multilin D20E

  • Page 1 Grid Solutions Multilin D20E Ethernet I/O Module Installation and Maintenance Guide 994-0145 Version 1.00 Revision 4 DAPserver Studio Version: 6.2.0-4 GE Information...
  • Page 2 GE Grid Solutions Copyright Notice © 2022, General Electric Company. All rights reserved. The information contained in this online publication is the exclusive property of General Electric Company, except as otherwise indicated. You may view, copy and print documents and graphics incorporated in this online publication (the “Documents”) subject to the following: (1) the Documents may be used solely for personal, infor-...
  • Page 3: Table Of Contents

    Purpose ..........................11 DOCUMENT Intended audience ......................11 Example module being configured and monitored..........12 Additional documentation ..................12 GE Grid Solutions and Alstom product naming ............12 Form C point references....................12 How to use this manual ....................13 Safety words and definitions..................13 BEFORE YOU START Product overview......................16...
  • Page 4 Analog input configuration procedure ....................68 Control output points ....................69 Control output type............................69 Control output point quality flag ......................70 Control output point configuration settings..................70 Check operation of the D20E..................73 Operation of control output points......................73 GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 5 TABLE OF CONTENTS Check the D20E system status ....................... 73 Access the Event Log........................... 73 Make D20E device setting changes ................74 MOUNTING A D20E Mounting........................75 MODULE Rack spacing .........................75 Required clearances ............................ 75 Rack mounting procedure ..................76 CONNECTING TO D20E connectors......................77 Console port ........................78 DEVICES AND Console port connection..........................
  • Page 6 Main window ......................126 Project configuration window................. 127 Window title bar ............................127 Menu bars...............................128 Main workspace ............................128 Task bar ................................128 D20E MODULE DNP3 IED protocol document.................. 129 DNP3 SERVER DNP3 object implementation table................ 131 PROFILE GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 7 TABLE OF CONTENTS MISCELLANEOUS Warranty........................135 Revision history ......................135 LIST OF ACRONYMS Acronym Definitions ....................137 FREQUENTLY ASKED Questions and answers.................... 139 QUESTIONS D20E ETHERNET I/O MODULE INSTRUCTION MANUAL INFORMATION...
  • Page 8: Product Support

    D20E Ethernet I/O Module Product Support Product Support If you need help with any aspect of your GE Grid Solutions product, you can: • Access the GE Grid Solutions Web site • Search the GE Technical Support library • Contact Technical Support Also covered are: •...
  • Page 9: Contact Ge Grid Solutions Technical Support

    PRODUCT SUPPORT Contact GE Grid Solutions technical support GE Grid Solutions Technical Support is open 24 hours a day, seven days a week for you to talk directly to a GE representative. In the U.S. and Canada, call toll-free: 1 800-547-8629...
  • Page 10: About This Document

    SCADA equipment. This manual assumes that the user is experienced in: • Electrical utility applications • Electrical wiring and safety procedures • Other related manufacturers’ products, such as protective relays and communications equipment D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 11: Example Module Being Configured And Monitored

    DAPserver Studio Online Help • DAPserver Studio User Guide GE Grid Solutions and Alstom product naming The following table provides a cross-references of the GE Grid Solutions IO module product names, and the equivalent legacy Alstom product names: Product description Product name...
  • Page 12: How To Use This Manual

    Indicates a hazardous situation which, if not avoided, could result in death or serious injury. Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. Indicates practices that are not related to personal injury. D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 13 The D20E Ethernet I/O Modules provide digital input, control output and analog input interfaces, as well as, a mixed interface I/O unit. These products can be integrated with GE Grid Solutions D400, DAP-416, DMC490, and D2x substation automation products or installed as stand-alone I/O modules with either DNP3 TCP/IP subset level 2 or IEC 61850 GGIO server network protocols.
  • Page 14 Figure 1: D20E-C (combination inputs/outputs) module front panel Figure 2: D20E-S (status digital inputs) module front panel Figure 3: D20E-K (control digital outputs) module front panel Figure 4: D20E-A (analog inputs) module front panel GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 15: Comparing D20E To D.20 I/O Module Operation

    The D20E module comes with factory configuration as ordered. Always check the order code configuration on the D20E prior to connecting field I/O. • Do not operate the D20E if it has been dropped or damaged. Return it to GE Grid Solutions for inspection and repair. •...
  • Page 16: Protective Earth Ground

