INSTALLATION
MANUAL
R410A Split Series
Models
RXS20G2V1B
RXS25G2V1B
RXS35G2V1B
RXG25E3V1B
RXG35E3V1B
ARXS20G2V1B
ARXS25G2V1B
ARXS35G2V1B
ARXG25E3V1B
ARXG35E3V1B
RKS20G2V1B
RKS25G2V1B
RKS35G2V1B
Installation manual
R410A Split series
Installationsanleitung
Split-Baureihe R410A
Manuel d'installation
Série split R410A
Montagehandleiding
R410A Split-systeem
Manual de instalación
Serie Split R410A
Manuale d'installazione
Serie Multiambienti R410A
Εγχειρßδιο εγκατÜστασηò
διαιροýìενηò σειρÜò R410A
Manual de Instalação
Série split R410A
Рóêоводство по монтажó
Серия R410A с раздельной óстановêой
Montaj kýlavuzlarý
R410A Split serisi
English
Deutsch
Français
Nederlands
Español
Italiano
ΕλληνικÜ
Portugues
Рóссêий
Türkçe
Table of Contents
loading

Summary of Contents for Daikin RXS20G2V1B

  • Page 1 Deutsch Split-Baureihe R410A Manuel d’installation Français Série split R410A Montagehandleiding Nederlands R410A Split-systeem Models Manual de instalación Español Serie Split R410A RXS20G2V1B RKS20G2V1B RXS25G2V1B RKS25G2V1B Manuale d’installazione Italiano Serie Multiambienti R410A RXS35G2V1B RKS35G2V1B Εγχειρßδιο εγκατÜστασηò RXG25E3V1B ΕλληνικÜ διαιροýìενηò σειρÜò R410A RXG35E3V1B Manual de Instalação...
  • Page 2 3SB63850-9E...
  • Page 3: Safety Precautions

    Safety Precautions • Read these Safety Precautions carefully to ensure correct installation. • This manual classifies the precautions into WARNING and CAUTION. Be sure to follow all the precautions below: they are all important for ensuring safety. WARNING....Failure to follow any of WARNING is likely to result in such grave consequences as death or serious injury. CAUTION....Failure to follow any of CAUTION may result in grave consequences in some cases.
  • Page 4: Precautions For Selecting The Location

    Accessories Accessories supplied with the outdoor unit: (A) Installation Manual (B) Drain plug (Heat pump-Models) (C) Refrigerant charge label There is on the bottom packing case. Precautions for Selecting the Location 1) Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will not be amplified. 2) Choose a location where the hot air discharged from the unit or the operation noise will not cause a nuisance to the neighbors of the user.
  • Page 5: Outdoor Unit Installation Drawings

    Outdoor Unit Installation Drawings Max. allowable length Min. allowable length 1.5m Max. allowable height Additionl refrigerant Wrap the insulation pipe with required for refrigerant the finishing tape from bottom 20g/m to top. pipe exceeding 10m in length. Gas pipe O.D. 9.5mm Liquid pipe O.D.
  • Page 6: Precautions On Installation

    Installation Guidelines • Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the installation guidelines below. • For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less. Wall facing one side Walls facing two sides More than 50...
  • Page 7 Outdoor Unit Installation Flaring the pipe end. (Cut exactly at 1) Cut the pipe end with a pipe cutter. right angles.) Remove burrs 2) Remove burrs with the cut surface facing down- ward so that the chips do not enter the pipe. Flaring Set exactly at the position shown below.
  • Page 8 Purging air and checking gas leakage. • When piping work is completed, it is necessary to purge the air and check for gas leakage. WARNING 1) Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle. 2) When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
  • Page 9 Outdoor Unit Installation Refilling the refrigerant. Check the type of refrigerant to be used on the machine nameplate. Precautions when adding R410A Fill from the liquid pipe in liquid form. It is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal operation. 1) Before filling, check whether the cylinder has a siphon attached or not.
  • Page 10: Standby Electricity Saving

    Standby Electricity Saving The standby electricity saving function turns OFF power supply to the outdoor unit and sets the indoor unit into standby electricity saving mode, thus educing the power consumption of the air conditioner. The standby electricity saving function works on the following indoor units. FTXS20G2V1B ATXS20G2V1B FTXS25G2V1B...
  • Page 11: Pump Down Operation

    Pump Down Operation In order to protect the environment, be sure to pump down when relocating or disposing of the unit. 1) Remove the valve cap from liquid stop valve and gas stop valve. Hexagonal 2) Carry out forced cooling operation. wrench Liquid 3) After five to ten minutes, close the liquid stop valve with a hexagonal wrench.
  • Page 12 Wiring WARNING 1) Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical shock, or fire. 2) Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the terminal block.) Doing so may cause electric shock or fire.
  • Page 13: Test Run And Final Check

    Test Run and Final Check Trial operation and testing. 1-1 Measure the supply voltage and make sure that it falls in the specified range. 1-2 Trial operation should be carried out in either cooling or heating mode. ■ For heat pump •...
  • Page 14 Two-dimensional bar code is a code for manufacturing. 3P203824-5A M07B117 (0711) HT...