Cisco Catalyst 8500 Series Regulatory Compliance And Safety Information Manual
Cisco Catalyst 8500 Series Regulatory Compliance And Safety Information Manual

Cisco Catalyst 8500 Series Regulatory Compliance And Safety Information Manual

Cisco systems atm switch regulatory compliance and safety information
Hide thumbs Also See for Catalyst 8500 Series:

Quick Links

Regulatory Compliance and Safety Information

for the Catalyst 8500 and LightStream 1010 Series
Read this document before installing or servicing the following Catalyst 8500 and LightStream 1010
series switches:
Catalyst 8540 MSR
Catalyst 8510 MSR
Catalyst 8540 CSR
Catalyst 8510 CSR
LightStream 1010 ATM switch
Note
Only trained and qualified service personnel (as defined in IEC 60950 and AS/NZS 3260) should install,
replace, or service the equipment. Install the system in accordance with the U.S. National Electric Code
if you are in the United States.
This warning symbol means danger. You are in a situation that could cause bodily injury. Before you
Warning
work on any equipment, be aware of the hazards involved with electrical circuitry and be familiar
with standard practices for preventing accidents.
The following guidelines are applicable for products intended for use in Australia:
Note
Only trained and qualified service personnel should install, replace, or service the equipment, as
defined by AS/NZS 3260.
Incorrect connection of this or connected equipment to a general purpose outlet could result in a
hazardous situation.
This document includes the following sections:
Site Preparation, page 2
Regulatory Standards Compliance, page 9
Translated Safety Warnings, page 16
Corporate Headquarters:
Cisco Systems, Inc., 170 West Tasman Drive, San Jose, CA 95134-1706 USA
Copyright © 2003 Cisco Systems, Inc. All rights reserved.
Table of Contents
loading

Summary of Contents for Cisco Catalyst 8500 Series

  • Page 1: Regulatory Compliance And Safety Information

    Site Preparation, page 2 • Regulatory Standards Compliance, page 9 • Translated Safety Warnings, page 16 • Corporate Headquarters: Cisco Systems, Inc., 170 West Tasman Drive, San Jose, CA 95134-1706 USA Copyright © 2003 Cisco Systems, Inc. All rights reserved.
  • Page 2: Site Preparation

    Site Preparation Related Documentation, page 26 • Obtaining Documentation, page 27 • Obtaining Technical Assistance, page 28 • Obtaining Additional Publications and Information, page 30 • Site Preparation This section describes the site requirements for installing the Catalyst 8500 MSR, Catalyst 8500 CSR, and LightSteam 1010 series switches.
  • Page 3: Rack-Mounting The System

    Rack-Mounting the System A rack-mount kit and cable guides come with the system. The kit is not suitable for racks with obstructions (such as a power strip) that could impair access to system components. Allow sufficient clearance around the rack for system maintenance. Ensuring Proper Airflow Follow these guidelines to ensure proper airflow: •...
  • Page 4 Site Preparation Figure 1 Catalyst 8540 Chassis Standard Equipment Rack Dimensions 19.25 " (48.09 cm) 17.25 " (45.09 cm) Regulatory Compliance and Safety Information for the Catalyst 8500 and LightStream 1010 Series 78-14229-02...
  • Page 5: Lifting The System

    Figure 2 Catalyst 8510 and LightStream 1010 Chassis Standard Equipment Rack Dimensions Ensure that the weight of the chassis does not make the rack unstable. Secure telco racks with ceiling • brackets if the rack is populated with heavy equipment. •...
  • Page 6: Power Considerations

    Ensure that power is removed from the DC circuit before installing or removing power supplies. • Tape the switch handle of the DC circuit breaker in the off position. • Use only copper conductors to connect to a DC terminal block.
  • Page 7: Preventing Esd

    Using Redundant Power If your system includes an optional redundant (second) power supply, connect each of the two power supplies to different input power sources. Failure to do so makes the system susceptible to total power failure in the event that one of the power supplies fails. Preventing ESD Electrostatic discharge (ESD) damage occurs when electronic cards or components are mishandled and can result in complete or intermittent failures.
  • Page 8: Disconnecting Power

    For DC power supplies, locate the circuit breaker on the panel board that services the DC circuit, • switch the circuit breaker to the off position, and tape the switch handle of the circuit breaker in the off position. •...
  • Page 9: Disposing Of The System