    If the D20E is used in a manner not specified in this manual, the protection provided by the equipment may be impaired. • Changes or modifications made to the unit not authorized by GE Grid Solutions could void the warranty. Protective earth ground...
  • Page 17: Warning Symbols

    Cyber security precautions The D20E can be deployed with a GE Grid Solutions' server (for example, D20MX or D400) or with IEDs, provided the D20E is behind the GE Grid Solutions server or IED.
  • Page 18: Hardware Overview

    Analog inputs accept DC sensor or transducer signals and can be set for either voltage or current inputs on an individual per input basis. A REMOTE/LOCAL switch is provided on both the D20E-K and D20E-C modules to enable or disable control outputs for added station maintenance safety. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 19: Configure Device Firmware

    Data communications The D20E module supports the following TCP/IP network based communication protocols: • IEC 61850 GGIO server • DNP3 server Redundancy is not an enabled feature on the D20E (not licensed). D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 20: Dnp3 Server

    Unsolicited data report is initiated from outstations to master stations. • Data types (Objects) can be assigned priorities (Class) and be requested based on the priority. • Time-stamped events. • Broadcast messages. • Data link and application layer confirmation and configurable. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 21: Ordering Guides

    CHAPTER 1: BEFORE YOU START Ordering guides The latest ordering guides are available on the GE Grid Solutions website at: http://www.gedigitalenergy.com/multilin/energy/catalog/d20e.htm You can select the required options from the available Product Option items. The Order Code automatically updates as each option is selected.
  • Page 22 D20E -* * -* * * -* 0 0 * * * -* * * * -* * (U) - Not required (A) - Cable Assembly USB 2m 28AWG USB Type A to Micro-USB Type B M-M Bag (GE part number, 580-3767)
  • Page 23 (0) D20E Firmware, Latest Release Documentation Options D20E -* * -* * * -* 0 0 * * * -* * * * -* * (U) - Not required (B) - SAS Product Documentation CD D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 24: Specifications

    29 • Power supply on page 29 • Enclosure electro-magnetic capability on page 30 • Environmental on page 30 • Physical on page 30 • Communication ports on page 31 GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 25 Blue LED per input • D20E-C 16 input points • D20E-S 64 input points Conducted Immunity As per: • IEEE C37.90.1 • IEC 61000-4-4 • IEC 61000-4-5 • IEC 61000-4-6 • IEC 61000-4-16 D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 26 • External control supply input: 24/48 VDC nominal • Dielectric insulation: 1400 VDC • Conducted Immunity: IEEE C37.90.1, IEC 61000-4-4 • D20E-K (DB25) interface connects to WESTERM D20KI 517-0143 with cable 977-0069 GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 27 DC1 and DC2 Blue LEDs; Power Supply output ON Red LED Conducted Immunity As per: • IEEE C37.90.1 • IEC 61000-4-4 • IEC 61000-4-5 • IEC 61000-4-6 • IEC 61000-4-16 • IEC 61000-4-17 • IEC 61000-4-29 D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 28 19.0 x 5.2 x 1.6 inches; 483 x 132 x 41mm Weight 4.8 lbs; 2.2 kg (except D20E-K: 5.7 lbs or 2.6 kg) Termination Facilities Compression Terminal Block: 2.5 mm (#13 AWG) maximum GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 29 USB 2.0 (micro AB jack): • Secure Shell (SSH) Port Default IP Address LAN 1 IP = 192.168.0.189 Port 22 LAN 2 IP = 192.168.1.189 Port 22 USB 2.0 IP = 10.0.0.1 Port 22 D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 30: Testing And Certification

    Damped Oscillatory IEEE/ANSI C37.90.1 2.5 kV, 1 MHz Make and Carry IEEE C37.90 Electrostatic Discharge (ESD) IEEE/ANSIC 37.90.3 8 kV CD/ 15 kV AD Product Safety IEC 61010-1 As per Normative sections GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 31: Rohs Compliance

    Cr6: Hexavalent Chromium • PBB: Polybrominated biphenyls • PBDE: Polybrominated diphenyl ethers Table 3: RoHS Material Declaration Data Content by Assembly GE part Description PBDE number 507-0501LF D20E-S - Status Input Logic Main 508-0501LF D20E-K - Control  Logic Main 509-0501LF D20E-C - Combination Logic Main ...
  • Page 32: Storage Recommendations

