AERMEC S.p.A AERMEC S.p.A. reserves the right at any moment to make any modifications considered necessary to improve our products and is not obliged to add these modifications to machines that have already been fabricated, delivered or are under construction.
Page 3
Plasmacluster, this device is a standard equipment on each unit high Aware of the importance of air renewal and purification, AERMEC RePuro, has been designed in order to e ciency offer the best performances compared to the products currently available on the market, we can high- light: 1 –...
3.5. Electrical power cable ................................6 3.6. Connecting cable for the wired control panel ........................6 3.7. Installation ....................................6 4. INTRODUCTION TO RESIDENTIAL VENTILATION AND THE AERMEC RePuro TECHNICAL SOLUTION ........7 4.1. INDOOR AIR QUALITY (IAQ) ..............................7 4.2. Plasmacluster ..................................12 4.3.
− Before commencing any works The AERMEC RePuro units are manu- it is necessary to CAREFULLY READ factured in accordance with recog- THE INSTRUCTIONS AND MINIMISE nised technical standards and safety ANY RISKS BY TAKING APPROPRIATE regulations.
For all future reference and com- • the unit and any accessories 3.4. LOOSE ITEMS munication with AERMEC S.p.A. it is must be appropriately secured necessary to state the serial number. on the transport device with The components for the installation...
the unit. Before installation, check the technical spaces required: Before starting with the installation it • for installation; is necessary to open the heat exchang- • for the set up of the flow and expul- er unit panel and remove the material sion ducts;...
INTRODUCTION TO RESIDENTIAL VENTILATION AND THE AERMEC RePuro TECHNICAL SOLUTION 4.1. INDOOR AIR QUALITY (IAQ) - biological outdoors. In terms of preventing health risks deriv- Due to infiltration caused by the opening - physical ing from ambient factors it is only in recent...
Page 10
chemical-physical pollutants, piratory symptoms. A collection of studies percentages that occur to people living in shown above, are not the only elements on this subject is published in DAMPNESS environments with polluted air. that contribute to the pollution of the in- AND MOULD from 2009 produced by the door environment.
4.2. PLASMACLUSTER and viruses present in the air. It is not an electrostatic filter, having an air Each RePuro unit is supplied as standard purification mechanism. Using a genera- with a Plasmacluster filter. tor it decomposes certain water molecules Plasmacluster is a system of ion genera- present in the air (humidity) by electrical tion suitable for the purification of internal discharges, creating a flow of hydrogen and...
Page 12
Compared to electrostatic filter the Plas- its appearance. From this it can be easily described here. macluster technology has four main ad- understood that over time there is a pro- vantages: gressive degradation in filter efficiency of • In electrostatic filters the air is forced such devices.
Page 13
Mould From 50 to 100% of total As with viruses and bacteria, the ions freed by Plasmacluster work on the pro- liferation of the mould in closed spaces. . Spontaneous dust A test conducted by Japanese researchers From 0 to 25% of total formation has shown how the exposure of a normal PVC window to the action of the Plasma-...
Page 14
4.3. REFERENCE STANDARD FOR THE renewal and not aeration: opening and III: Acceptable, moderate requirement lev- VENTILATION OF RESIDENTIAL BUILD- closing windows is not considered an effec- el, to be sued for existing buildings. INGS tive system for the renewal of air. IV: Values outside of the criteria for the cat- The concept of air ventilation for confine How and when to renew is considered in...
Page 15
4.4. EXAMPLE OF ENERGY SAVING ery solution used in a residential building face area of 150m . The dwelling consists of CALCULATION located in 2468 DD climatic zone (EN ISO two stacked floors. 15927-6:2007). The following shows an analysis made on The analysis takes into consideration a por- the energy advantage for the heat recov- tion of a twin apartment, with useful sur-...
Page 16
4.5. HEAT RECOVERY ENERGY EFFI- extract), the efficiency becomes the ratio = 20°C internal air CIENCY between temperature difference: The supply air temperature is determined once the efficiency of the heat recovery Generally heat exchanger energy ef- real η = unit is known.
DESCRIPTION RePuro is an innovative counter-flow heat ditional fresh air systems or mechanical recovery system which ensures the correct ventilation only. renewal of air to indoor environments. PLASMACLUSTER ionising filter capable of Through the use of heat exchangers of destroying pollutants by decomposing high efficiency up to 90%, RePuro allows their molecules.
G4 supply air filter (standard the 20 speeds use the selection programme Air flow - Efficiency curve. configuration). available on www.aermec.com. Air flow - Pressure Curves with G2 extract air filter and efficiency class F7 supply air filter (accessory FF7170).
Page 21
RePuro100 - Sound power output at supply opening [Pa] RePuro100 Sound power 64dB(A) Air flow curve - Available static pressure 60dB(A) 56dB(A) ⑳ 50dB(A) ⑰ ⑭ ⑪ ⑦ [m³/h] Air flow RePuro100 - Sound power output at intake opening [Pa] RePuro100 Sound power 60dB(A)
Page 22
G4 supply air filter (standard the 20 speeds use the selection programme Air flow - Efficiency curve. configuration). available on www.aermec.com. Air flow - Pressure Curves with G2 extract air filter and efficiency class F7 supply air filter (accessory FF7170).
