Malfunction; Room - Daikin Altherma EPGA011-016DV Installer's Reference Manual

Low temperature split
Hide thumbs Also See for Altherma EPGA011-016DV:
Table of Contents
8 Configuration
8.4.1

Malfunction

In case of a malfunction,
or
If you open the menu screen, the Malfunctioning menu will now be
visible. Open the menu to see the error code. Press
information about the error.
8.4.2

Room

Setpoint screen
You can control the room temperature of the main zone with the
setpoint screen, also see
"8.3.5 Setpoint screen" on
Schedule
In this menu item you can indicate if the room temperature is
controlled with a schedule or not.
#
Code
[1.1]
N/A
Schedule
▪ 0 No: Room temperature is controlled
by the user.
▪ 1 Yes: Room temperature is controlled
with a schedule and can be modified
by the user.
Heating schedule
This is available for all models.
You can set the room temperature heating schedule using the
schedule screen. For more information about this screen, see
"8.3.8 Schedule screen: Example" on
Cooling schedule
This is available for reversible models.
You can set the room temperature cooling schedule using the
schedule screen. For more information about this screen, see
"8.3.8 Schedule screen: Example" on
Antifrost
Room frost protection [1.4] prevents the room from getting too cold.
This setting behaves differently depending on the set unit control
method [2.9]. Perform actions according to the table below.
Main zone unit control
method [2.9]
Leaving water temperature
control ([C‑07]=0)
External room thermostat
control ([C‑07]=1)
Room thermostat control
([C‑07]=2)
INFORMATION
If a U4 error occurs, room frost protection is NOT
guaranteed.
For more detailed information about room frost protection in relation
to the applicable unit control method, see the sections below:
Leaving water temperature control ([C‑07]=0)
Installer reference guide
46
will appear on the home screen.
to get more
page 43.
Description
page 44.
page 44.
Description
Room frost protection is NOT
guaranteed.
Allow for the external room
thermostat to take care of room
frost protection:
▪ Turn ON [C.2]: Space heating/
cooling
Allow for the user interface used as
room thermostat to take care of
room frost protection:
▪ Choose
[1.4.1]=1:
Room
Antifrost > Activation > Yes
▪ Set the room antifrost setpoint
([1.4.2]): Room > Antifrost >
Room setpoint
Under leaving water temperature control, room frost protection is
NOT guaranteed. However, if room antifrost [1.4] is activated, limited
frost protection by the unit is possible:
External room thermostat control ([C‑07]=1)
Under external room thermostat control, room frost protection is
guaranteed by the external room thermostat, provided that Space
heating/cooling [C.2] is turned ON and the emergency setting [9.5] is
set to automatic.
Room thermostat control ([C‑07]=2)
During room thermostat control, room frost protection is guaranteed
if it is enabled. When room frost protection [2‑06] is activated and the
room temperature drops below the room antifrost temperature [2‑05],
the unit will supply leaving water to the heat emitters to heat up the
room again.
#
Code
[1.4.1]
[2-06]
[1.4.2]
[2-05]
INFORMATION
When the user interface used as room thermostat is
disconnected (due to miswiring, damage of the cable), then
room frost protection is NOT guaranteed.
NOTICE
If Emergency is set to Manual ([9.5]=0), and the unit is
triggered to start emergency operation, the unit will stop
and need to be recovered manually via the user interface.
To recover operation manually, go to the Malfunctioning
main menu screen, where the user interface will then ask
you to confirm emergency operation before starting.
Room frost protection is active even if the user does NOT
confirm emergency operation.
Setpoint range
ONLY applicable in room thermostat control. To save energy by
preventing overheating or undercooling the room, you can limit the
range of the room temperature, both for heating and/or cooling.
NOTICE
When adjusting the room temperature ranges, all desired
room temperatures are also adjusted to guarantee they are
between the limits.
#
Code
[1.5.1]
[3-07]
[1.5.2]
[3-06]
[1.5.3]
[3-09]
[1.5.4]
[3-08]
Room sensor offset
>
ONLY applicable in case of room thermostat control. You can
calibrate the (external) room temperature sensor. It is possible to
give an offset to the room thermistor value measured by the user
interface used as room thermostat or by the external room sensor.
The settings can be used to compensate for situations where the
user interface used as room thermostat or the external room sensor
CANNOT be installed on the ideal installation location (see
"5.7 Setting up an external temperature sensor" on
Description
Activation:
▪ 0 No: Antifrost functionality is OFF.
▪ 1 Yes: Antifrost functionality is on.
Room setpoint 4°C~16°C
Description
Heating minimum
Heating maximum
Cooling minimum
Cooling maximum
page 21).
EPGA11~16DAV3 + EABH/X16DA6V+9W
Daikin Altherma – Low temperature split
4P556069-1 – 2018.10