    Direct the flow of cooling air through the chassis • Protect the backplane from dust • Disposing of the System Dispose of the system and its components (including batteries) as specified by all national laws and regulations. Regulatory Standards Compliance This section includes the regulatory compliance, safety, and EMC standards.
  • Page 10: Fcc Part 68 Notice

    The T1 IMA (Model C85MS-8T1-IMA) and CES T1 (Model WAI-T1C-4RJ48) interface modules used in the ATM switch router comply with Part 68 of the FCC rules. On the bottom of this equipment is a label that contains, among other information, the FCC registration number. If requested, this information must be provided to the telephone company.
  • Page 11 Table 3 USOC Jacks for CES Port Adapters (continued) Model No. WAI-T1C-4RJ48 WAI-T1C-4RJ48 WAI-T1C-4RJ48 WAI-T1C-4RJ48 WAI-T1C-4RJ48 CS-03 Certification The T1 IMA interface module is CS-03 certified. See equipment. Observe the following general information and safety precautions: The industry Canada label identifies CS-03 certified equipment. This certification means that the equipment meets certain telecommunications network protection, operation, and safety requirements as described in the appropriate terminal equipment requirements document(s).
  • Page 12: European Community, Switzerland, Norway, Iceland And Liechtenstein

    The T1 IMA interface module meets the requirements of the Japan Approvals Institute for Telecommunications Equipment (JATE). Table 5 JATE Approval Applicant Name Nihon Cisco Systems European Community, Switzerland, Norway, Iceland and Liechtenstein Declaration of Conformity with Regard to the Directives 73/23/EEC and 89/336/EEC as amended by Directive 93/68/EEC Deutsch: Dieses Gerät entspricht den wesentlichen Anforderungen und weiteren...
  • Page 13 Denna utrustning uppfyller de väsentliga kraven och andra villkor i direktiven 73/23/EEC och 89/336/EEC enligt ändringarna i direktiv 93/68/EEC. Romania: Prin prezenta, noi Cisco Systems România SRL, declarãm pe propria rãspundere cã produsul Catalyst 8500 Series/LightStream 1010, îndeplineste principalele cerin e de conformitate cu Directiva Europeanã 89/336/EEC, 73/23/EEC.
  • Page 14: Cispr 22 Class A Warning

    Regulatory Standards Compliance Canada Class A Warning Warning This Class A digital apparatus complies with Canadian ICES-003. Cet appareil numèrique de la classe A est conforme á la norme NMB-003 du Canada. CISPR 22 Class A Warning This is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
  • Page 15: Class A Notice For Hungary

    Class A Notice for Hungary Warning This equipment is a class A product and should be used and installed properly according to the Hungarian EMC Class A requirements (MSZEN55022). Class A equipment is designed for typical commercial establishments for which special conditions of installation and protection distance are used.
  • Page 16: Translated Safety Warnings

    Translated Safety Warnings Translated Safety Warnings This section includes translations in multiple languages of the warnings that may appear in the Catalyst 8500 MSR, Catalyst 8500 CSR, and LightSteam 1010 series switch product documents. Warning Definition IMPORTANT SAFETY INSTRUCTIONS Warning This warning symbol means danger.
  • Page 17 Translated Safety Warnings Warnung WICHTIGE SICHERHEITSHINWEISE Dieses Warnsymbol bedeutet Gefahr. Sie befinden sich in einer Situation, die zu Verletzungen führen kann. Machen Sie sich vor der Arbeit mit Geräten mit den Gefahren elektrischer Schaltungen und den üblichen Verfahren zur Vorbeugung vor Unfällen vertraut. Suchen Sie mit der am Ende jeder Warnung angegebenen Anweisungsnummer nach der jeweiligen Übersetzung in den übersetzten Sicherheitshinweisen, die zusammen mit diesem Gerät ausgeliefert wurden.
  • Page 18 Translated Safety Warnings Varning! VIKTIGA SÄKERHETSANVISNINGAR Denna varningssignal signalerar fara. Du befinner dig i en situation som kan leda till personskada. Innan du utför arbete på någon utrustning måste du vara medveten om farorna med elkretsar och känna till vanliga förfaranden för att förebygga olyckor. Använd det nummer som finns i slutet av varje varning för att hitta dess översättning i de översatta säkerhetsvarningar som medföljer denna anordning.
  • Page 19: Backplane Voltage

    Translated Safety Warnings Backplane Voltage Hazardous voltage or energy is present on the backplane when the system is operating. Use caution Warning when servicing. Waarschuwing Er is gevaarlijke spanning of energie aanwezig op de achterplaat wanneer het systeem bediend wordt. Wees voorzichtig bij het onderhoud. Kun laite on toiminnassa, taustalevyyn muodostuu vaarallista jännitettä.
  • Page 20: Ground Conductor

