12-2. External output
With using external output function, some status signals are transmitted to the control PCB, and the
related LED lamp indicates the status of this product.
¢ Error status output
Signal on air conditioner error status is generated when a malfunction occurs.
 Circuit diagram example
Outdoor unit
control PCB
Connector
+
1
2
Error status
Output signal
 Optional part
Part name
External connect kit
12-2. External output
Connected unit
Vcc
Vcc
Power
supply
+
Load
-
33 ft (10 m)*
Signal
Locally purchased
Error
Normal
On
Off
Model name
UTY-XWZXZ3
• 1: Power supply
Voltage (Vcc): DC 24 V or less
• 2: Load
DC 500 mA or less
• *: Make the distance from the PCB to the
connected unit within 33 ft (10 m).