Honeywell Ex-Or MSB1001T Installation And Commissioning Instructions

Honeywell Ex-Or MSB1001T Installation And Commissioning Instructions

Ip65 battenfit sensor

Quick Links

IP65 BattenFit Sensor
MSB1001T - Switching
MSB1001PT - Switching with photocell
Installation and Commissioning
Instructions
Note: QuickSet Pro or HP18* required for commissioning
* Please note that the HP18 offers different/limited programming options
loading

Summary of Contents for Honeywell Ex-Or MSB1001T

  • Page 1 IP65 BattenFit Sensor MSB1001T - Switching MSB1001PT - Switching with photocell Installation and Commissioning Instructions Note: QuickSet Pro or HP18* required for commissioning * Please note that the HP18 offers different/limited programming options...
  • Page 2 IP65 BattenFit Sensor: MSB1001T - Switching MSB1001PT - Switching with photocell Only suitably qualified personnel should install this equipment. This passive infrared presence detector is designed to be fitted to a batten-style luminaire. Installation 1. Remove the M20 knockout from the end cap of the luminaire. 2.
  • Page 3: Electrical Connections

    SEE TEXT Polarising Plate (not supplied) The purpose of the polarising plate is to ensure that the sensor does not rotate from the correct position, i.e. pointing vertically downwards, during transport or installation. The two overall dimensions marked ‘SEE TEXT’ need to be made such that when the plate is positioned against the inner face of the luminaire end cap, it cannot rotate.
  • Page 4 Detection Profile Plan View Detection pattern is a 360 cone shape. Diameter is 2.25 x the mounting height. The squares show the arrangement of the detection pattern. BATTEN LUMINAIRE Fig. 8 2.5m Direction of most commonly used entry into detection zone, i.e.
  • Page 5 If the distance between the bottom of the sensor and the bottom of the end cap exceeds 59mm (in the case of square covers) or 82mm (for rounded covers), there may be a blind spot in the detection zone. Fig. 10 Walk Testing In order to verify the installation, there is an inbuilt facility (Walk Test Mode) to temporarily reduce the time delay to 10 seconds.
  • Page 6 Photocell The photocell (MSB1001PT only) can be programmed to operate in one of two ways: Active or Passive. (Factory default setting is ‘Passive’.) In all operating modes, the photocell can hold lights off as a vacant area becomes occupied, and if the light level falls too low during the period of occupancy, the lights switch on.
  • Page 7 Parameter Options - MSB1001PT only Programming is carried out using an infrared programming tool. Please note that the full range of parameters is accesible via the QuickSet Pro; the HP18 offers different/limited programming options. Off Delay The Off Delay may be set between 1 minute and 96 hours using the QuickSet Pro, or at 5, 10 or 20 minutes with the HP18.
  • Page 8 (e.g. ‘2D’ luminaires) may specify a maximum number of switching cycles in order to achieve a predicted lamp life. Please check with the manufacturer of the luminaires to ensure that they are compatible with automatic controls in this respect. Honeywell Ex-Or Albery House, Springfield Road, At the end of their useful life...