Page 23
RePuro170 - Sound power output at supply opening [Pa] RePuro170 Sound power Air flow curve - Available static pressure 64dB(A) 60dB(A) 56dB(A) 50dB(A) ⑳ ⑰ ⑭ ⑪ ⑦ [m³/h] Air flow RePuro170 - Sound power output at intake opening [Pa] RePuro170 Sound power 64dB(A)
Page 24
G4 supply air filter (standard the 20 speeds use the selection programme Air flow - Efficiency curve. configuration). available on www.aermec.com. Air flow - Pressure Curves with G2 extract air filter and efficiency class F7 supply air filter (accessory FF7350).
Page 25
RePuro250 - Sound power output at supply opening [Pa] RePuro250 Sound power Air flow curve - Available static 64dB(A) pressure 60dB(A) ⑳ 56dB(A) ⑰ 50dB(A) ⑭ ⑪ ⑦ [m³/h] Air flow RePuro250 - Sound power output at intake opening [Pa] RePuro250 Sound power 64dB(A)
Page 26
G4 supply air filter (standard the 20 speeds use the selection programme Air flow - Efficiency curve. configuration). available on www.aermec.com. Air flow - Pressure Curves with G2 extract air filter and efficiency class F7 supply air filter (accessory FF7350).
Page 27
RePuro350 - Sound power output at supply opening [Pa] RePuro350 Sound power Air flow curve - Available static pressure 70dB(A) 66dB(A) 62dB(A) ⑳ ⑰ 57dB(A) ⑭ ⑪ ⑦ [m³/h] Air flow RePuro350 - Sound power output at intake opening [Pa] RePuro350 Sound power 70dB(A)
Page 28
G4 supply air filter (standard the 20 speeds use the selection programme Air flow - Efficiency curve. configuration). available on www.aermec.com. Air flow - Pressure Curves with G2 extract air filter and efficiency class F7 supply air filter (accessory FF7650).
Page 29
RePuro450 - Sound power output at supply opening [Pa] RePuro450 Sound power Air flow curve - Available static pressure 70dB(A) 66dB(A) ⑳ 62dB(A) ⑭ ⑰ 57dB(A) ⑦ ⑪ [m³/h] Air flow RePuro450 - Sound power output at intake opening [Pa] RePuro450 Sound power 70dB(A)
Page 30
G4 supply air filter (standard the 20 speeds use the selection programme Air flow - Efficiency curve. configuration). available on www.aermec.com. Air flow - Pressure Curves with G2 extract air filter and efficiency class F7 supply air filter (accessory FF7650).
Page 31
RePuro550 - Sound power output at supply opening [Pa] RePuro550 Sound power Air flow curve - Available static pressure 70dB(A) 66dB(A) ⑳ ⑰ ⑭ ⑪ 62dB(A) ⑦ 57dB(A) [m³/h] Air flow RePuro550 - Sound power output at intake opening [Pa] RePuro550 Sound power Air flow curve - Available static...
Page 32
G4 supply air filter (standard the 20 speeds use the selection programme Air flow - Efficiency curve. configuration). available on www.aermec.com. Air flow - Pressure Curves with G2 extract air filter and efficiency class F7 supply air filter (accessory FF7650).
Page 33
RePuro650 - Sound power output at supply opening [Pa] RePuro650 Sound power Air flow curve - Available static pressure 70dB(A) ⑪ 66dB(A) ⑰ ⑭ ⑳ ⑦ 62dB(A) 57dB(A) [m³/h] Air flow RePuro650 - Sound power output at intake opening [Pa] RePuro650 Sound power Air flow curve - Available static...
Page 34
10.8. PLS - PLSM Plenum performances PLS350W PLS650W Plenum performances with water heat exchanger coil Option “W” PLSM350W PLSM650W Air flow Cooling Total cooling capacity 1730 3470 Sensible cooling capacity 1300 2480 Sensible/Total heat ratio 0,751 0,715 Water flow rate Water side pressure drop 10,8 Water inlet temperature...
ACCESSORIES RePuro 250R 350R 450R 550R 650R INSTALLATION Anti-vibration feet Anti-vibration brackets FILTERS FF7170 Supply air F7 filter FF7350 Supply air F7 filter FF7650 Supply air F7 filter PLENUM supply with multiple outlets PLS350 Empty PLS350W Coil and drain pan (option VCH) PLS350E Electric Heater PLS350L...
Page 36
Anti-vibration feet For floor mounted units. Feet in plastic material to screw onto the base. When selecting consider the space needed for the condensate discharge. Support brackets with anti-vibration items For floor mounted units. Support bracket in painted galvanised steel to screw onto the base. When select- ing consider the space needed for the con- densate discharge.
Page 37
VCHR The valve is of the on-off type and is 230V single phase powered. Three way valve kit with insulation For plenum PLS and PLSM with water coil (W). Complete with connection tube and fix- ings between valve and heat exchanger coil.
