Fujitsu AO G36KBTB Series Service Instruction page 67

1 phase type room air conditioner
Hide thumbs Also See for AO G36KBTB Series:
Table of Contents
Trouble shooting 23
OUTDOOR UNIT Error Method:
Compressor Temp. Thermistor Error
Detective Actuators:
Compressor temperature thermistor
Forecast of Cause :
1. Connector connection failure, open
2. Thermistor failure
3. Main PCB failure
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check
(Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 8".
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB P10:1-3 voltage value =5V
Remove the thermistor from Main PCB, check the voltage.
1
2
3
1
2
3
P10
If the voltage does not appear, replace Main PCB,
and execute the check operation again.
Indicate or Display:
Error code : 72
Detective details:
Compressor temperature thermistor short or open detected
02-24
Outdoor unit :
Mode Error L1 L2
2
7
2
: Light OFF
: Light ON
DC
L3
L4
L5
L6
n : n times blinking