13 Disposal; Overview: Disposal; To Pump Down; To Start And Stop Forced Cooling - Daikin Altherma EHVH08SU18CB6W Installer's Reference Manual

Low temperature split
Hide thumbs Also See for Altherma EHVH08SU18CB6W:
Table of Contents
If the 7H-01 error persists, the unit will stop operation and the user
interface will display an error code that needs to be reset manually.
Depending on the problem, this error code is different:
Error code
Detailed error
code
7H
04
7H
05
7H
06
INFORMATION
Error AJ-03 is reset automatically from the moment there is
a normal tank heat-up.
13
Disposal
NOTICE
Do NOT try to dismantle the system yourself: dismantling
of the system, treatment of the refrigerant, oil and other
parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for
reuse, recycling and recovery.
13.1

Overview: Disposal

Typical workflow
Disposing of the system typically consists of the following stages:
1
Pumping down the system.
2
Bringing the system to a specialized treatment facility.
INFORMATION
For more details, see the service manual.
13.2

To pump down

Example: To protect the environment, pump down when relocating
the unit or when disposing of the unit.
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump
down the system, and there is a leak in the refrigerant
circuit:
▪ Do NOT use the unit's automatic pump down function,
with which you can collect all refrigerant from the
system into the outdoor unit. Possible consequence:
Self-combustion and explosion of the compressor
because of air going into the operating compressor.
▪ Use a separate recovery system so that the unit's
compressor does NOT have to operate.
ERLQ004~008CA + EHVH04+08SU18+26CB6W
Daikin Altherma – Low temperature split
4P449978-1B – 2018.07
Description
The water flow problems mainly
occurred during domestic hot
water operation. Check the
domestic hot water circuit.
The water flow problems mainly
occurred during space heating
operation. Check the space
heating circuit.
The water flow problems mainly
occurred during defrost
operation. Check the space
heating circuit.
Additionally, this error code might
be an indication of frost damage
to the plate heat exchanger. In
that case, contact your local
dealer.
NOTICE
During pump down operation, stop the compressor before
removing the refrigerant piping. If the compressor is still
running and the stop valve is open during pump down, air
will be sucked into the system. Compressor breakdown or
damage to the system can result due to abnormal pressure
in the refrigerant cycle.
Pump down operation will extract all refrigerant from the system into
the outdoor unit.
1 Remove the valve cap from the liquid stop valve and the gas
stop valve.
2 Carry out forced cooling. See
cooling" on
page 85.
3 After 5 to 10 minutes (after only 1 or 2 minutes in case of very
low ambient temperatures (<−10°C)), close the liquid stop valve
with a hexagonal wrench.
4 Check on the manifold if the vacuum is reached.
5 After 2-3  minutes, close the gas stop valve and stop forced
cooling.
b
c
a
d
e
d
a
Gas stop valve
b
Closing direction
c
Hexagonal wrench
d
Valve cap
e
Liquid stop valve
13.3

To start and stop forced cooling

Confirm that DIP switch SW2 is in COOL mode.
1 Press the forced cooling operation switch SW1 to begin forced
cooling.
2 Press the forced cooling operation switch SW1 to stop forced
cooling.
H
C
E
O
A
O
SW1
T
L
SW2
NOTICE
Take care that while running forced cooling operation, the
water
temperature
remains
temperature read out of the indoor unit). You can achieve
this, for example, by activating all fans of the fan coil units.

13 Disposal