    Maximum altitude: 12192 m [40,000 feet] above sea level To avoid deterioration and early failure of electrolytic capacitors, power up units that are stored in a de-energized state once every 12 months, for one hour continuously. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 33: Installing The D20E Module

    • Wire strippers (for field wiring) • Wire crimping tool (for field wiring) • Tie-wraps (for organizing wiring and cables) • Multimeter (for testing voltages and I/O points) • Needle nose pliers D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 34: Configuring The D20E Firmware

    Power-up the D20E module and verify that D20E module is functioning properly; see chapter: Powering-up and Testing a D20E Module on page 101. Monitor D20E module operation; see chapter Using the D20E Module on page 103 GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 35 Connect the D20E module (port 1) to a Windows PC with an Ethernet cable as shown in Figure 6. A standard Ethernet cable can be used if connecting to a network with an Ethernet switch. D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 36 Result: The DAPserver Studio opens. Select the I agree to the license terms and conditions check-box. Click Next. Result: The Create Application Shortcuts window appears. Select either a Typical or Custom setup type. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 37 Result: The tools are installed in the specified location. Result: The Setup wizard - Completed pane appears. Result: A DAPserver Studio status (progress) bar appears. Result: The message appears: DAPserver Studio has been successfully installed. Click Finish. D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 38: Start Dapserver Studio

    D20E module for a successful connection. The default IP addresses for DAPserver Studio projects and the D20E module LAN 1 are 192.168.0.189. Result: For example, the Explore window can appear as shown in Figure 7. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 39: Change D20E Module Ip Address

    Navigate to the Device menu bar. Select Network. Result: The Device Information window appears. Type in the IP Address of the D20E module. Type in the Username and Password login credentials (default: admin). D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 40 Result: The Task bar appears at the bottom of the screen. 11. Click Sync in the Task bar. Result: DAPserver Studio updates the D20E module with the new IP address and restarts the device. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 41: Dapserver Studio Sync Project

    48 • Save a project; see subsection: Save a project on page 48 • Delete a project; see subsection: Delete a project on page 49 D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 42: Create A Project

    A D20E project must be created from a blank template. If your D20E is to be connected to a GE Grid Solutions D20, D20MX, D400, or DMC490 device, only use the device template files provided on the D20E Doc CD. Do not use the device template files available on DAPserver Studio.
  • Page 43 IO Provider with scaling, controls and alarm values. The default projects vary for the D20E-A, K and C models; accordingly, a specific project is available for each model. All D20E-S board variations share a single default project. D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 44 The D20E 61850 Provider must have GOOSE enabled. If there is no GOOSE configured in the SCL model, DAPserver Studio will not import the model. 11. Click Next. Result: The Summary page appears showing a configuration summary. 12. Click Finish. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 45: Open A Project

    Import an existing project from a folder To import an existing project file from a folder: Open DAPserver Studio. Click the From Folder box. Navigate to the project folder for the project configuration that is to be imported. D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 46: Import An Existing Project From A Device

    Type in the IP Address of the D20E (DAP IO). Type in the Username and Password. Click OK. Save a project To save a project configuration after modifications have been made: Open the Settings menu bar. Click Save. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 47: Delete A Project

    • Change an existing user’s password on page 51 • Change an existing user’s permissions on page 53 For detailed information on configuring the point types, see section Configuring points page 55. D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 48: Configure Ntp Time Sync

    Select Time Sync from the Device menu. Result: The NTP configuration window appears. Type in the IP Address of the D20E module. Type in the Username and Password login credentials. Result: The Time Sync window appears. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 49: Change An Existing User's Password

    For information on setting the clock, see section: Clock setting on page 118. Change an existing user’s password The default User names and Passwords are Username Password admin admin root root D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 50 Password. The root password provides limited DAPserver Studio access. It is the responsibility of the customer to change these default passwords. If a customer loses the password, the D20E module will need to be returned to GE Grid Solutions to be re- imaged in order to regain access.
  • Page 51: Change An Existing User's Permissions

    Double-clicking the user, or – Clicking the user, right-clicking a blank area of the window, and then clicking Edit at the bottom of the page. Result: The Users - “root” Configuration window appears. D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 52 13. Right-click a blank area of the screen. Result: The Task bar appears at the bottom of the screen. 14. Click Sync in the Task bar. Result: The Change Pending message is cleared. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 53: Configuring Points