Page 38
VMF VOC Air quality sensor accessory (see the item on the description of the VMF-E5B) VMF E5 ing to time-clocks and/or by measuring the air quality obtained with the VMF- Wall recess mounted supervisor control VMF-E5B VOC accessory. panel • Domestic hot water module: complete Available in two colours: management of the production of domes- •...
Page 39
PLS350 PLSM350 * - W - WE - WL - WLE * - W - WE - WL - WLE PLS - PLSM Plenum for air treatment and distribu- tion. Plenum with acoustic lining, for connec- tion to the inlet of the supply air coming from the RePuro unit.
Page 40
PLS350 PLS650 PLS - PLSM configurations PLSM Diameter flanges Diameter Plenum Plenum Configuration of the air post-treatment elements [mm] flanges [mm] PLS350 PLSM350 80(x6) Empty and without electrical box PLS350W 80(x6) PLSM350W Battery and tray (VCH option) PLS350E 80(x6) PLSM350E Electrical Resistance PLS350L 80(x6)
INSTALLATION OF THE HEAT RECOVERY UNIT 13.1. PRELIMINARY OPERATIONS Prepare the system for the electrical power and connection for the wired control panel. Prepare an adequate condensate drainage system. RePuro100 - RePuro170 The components for the installation of the RePuro unit are contained within the unit. Before commencing with the installation it is necessary to open the panel and recover the material contained within.
Page 43
RePuro250 - RePuro350 The components for the installation of the RePuro unit are contained within the unit. Before commencing with the installation it is necessary to open the panel and recover the material contained within. RePuro450 - RePuro550 - RePuro650 The components for the installation of the RePuro unit are contained within the unit.
13.2. CEILING INSTALLATION Warning: The unit must be installed hori- zontal; check with a spirit level. RePuro100 - RePuro170 Warning: Use expansion plugs suitable for the mounting material. Warning: The ceiling must be capable of safely carrying the weight of the unit. RePuro100-170 To ceiling mount the unit it is necessary to use the 4 mounting brackets supplied...
13.3. WALL INSTALLATION Warning: The unit must be installed hori- RePuro100 - RePuro170 zontal; check with a spirit level. Warning: Use expansion plugs suitable for the mounting material. Warning: The wall must be capable of safely carrying the weight of the unit. RePuro100-170 To wall mount the unit it is necessary to use the 4 mounting brackets supplied...
13.4. FLOOR INSTALLATION Warning: The unit must be installed hori- zontal; check with a spirit level. Warning: The floor must be capable of safely supporting the weight of the unit. Warning: Before proceeding with the in- stallation refer to the accessory manuals. Warning: Before proceeding with the in- stallation apply the correct accessory for the type of installation.
13.5. ELECTRICAL CONNECTIONS Power supply 230V ~50Hz. The unit is supplied with the power cable 2 REPURO m long and Schuko plug. 100 - 170 Provide a Schuko socket in proximity to the unit. To protect the unit against short circuits provide in the power supply line a circuit breaker 2A, 250V (IG) with minimum open- ing contact of 3 mm.
13.6. CONNECTING THE AIR DUCT TO THE UNIT RePuro100 - RePuro170 : - To identify the location of the ducts refer to the drawing. - Connect the ducting to the connectors, fix the ducting with ties. Extract air Supply air RePuro250 - RePuro350 : - Mount the 4 connectors to the unit flange to the drawings.
13.7. CONDENSATE DISCHARGE The condensate discharge connection has an RePuro external diameter of 20 mm. The condensate discharge system must be 100mm sized for the condensate flow produced by the unit and any other unit (recovery unit, plenum, etc.) connected to the same system. 60mm Procedure for mounting the connection: - Identify the condensate discharge hole and...
INSTALLATION OF THE WIRED PANEL The AERMEC RePuro units are controlled by the user through a wired wall VMF system panel of an especially low profile design 12 mm. The wired panel can be wall mounted over a recessed electrical wall box. (E.g.: module 503).
14.2. COMPATIBILITY BETWEEN THE WIRED CONTROL PANEL AND THE ELECTRICAL WALL BOXES The wired control panel can be mounted to various types of electrical wall boxes. Several examples are shown below: Type Type 503E 503E Type Type 502E 502E Type Type Wall Wall...
ORDINARY MAINTENANCE Any cleaning procedure is forbidden before disconnecting the unit from the power sup- ply. Check for the absence of voltage before pro- ceeding. Periodic maintenance is fundamental to keep the unit in perfect efficiency both func- tionally and for energy. RePuro100 - RePuro170 It is fundamental to provide annual checks.
Page 56
AERMEC S.p.A. Aermec si riserva la facoltà di apportare in qualsiasi momento tutte le modifiche ritenute necessarie per il miglioramento del prodotto con 37040 Bevilacqua (VR) - Italy eventuale modifica dei relativi dati tecnici. Via Roma, 996 - Tel. (+39) 0442 633111 Telefax (+39) 0442 93730 - (+39) 0442 93566 www.aermec.com...