    Translated Safety Warnings Ground Conductor This equipment must be grounded. Never defeat the ground conductor or operate the equipment in Warning the absence of a suitably installed ground conductor. Contact the appropriate electrical inspection authority or an electrician if you are uncertain that suitable grounding is available. Waarschuwing Deze apparatuur dient geaard te zijn.
  • Page 21: Restricted Area Warning

    Translated Safety Warnings Restricted Area Warning This unit is intended for installation in restricted access areas. A restricted access area is where Warning access can only be gained by service personnel through the use of a special tool, lock and key, or other means of security, and is controlled by the authority responsible for the location.
  • Page 22: Qualified Personnel Warning

    Translated Safety Warnings Avvertenza Questa unità deve essere installata in un'area ad accesso limitato. Un'area ad accesso limitato è un'area accessibile solo a personale di assistenza tramite un'attrezzo speciale, lucchetto, o altri dispositivi di sicurezza, ed è controllata dall'autorità responsabile della zona. Advarsel Denne enheten er laget for installasjon i områder med begrenset adgang.
  • Page 23 Translated Safety Warnings Varning Denna utrustning ska endast installeras och bytas ut av utbildad och kvalificerad personal. Warning Definition This warning symbol means danger . You are in a situation that could cause bodily injury. Before you Warning work on any equipment, be aware of the hazards involved with electrical circuitry and be familiar with standard practices for preventing accidents.
  • Page 24 Translated Safety Warnings Warnung Dieses Warnsymbol bedeutet Gefahr. Sie befinden sich in einer Situation, die zu einer Körperverletzung führen könnte. Bevor Sie mit der Arbeit an irgendeinem Gerät beginnen, seien Sie sich der mit elektrischen Stromkreisen verbundenen Gefahren und der Standardpraktiken zur Vermeidung von Unfällen bewußt.
  • Page 25: Disconnect Device Warning

    Disconnect Device Warning A readily accessible two-poled disconnect device must be incorporated in the fixed wiring. Warning Waarschuwing Er moet een gemakkelijk toegankelijke, tweepolige stroomverbreker opgenomen zijn in de vaste bedrading. Varoitus Kiinteään johdotukseen on liitettävä kaksinapainen kytkinlaite, johon on helppo päästä käsiksi. Attention Un disjoncteur bipolaire facile d’accès doit être intégré...
  • Page 26: Related Documentation

    Regulatory Compliance and Safety Information for the Catalyst 8500 and LightStream 1010 Series Description Provides information specific to installing and cabling the Catalyst 8500 series and LightStream 1010 ATM switch chassis. modules that can be installed in the ATM and Layer 3 systems.
  • Page 27: Software Documents

    Obtaining Documentation Cisco provides several ways to obtain documentation, technical assistance, and other technical resources. These sections explain how to obtain technical information from Cisco Systems. Cisco.com You can access the most current Cisco documentation on the World Wide Web at this URL: http://www.cisco.com/univercd/home/home.htm...
  • Page 28: Documentation Cd-Rom

    • Nonregistered Cisco.com users can order documentation through a local account representative by calling Cisco Systems Corporate Headquarters (California, USA.) at 408 526-7208 or, elsewhere in North America, by calling 800 553-NETS (6387). Documentation Feedback You can submit comments electronically on Cisco.com. On the Cisco Documentation home page, click Feedback at the top of the page.
  • Page 29: Cisco Tac Website

    Cisco TAC Website The Cisco TAC website (http://www.cisco.com/tac) provides online documents and tools for troubleshooting and resolving technical issues with Cisco products and technologies. The Cisco TAC website is available 24 hours a day, 365 days a year. Accessing all the tools on the Cisco TAC website requires a Cisco.com user ID and password. If you have a valid service contract but do not have a login ID or password, register at this URL: http://tools.cisco.com/RPF/register/register.do Opening a TAC Case...
  • Page 30: Obtaining Additional Publications And Information

    CCIP, CCSP, the Cisco Arrow logo, the Cisco Powered Network mark, Cisco Unity, Follow Me Browsing, FormShare, and StackWise are trademarks of Cisco Systems, Inc.; Changing the Way We Work, Live, Play, and Learn, and iQuick Study are service marks of Cisco Systems, Inc.;...

Table of Contents