    Table 4: Single Input States: State Input Off/Open On/Close Table 5: Double Input States: State Input Off/Open Transition On/Close Invalid The D20MX Substation Controller does not support double Digital Input from the D20E IO Module. D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 54: Cos And Soe

    (status is valid) and events can be reported. The oscillation recovery (Off Hysteresis) must be set lower than the oscillation On Trigger level to enable the input to be restored from oscillation. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 55: Digital Input Status Change Report As Counter Value

    Close When connecting to a D20MX Substation Controller, Open is OFF and Closed is ON. Class Specify the class to which the digital input belongs. Alarm Fault Status Information D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 56 Chatter Filter Specify the number of changes during the Chatter Filter On Trigger Time period that enables the Chatter Filter. The recommended value is 10 to 20 changes, to reduce event noise. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 57: Double Digital Input Configuration Procedure

    Change the Value Type setting for the first 32 points to Double Point. Multiple inputs mapped to the same physical index may cause these points to appear off- line and not be reported. The Inspect tool does identify conflicts under Physical Index 2. D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 58: Counter Points

    Figure 10 shows the indicator states triggered by Point 1 and Point 2. The first transition is from Point 1, then the opposite transition from Point 2, and so on. Figure 10: Dual point counter - state changes Point 1 Point 2 Counts GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 59 Signed or Unsigned Integer Signed Long Integer Short (32-bit IEEE format) Floating Double (64-bit IEEE format) Floating Initial Value Specify the initial counter value that appears in the database during initialization. D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 60 RTDB Point Specify the RTDB point whose value is reported for the counter. A custom window allows you to associate the counter to any analog input or counter available in the D20E. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 61: Analog Input Points

    The qualification time could be set on milliseconds or a number of power cycles. D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 62: Analog Input Point Quality Flag

    Point Name Specify the name of the point. The Point Name should be unique within the bay and group to which it belongs. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 63 The DAP will use this value as its minimum range (0%) during its calculation. Percentage Example: • Min Value = 0 • Max Value = 1000 • If percentage is at 50%, the Explore window shows 500 D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 64 Specify the value for the lowest-value limit. LL Name Specify the name for the lowest-value limit. L Limit Specify the value for the low-value limit. L Name Specify the name of the low-value limit. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 65 Publisher settings Reference Specify a text string that combines the bay name, Name group name, and provider name from the General tab. Point Specify the point description of the mapped analog Description input. D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 66: Analog Input Configuration Procedure

    DMC490), a signed 16 bit range (-32,768 to +32,767) is required from the D20E Publisher in a Signed Integer format. Since the Raw value is a signed 15 bit value, it must be doubled. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 67: Control Output Points

    Go to DNP3 Publisher > View > Analog Input > Protocol > Divisor column. Type 0.5 in the Divisor column. Click Save. For communication with a GE Grid Solutions device: • A D2x substation controller product supports Short Floating AI, which may benefit from the use of engineering units.
  • Page 68: Control Output Point Quality Flag

    Specify the initial counter value that appears in Open the database during initialization. Close Command Specify the digital output type used to Trip/Close Trip/ Type command the remote device. Close Regulating step Reset Freeze GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 69 Table 27: D20E-C - summary of control types and jumper setting positions on page Activity Timer Specify the length of time (in milliseconds) 0 to 100000 ms 10 ms before the signal is set to inactive. D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 70 Client. device Reset the remote device Freeze the counters in the remote device Trip Only an output in the remote device Close Only an output in the remote device GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 71: Check Operation Of The D20E

    Go to the Device menu > Explore tab view. Result: The Event Log appears in the bottom section of the Explore window; see Figure 7: Explore window - Main window and Event window on page 41 D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 72: Make D20E Device Setting Changes

    – Pseudo – View For detailed information on the Value Types and the specific Provider and Publisher settings, see Table 15: Provider IO and Publisher Protocol - Value Type: on page 68. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 73: Mounting A D20E Module

    D20E module to allow for cooling air flow and cable routing (1 RU = 1.75 inches or 44.5 mm). Required clearances The exterior dimensions of the D20E module are: • 19" wide x 5.2" high x 1.6" deep (483 mm x 132 mm x 63.5 mm) D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 74: Rack Mounting Procedure

