Online View
June 2023
Table 7-1: Card health temperature flag
Icon
7.2
Details
Figure 7-5
Overview). The graphic objects not yet described are described.
Figure 7-5: Details
A. Service data
62
Meaning
No over temperature
The temperature, measured by
the internal temperature
sensor has exceeded the alert
limit of 70°C.
The temperature, measured by
the internal temperature
sensor has exceeded the shut
down limit of 80°C.
shows the Details page. Some graphic objects are already described, see
Operating Manual
MHM-97876
Action
---
Take appropriate measures to
reduce the environmental
temperature.
We recommend to replace the
card as parts might be stressed
or damaged because of the
high temperature. Take
appropriate measures to
reduce the environmental
temperature.
MHM-97876, Rev. 5.06