Quick Links

QUICK START GUIDE
GFK-3000B
Sep 2019
PACSystems
RX3i
TM
RACKLESS ENERGY PACK
(IC695ACC403)
Table of Contents
loading

Summary of Contents for Emerson PACSystems RX3i Energy Pack

  • Page 1 QUICK START GUIDE GFK-3000B Sep 2019 PACSystems RX3i RACKLESS ENERGY PACK (IC695ACC403)
  • Page 2: Table Of Contents

    Contents Overview ..................2 Hardware Installation ..............4 Mounting the Energy Pack on a DIN Rail ............... 4 Panel-Mounting the Energy Pack ................5 Cable Connections ............... 6 Connect Input Power to Energy Pack ..............7 Connecting the Energy Pack to the Controller ............8 Grounding ...................
  • Page 3 These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met during installation, operation, and maintenance. The information is supplied for informational purposes only, and Emerson makes no warranty as to the accuracy of the information included herein. Changes, modifications, and/or improvements to equipment and specifications are made periodically and these changes may or may not be reflected herein.
  • Page 4: Overview

    Quick Start Guide Chapter 1 GFK-3000B Sep 2019 1 Overview An Energy Pack is used in conjunction with a Controller to preserve user memory in the Controller during power fluctuations or outages. If system power is lost, the Energy Pack maintains power long enough for a Controller to write its user memory contents to non-volatile memory.
  • Page 5 Quick Start Guide Chapter 1 GFK-3000B Sep 2019 Ordering Information IC695ACC403 Energy Pack. Includes base, CapPack module and Energy Pack to Controller cable. IC695ACC413 Replacement CapPack module. IC695CBL003 Replacement 0.6m (24”) Energy Pack to Controller cable. Overview...
  • Page 6: Hardware Installation

    Quick Start Guide Chapter 2 GFK-3000B Sep 2019 2 Hardware Installation The Energy Pack can be mounted on a standard EN50022 DIN rail or an equipment panel. It is designed to be mounted adjacent to the Controller and connected to the Controller using the provided cable (IC695CBL003).
  • Page 7: Panel-Mounting The Energy Pack

    Quick Start Guide Chapter 2 GFK-3000B Sep 2019 Figure 2.1: Snap Mount to DIN Rail Panel-Mounting the Energy Pack Recommended fasteners: Four M4-0.7 machine screws with minimum length of 25mm (or 8-32, 1” min. length) and nuts. Caution • Over tightening the mounting screws could crack the plastic housing. Hardware Installation...
  • Page 8: Cable Connections

    Quick Start Guide Chapter 3 GFK-3000B Sep 2019 3 Cable Connections Figure 3.1: Input Power and Output Power/Control Connections Cable Connections...
  • Page 9: Connect Input Power To Energy Pack

    Quick Start Guide Chapter 3 GFK-3000B Sep 2019 3.1 Connect Input Power to Energy Pack IMPORTANT Before connecting input power, see complete installation instructions in the PACSystems Controllers: Battery and Energy Pack Manual, GFK-2741E or later. You will need: • A 24Vdc, 72W SELV power supply •...
  • Page 10: Connecting The Energy Pack To The Controller

    Quick Start Guide Chapter 3 GFK-3000B Sep 2019 Figure 3.2: Energy Pack Input Power Mating Connector (bottom view) Insert the plug into the Energy Pack’s Input Power connector and securely tighten the attaching screws. Connecting the Energy Pack to the Controller With power to the system turned off, use the supplied cable (IC695CBL003) to connect the output of the Energy Pack (green connector) to the 24Vdc input on the Controller (3-pin green connector) and to the serial...
  • Page 11: Grounding

    Quick Start Guide Chapter 4 GFK-3000B Sep 2019 4 Grounding Proper grounding of this device is essential. All ground wires must be as short as possible and terminated at the same grounding point. Figure 4.1: Frame Ground Connection Grounding...
  • Page 12: Initial Power-Up

    Quick Start Guide Chapter 5 GFK-3000B Sep 2019 5 Initial Power-up When 24Vdc power is first applied to the Energy Pack, the power-up process goes through the following steps: The IN LED turns on green. The Energy Pack performs a self-diagnostic test. If this test passes, output power to the Controller is turned on and the OUT LED turns on green.
  • Page 13: Led And Status Indications

    Quick Start Guide Chapter 6 GFK-3000B Sep 2019 6 LED and Status Indications The LEDs on the Energy Pack indicate its status. LEDState Energy Pack Status Green, solid Input power is applied and within the specified range. Red, solid Input power is outside the specified range. Input power is not applied.
  • Page 14: Led Indications: Special Cases

    Quick Start Guide Chapter 6 GFK-3000B Sep 2019 LED Indications: Special Cases All LEDs blinking in unison: See Firmware Updates, page 15. Energy Pack Status Bit Operation As shown in the table below, a CPU application program can automatically monitor the status of the attached Energy Pack via %S0014 (PLC_BAT) and %SA0011 (LOW_BAT).
  • Page 15: Replacing The Cap Pack Module

    Quick Start Guide Chapter 7 GFK-3000B Sep 2019 7 Replacing the CAP Pack Module The CAP Pack can be removed and replaced while power is applied to the Energy Pack (hot swapped.) Caution • When hot swapping CapPacks, do not cycle power until the new CapPack is fully charged and operational.
  • Page 16 Quick Start Guide Chapter 7 GFK-3000B Sep 2019 Caution • Over tightening the mounting screws could crack the plastic housing. Use the four screws provided to secure the CapPack to the base. When the CapPack is first inserted, the STAT LED blinks green while the CapPack is charging.
  • Page 17: Firmware Updates

    Quick Start Guide Chapter 8 GFK-3000B Sep 2019 8 Firmware Updates The firmware for the Energy Pack is automatically updated by the Controller. At power-up, the Controller checks the version of Energy Pack firmware to verify compatibility with the Controller firmware. If an update is needed, the Controller performs it automatically.
  • Page 18: Additional Information

    PACSystems Controllers: Battery and Energy Pack Manual, GFK-2741E or later PACSystems RX3i / Series 90-30 Installation and Maintenance Requirements, GFK- 2975 For user manuals, product updates and other information go to the Support website, https://www.emerson.com/Industrial-Automation-Controls/support refer to Controllers and IO, RX3i Rackless Controllers. Additional Information...
  • Page 19 Note: If the product is purchased through an Authorized Channel Partner, please contact the seller directly for any support. Emerson reserves the right to modify or improve the designs or specifications of the products mentioned in this manual at any time without notice. Emerson does not assume responsibility for the selection, use or maintenance of any product.

This manual is also suitable for:

Ic695acc403

Table of Contents