    You are now ready to connect ground, power, and network link cabling to the D20E module: See chapter: Mounting a D20E Module on page 75. See chapter: Connecting Field Wiring to the D20E Module on page 87 GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 75 D20E for device setup and servicing. Figure 12: D20E side panel Ethernet and USB connectors 10/100 Mbps LAN#2 LAN #2 switched port 10/100 Mbps LAN#1 LAN #1 switched port USB 2.0 port D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 76: Connecting To Devices And Networks

    D20E module. Logon to the D20E with the default user ID root, and a default password root. Result: The Linux command prompt appears. a new IP address of 10.0.0.x GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 77: Network Data Communication

    Typically, you can modify an IP address from DAPserver Studio In the unlikely event that you are unable to access the D20E Ethernet I/O Module from DAPserver Studio, it may be necessary to modify an IP address using Linux. D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 78 10. Right-click a blank area of the screen. Result: The Task bar appears at the bottom of the screen. 11. Click Sync. Result: DAPserver Studio updates the D20E module with the new IP address and restarts the device. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 79 Exit the file by pressing Enter. Repeat step 6. and step 7. for eth1 using the ifcfg-eth1 command. Save the change. 10. Run the ifconfig command again to check that the IP addresses have changed as expected. D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 80: Daisy-Chaining D20E Modules

    Daisy-chaining D20E modules The daisy chaining of D20E Ethernet I/O Modules is shown in Figure 13. Figure 14: Daisy chaining of D20E modules LAN #1 D400 LAN #2 D20E-C D20E-K D20E-S D20E-A GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 81: Preliminary Power Up And Test

    (see Figure 15) with a ring lug. When making ground connections, ensure that all surfaces that are used for grounding are free of dirt, residue and corrosion. Figure 15: D20E protective earth ground Safety and protective earth ground screw D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 82 The Control Output external supplies listed above must be connected in order to facilitate the D20E-K (see section Control output external supply on page 90) and D20E-C Remote/ Local switch (see section D20E-C module -Local/Remote switch on page 100). GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 83: Preliminary Power-Up And Test Procedure

    If you did not order a GE Grid Solutions power supply (see Ordering guides on page 23 > D20E Power Supply), and instead are obtaining a non-GE power supply, ensure that you purchase a power supply unit that is: •...
  • Page 84 ‒ Analog Input 4+ Analog Input 4 ‒ Analog Input 5+ Analog Input 5 Shield/Screen Ground Shield/Screen Ground ‒ Analog Input 6+ Analog Input 6 ‒ Analog Input 7+ Analog Input 7 D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 85 Analog Input 32 ‒ External AI DC Loop Supply (+) External AI DC Loop Supply ( Chassis Earth Ground (PE GND on #10 Chassis Earth Ground (PE GND on #10 stud) stud) GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 86 REMOTE/LOCAL switch supply: TB2-54(+) and TB2-1(‒) Raise/Lower W2-W5, W7-W34 Raise/Lower supply: TB2-54(+/‒) and TB2-1(‒/+) Jumper W1: 1 & 2 See Table 24 (and Notes) for D20E-K (DB25) Interface jumper settings and terminal block connections. D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 87: Remote/Local Switch

    Figure shows the Trip/Close control output path. For the Trip/Close configuration the control supply is connected between on TB2-54 for positive polarity and TB2-1 for negative polarity. There are 32 dual Trip/Close outputs supported on the D20E-K. Figure 19: Trip/Close outputs GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 88: Form C Control Outputs

