Symptom: The Compressor Does Not Start (Space Heating Or Domestic Water Heating); Symptom: The System Is Making Gurgling Noises After Commissioning - Daikin ERLA11D V3 Series Installer's Reference Manual

Hide thumbs Also See for ERLA11D V3 Series:
Table of Contents
15
|
Troubleshooting

15.3.3 Symptom: The compressor does NOT start (space heating or domestic water heating)

15.3.4 Symptom: The system is making gurgling noises after commissioning

Installer reference guide
260
Possible causes
The compressor cannot start if the
water temperature is too low. The unit
will use the backup heater to reach the
minimum water temperature (12°C),
after which the compressor can start.
The preferential kWh rate power supply
settings and electrical connections do
NOT match
The preferential kWh rate signal was
sent by the electricity company
Domestic hot water (including
disinfection) and space heating
operation are scheduled to start at the
same time.
Possible cause
There is air in the system.
Incorrect hydraulic balance.
Corrective action
If the backup heater doesn't start
either, check and make sure that:
The power supply to the backup
heater is correctly wired.
The backup heater thermal protector
is NOT activated.
The backup heater contactors are
NOT broken.
If the problem persists, contact your
dealer.
This should match with the connections
as explained in:
"9.3.1  To connect the main power
4
supply" [
 123]
"9.1.4  About preferential kWh rate
4
power
supply" [
 116]
"9.1.5 
Overview
connections
except
4
actuators" [
 117]
In the user interface of the unit, go to
[8.5.B] Information > Actuators >
Forced off contact.
If Forced off contact is On, the
unit is operating under the preferential
kWh rate. Wait for the power to return
(maximum 2 hours).
Change the schedule to not start both
operation modes at the same moment.
Corrective action
Purge air from the system.
To be performed by the installer:
1
Perform hydraulic balancing to
assure that the flow is correctly
distributed between the emitters.
2
If
hydraulic
balancing
sufficient,
change
limitation settings ([9-0D] and [9-0E]
if applicable).
ERLA11~16D + EBVH/X11+16S18+23D
of
electrical
external
(a)
is
not
the
pump
Daikin Altherma 3 R F
4P643602-1B – 2022.05
Table of Contents
loading

Table of Contents