7. COMPRESSOR CONTROL
1. OPERATION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in the table 6.
(Table 6 : Compressor Operation Frequency Range)
AO*G18LAC2
2. OPERATION FREQUENCY CONTROL AT START UP
The compressor frequency soon after the start-up is controlled as shown in the figure 9.
(Fig.11 : Compressor Control at Start-up)
82rps
60rps
40rps
Cooling
Min
Max
15rps
85rps
60 - 720sec
180sec
240 - 900sec
01-17
Heating
Min
Max
21rps
130rps
120sec
360 - 1020sec