    DPST outputs are shown as DO(+/‒) in Table 23. 32 single DPST outputs are available on the D20E-K. The wiring connected to terminal block TB2 must not have exposed accessible conductors. The wire and cable connected must have at least a +80 C temperature rating. ° D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 89 Trip23/Raise5/Normal Open23/DO23+ Close23/Common23/DO23‒ Normal Close23 Trip24/Lower5/Normal Open24/DO24+ Close24/Common24/DO24‒ Normal Close24 Trip25/Raise4/Normal Open25/DO25+ Close25/Common25/DO25‒ Normal Close25 Trip26/Lower4/Normal Open26/DO26+ Close26/Common26/DO26‒ Normal Close26 Trip27/Raise3/Normal Open27/DO27+ Close27/Common27/DO27‒ Normal Close27 Trip28/Lower3/Normal Open28/DO28+ Close28/Common28/DO28‒ Normal Close28 Trip29/Raise2/Normal Open29/DO29+ Close29/Common29/DO29‒ GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 90 See Z2-Z7 jumper settings in Table 24 above. See the locations of jumpers Z1 to Z7 in Figure 23. TB2-1: External DC Supply (‒/+) TB2-2: No Connection Control Output TB2-3: External DC Supply (+/‒) TB2-4: Interposer Current Limit Input Control Output D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 91 The Z1, Z2 - Z7 jumpers are located on the D20E-K (DB25) interface module as shown in Figure 23. Figure 23: D20E-K (DB25) interface module - jumper locations Jumper Z1 Jumper Z2 and Z3 Jumper Z4 Jumper Z5 Jumpers Z6 and Z7 GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 92: D20E-S Digital Inputs Module

    Status Input 30 Status Wetting 1 to 64 Status Input 32 Status Wetting 1 to 64 Status Input 33 Status Wetting 1 to 64 Status Input 34 Status Wetting 1 to 64 D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 93 Status Wetting 1 to 64 Status Input 64 Status Wetting 1 to 64 External DI DC Supply (+/‒) External DI DC Supply (‒/+) No Connection No Connection (PE GND on #10 stud) GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 94: D20E-C Combination Inputs And Outputs Module

    Analog 12‒ Analog 13+ Analog 13‒ Shield/Screen Ground Analog 14+ Analog 14‒ Analog 15+ Analog 15‒ Shield/Screen Ground Analog 16‒ Analog 16+ Status Wetting 1to 16 Status Input 1 Status Wetting 1to 16 D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 95: D20E-C Module Digital Inputs

    TB2-15 to TB2-34 and TB2-64 to TB2-83. See Table 26 for termination block details. One shield termination is allocated for two adjacent inputs. See Table 26 for the terminal block assignments. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 96: D20E-C Module Control Outputs

    W1 and W2 Form C W3-W9, W11 LOCAL/REMOTE Switch supply: TB2-1(+/‒) and TB2-51(‒/+) W10 and W12 Raise/Lower W3-W9, W11 R/L supply TB2-2 (+/‒) and TB2-51 (‒/+) LOCAL/REMOTE Switch supply: TB2-1(+/‒) and TB2-51(‒/+) D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 97 One for the raise and • One for the lower. This provides support for 4 Raise/lower control outputs using 8 select relays on the D20E-C. Figure 21 shows the Raise/Lower output configuration. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 98: Powering-Up And Testing A D20E Module

    Firmware has been configured; see chapter: Configuring the D20E Firmware on page In addition, DAPserver Studio must be on-hand. You are now ready to power-up the D20E module and verify that the D20E module is functioning properly. D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 99 Analog Input – Counter Verify the D20E module operation of inputs or outputs by sending a DO command or reading the status of a DI and AI point through DAPserver Studio > Explorer. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 100 • D20E-K module front panel on page 106 • D20E-A module front panel on page 108 • D20E-S module front panel on page 109 • D20E-C module front panel on page 110 D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 101: Using The D20E Module

    LEDs on the D20E module side panel indicate the status of LAN1 and LAN2 Ethernet connections; see Table 29. Table 29: D20E Ethernet connection status LEDs LED Indicator Color Description RJ45 LAN 1 and 2 Green LINK Yellow ACTIVITY GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 102: Leds Common To All D20E Module Types

    Number of I/O connections on module type D20E-K D20E-A D20E-S D20E-C Digital Outputs (control) Analog Inputs Digital Inputs (status) For connection details, see chapter: Connecting Field Wiring to the D20E Module on page D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 103: D20E-K Module Front Panel

    The remote/local switch (S1) operation is described in section: Module remote/local switch on page 105. D20E-K connectors For information on Terminal Block 2 (TB2) connector assignments for the D20E-K module, D20E-K control outputs module on page 89. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 104: Operate A Raise/Lower Do Point

    Type in the ON TIME, OFF TIME and the REPEAT COMMAND number of repeat times. Press Enter again. Result: The R/L DO point is now active. 10. Repeat this procedure for each required R/L DO point. D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 105: D20E-A Module Front Panel

    Analog Digital Conversion (ADC) processes 1 and 2 for analog inputs. D20E-A connectors For information on Terminal Block 2 (TB2) connector assignments for the D20E-A module, D20E-A analog inputs module on page 87. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 106: D20E-S Module Front Panel

