To Connect The Electrical Wiring On The Indoor Unit - Daikin Altherma EAVX-D9WG Installer's Reference Manual

Low temperature split
Hide thumbs Also See for Altherma EAVX-D9WG:
Table of Contents
7 Installation
d
b
a
e
e
f
a
Power supply cable
b
Communication cable
c
Cable for bottom plate heater (optional)
d
Ferrite core
e
Tie strap
f
Compressor
NOTICE
To guarantee electromagnetic compatibility:
▪ Make sure both power supply and communication
cables run parallel to one another. Use tie straps to
hold the cables together.
▪ Make sure the cables are located as far away from the
compressor as possible.
▪ The communication cable MUST pass through the
ferrite core.
5 Make sure that the cable does NOT come in contact with sharp
edges or hot gas piping.
6 Install the switch box cover.
INFORMATION
When installing field supply or option cables, foresee
sufficient cable length. This will make it possible to remove/
reposition the switch box and gain access to other
components during service.
CAUTION
Do NOT push or place redundant cable length in the unit.
7.6.7
To connect the electrical wiring on the
indoor unit
1 To open the indoor unit, see
page 27
and
"7.2.4 To open the switch box cover of the indoor
unit" on
page 28.
2 The wiring enters the unit from the top:
d
b+c
a
a, b, c
Field wiring (see table below)
Installer reference guide
36
c
e
e
e
"7.2.3 To open the indoor unit" on
d
Factory-mounted cable for power supply of backup heater
3 Routing of the wiring inside the unit should be as follows. Fix
the cable to the cable rail using cable ties:
Routing
Possible cables (depending on unit type
and installed options)
a
▪ Preferential power supply contact
Low voltage
▪ User interface (option)
▪ Power consumption digital inputs (field
supply)
▪ Outdoor
(option)
▪ Indoor
(option)
▪ Electrical meters (field supply)
▪ Safety thermostat (field supply)
b
▪ Interconnection cable
High voltage power
▪ Normal kWh rate power supply
supply
▪ Preferential kWh rate power supply
c
▪ Heat pump convector (option)
High voltage control
▪ Room thermostat (option)
signal
▪ Shut-off valve (field supply)
▪ Domestic hot water pump (field supply)
▪ Alarm output
▪ Changeover to external heat source
control
▪ Space cool/heat operation control
d
▪ Power supply for backup heater
High voltage power
supply (factory-
mounted cable)
CAUTION
Do NOT push or place redundant cable length in the unit.
4 Seal the low voltage wiring intake using the sealing tape
(delivered as accessory).
Without low voltage cables
EPGA11~16DAV3 + EAVH/X16S18+23DA6V+9W
b+c
a
ambient
temperature
sensor
ambient
temperature
sensor
With low voltage cables
Daikin Altherma – Low temperature split
4P556070-1 – 2019.02