D279A Independent Zone Control; Keyswitch; Description; Programming - Bosch D9412GV3 Operation And Installation Manual

Hide thumbs Also See for D9412GV3:
Table of Contents
.

Figure 28: Power at Keypads

1
1 - To control panel
2 - +12.0 VDC
3 - Data
11.3

D279A Independent Zone Control

Any on-board or OctoPOPIT point can be programmed so that the D279A Independent Zone Control operates
as independent point control (arming and disarming the point).
Refer to Point Assignments in the D9412GV3/D7412GV3 Program Entry Guide (P/N: F01U170807) for
programming information. Refer to the D279A Operation and Installation Instructions (P/N: 46458) for wiring
and operation instructions.
11.4

Keyswitch

11.4.1 Description

A maintained or momentary contact arming station (keyswitch) can be connected to master arm or disarm any
of the areas in the system. The keyswitch is connected to an on-board or off-board point's sensor loop. Relays
can be programmed to activate arming status LEDs for keyswitch arming stations. Refer to Relays in the
D9412GV3/D7412GV3 Program Entry Guide (P/N: F01U170807).

11.4.2 Programming

Refer to Point Assignments in the D9412GV3/D7412GV3 Program Entry Guide (P/N: F01U170807) for the
correct programming for points used for keyswitches.

11.4.3 Installation

For maintained switches, connect the EOL resistor for the point at the keyswitch so that the switch opens the
circuit when it operates. A short on the circuit produces an alarm if the area is armed and a trouble if it is
disarmed. Refer to Figure 29 on page 58.
For momentary keyswitches, connect the EOL resistor at the keyswitch point so that when the keyswitch
operates, it shorts the resistor. An open on the circuit causes an alarm if the area is armed and a trouble if it is
disarmed. Refer to Figure 29 on page 58.

11.4.4 Operation

Maintained Contact
If the point to which the keyswitch is connected is programmed for a maintained contact, an open on the arming
circuit arms the area. All faulted points are force armed, regardless of the entry in the FA Bypass Max program
item. Returning the circuit to normal disarms the area. Refer to Area Parameters and Point Assignments in the
D9412GV3/D7412GV3 Program Entry Guide (P/N: F01U170807).
Bosch Security Systems, Inc. | 10/10 | F01U143070-03
D9412GV3/D7412GV3 | Operation and Installation Guide | 11.0 Arming Devices
2
3
3
4
4 - Common
5 - D8132 or external power supply
5
2
4
57

Hide quick links:

Table of Contents
loading

This manual is also suitable for:

D7412gv3

Table of Contents