    DIGITAL INPUT 1 to 64 Blue Digital input 1 to 64 ON D20E-S connectors For information on Terminal Block 2 (TB2) connector assignments for the D20E-S module, D20E-S digital inputs module on page 95. D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 107: D20E-C Module Front Panel

    The remote/local switch (S1) operation is described in section: Module remote/local switch on page 105. D20E-C connectors For information on Terminal Block 2 (TB2) connector assignments for the D20E-C module, D20E-C combination inputs and outputs module on page 97. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 108: Maintaining A D20E Module Firmware

    DAPserver Studio may not connect (communicate) with the older D20E firmware device. However, most older firmware versions on the D20E will connect to the latest DAPserver Studio. Always use the latest version of DAPserver Studio. D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 109 Open the Device menu bar. 9.2. Click Explore. Result: Explorer opens. 10. Check that the firmware version and point status are all in a good state. You cannot downgrade to an older firmware version. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 110 If a D20E device is connected to: • A GE Grid Solutions D2x (for example, D20ME, iBOX, D25), D20MX, D400, or DMC490 device, only use the device template files provided on the D20E Doc CD. If you restore the D20E to the template files available on DAPserver Studio, the communications protocol settings will not be correct for connection to D20, D20MX, D400, or DMC490 devices.
  • Page 111 The D20E Ethernet I/O Modules do not require scheduled component or board level maintenance or replacement. Some maintenance tasks impact the D20E module firmware: • Firmware update on page 118 • Clock setting on page 118 • Time synchronization on page 118 D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 112: Fuse Replacement

    Use extra care when aligning the top Logic board with the bottom Interface board connectors. – Use the stand-off mounting holes as a locater guide before carefully and slowly pushing down on the Logic board GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 113: Dip Switch Settings

    CFG RESET 1-OFF 2-OFF 3-OFF 4-OFF 1-ON 2-OFF Do not press the CPU RST or the K10 Reset push-button switches. Pressing either of these switches causes the D20E module to reset or restart. D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 114: Firmware Update

    The D20E module can be time synchronized with an NTP time source on the network. See section: Configure NTP time sync on page 50. DO NOT use both DNP and NTP time sync simultaneously. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 115: Removing The D20E From Service

    • Device disposal Returning the D20E for maintenance If the D20E is being returned to GE Grid Solutions for maintenance (that is, RMA), you need to replace your configuration data with default configuration data prior to shipment. Prerequisites Prerequisites for removing your configuration data and sensitive information from the D20E: •...
  • Page 116: Device Disposal

    There are no special requirements for disposal of the unit at the end its service life. However, GE recommends that you destroy the device (i.e., shred, disintegrate, pulverize, or incinerate by burning the device in a licensed incinerator) as per Draft NIST Special...
  • Page 117 2.0 GHz to 2.7 GHz, 1 V/m IEC 61000-4-4 Electrical fast transient/burst immunity ±4.0 kV CM/TM test IEC 60255-22-4 IEEE C37.90.1 IEC 61000-4-5 Surge immunity test ±2.0 kV / 4.0 kV TM/CM D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 118 Dropping on each face Dropping on each corner Toppling (or pushover) For a total of 12 drops, 50 mm IEC 60068-2-78 Humidity Testing 96 hours steady state humidity at 40 °C and 93% RH GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 119 IEEE 802.3 CSMA/CD Access Method (and physical layer specifications) IEC 61850-3 Communication networks and systems in substation – General requirements IEEE 1613 Environmental and testing Requirements for Communications Network Devices in Substations D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 120: Dapserver Studio

    This section describes the following screen elements that appear in the DAPserver Studio user interface: • Main window – – My Devices – Recent • Configuration window – Window title bar – Menu bar – Main workspace – Task bar D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 121: Main Window

    • Recent: Similar to My Devices, a list of project names appears in this area for projects that have recently been worked on. Figure 30: DAPserver Studio - main window GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 122: Project Configuration Window

    Icon Description Close Standard Window commands. Minimize Maximize User Login Permanently save login information, or to just save the login information for the current session. About Show the firmware information of D20E D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 123: Menu Bars

    For example, the task bar can appear as: See the DAPserver Studio User Guide for details on each task bar command. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 124 DNP3 object implementation table on page 131 DNP3 IED protocol document The following document is provided for information purposes. D20E DNP3 Server Vendor Name: GE Grid Solutions Device Name: D20E Ethernet I/O Module Highest DNP Level Supported: Device Function: ...
  • Page 125: D20E Module Dnp3 Server Profile

     Either time-tagged and non-time-tagged for a single event  Configurable (attach explanation) Cold Restart Function: Warm Restart Function:   None None   Configurable Configurable Sends Multi-Fragment Responses:   GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 126 Control Command Event - Command Status Control Command Event - T.T Command Status Binary Counter - All Variations All valid 32-Bit Binary Counter 81,82 16-Bit Binary Counter 81,82 32-Bit Delta Counter 81,82 16-Bit Delta Counter 81,82 D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 127 Short Floating 81,82 Analog Input Event - All Variations All valid 32-Bit Analog Input Event without Time 81,82 16-Bit Analog Input Event without Time 81,82 32-Bit Analog Input Event with Time 81,82 GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 128 0x17, 0x28,0x39 Control and list of points (usually one or more Event objects (usually one unrelated points). or more unrelated points) For point: • #1 to #255 use 0x17; • #256 to use 0x28; • #655356 D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 129 1F. Activate configuration F. Initialize data 20. Authentication request 10. Initialize application 21. Authentication error Table 49: DNP3 Function Codes - Responds Responds (Hex) 81. Response 83. Authentication response 82. Unsolicited response GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 130 Miscellaneous This appendix provides the warranty and revision history. Warranty GE Grid Solutions warrants the D20E Ethernet I/O Module product for 10 years. For warranty details including any limitations and disclaimers, see the GE Grid Solutions Terms and Conditions at https://www.gegridsolutions.com/multilin/warranty.htm...
  • Page 131 Double Pole, Single Throw The new mark of conformity for CU (Customs Union) countries Electronic Access Point Electromagnetic Capability ElectroStatic Discharge Electronic Security Perimeter European Union Full Scale Analog Input General Electric D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 132 Trip/Close Terminal Block Time Delay Transmit Universal Serial Bus Coordinated Universal Time Unshielded Twisted Pair Volt Amps, unit of measure Volts, Alternating Current, unit of measure Volts, Direct Current, unit of measure GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 133 Method 1: To view the firmware version using DAPserver Studio: Go to Device menu > Explore tab. Result: The Explore window appears. Scroll down the main (top) window displayed for SYSTEM, REAL-TIME info Observe the information for the FMWVER line item. D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION...
  • Page 134 Use the Time Sync window in DAPserver Studio to enable NTP Client. Also, note that NTP should be used and DO NOT use both DNP and NTP simultaneously. Refer to section: Configure NTP time sync on page 50 for this procedure. GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 135 D20E Ethernet I/O Module Index RoHS ......................33 standards and protection .............. 121 CONFIGURATION DATA ACCESS EVENT LOG removal from GE device ..............119 operation ....................73 removal from PC ................. 120 ADDRESS CONFIGURE modification .................... 79 DAPserver Studio ...................21 setting ......................79 device ......................21...
  • Page 136 ............... 21, 79 DEBOUNCE FILTER PERIOD ..............56 DELETE PROJECT ..................49 DIGITAL COUNTER GUARANTEE ....................135 quality flag ....................61 DIGITAL INPUT chatter filter .....................56 configure parameters .................57 COS ......................56 HARDWARE OVERVIEW .................20 D20E-C .......................98 GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL...
  • Page 137 ................29 test .......................85 up ........................85 NAMING up procedure ..................102 Alstom products ..................12 PRECAUTIONS .....................17 GE products ..................... 12 warning symbols ...................19 NETWORK PREREQUISITES address setting ..................79 remove configuration data ............119 daisy-chain modules ................82 PREVENTATIVE MAINTENANCE ............
  • Page 138 SYNC PROJECT ...................43 Digital Input .....................57 TECHNICAL SUPPORT RACK MOUNTING ..................75 contact .......................10 RAISE/LOWER GE Grid Solutions web site ..............9 D20E-C control output ..............100 library ......................9 D20E-K .......................91 TERMINAL BLOCK RECOMMENDATIONS - STORAGE CONDITIONS ......34 summary ....................105 REMOTE/LOCAL SWITCH ..............

Table of Contents