Specifications - Mitsubishi Electric CITY MULTI PUMY-P200YKM2R2 Technical & Service Manual

Split-type, heat pump air conditioners
Table of Contents
3

SPECIFICATIONS

Model
Power source
Cooling capacity
(Nominal)
Power input
Current input
EER
Temp. range of
Indoor temp.
cooling
Outdoor temp.
Heating capacity
(Nominal)
Power input
Current input
COP
Temp. range of
Indoor temp.
heating
Outdoor temp.
Indoor unit
Total capacity
connectable
CITY MULTI
Branch box
Branch box
1 unit
Branch box
2 units
Sound pressure level (SPL) (measured in anechoic room) dB
Refrigerant
Liquid pipe
piping diameter
Gas pipe
FAN
Type × Quantity
Airflow rate
Control, Driving mechanism
Motor output
External static pressure
Compressor
Type × Quantity
Manufacturer
Starting method
Capacity control
Motor output
Case heater
Lubricant
External finish
External dimension HxWxD
Protection devices
High pressure protection
Inverter circuit (COMP./FAN)
Compressor
Fan motor
Refrigerant
Type × original charge
Control
Net weight
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Defrosting method
Drawing
External
Wiring
Standard attachment Document
Accessory
Optional parts
*1
Nominal cooling conditions
Indoor :
27°C D.B./19°C W.B. [81°F D.B/66°F W.B.]
Outdoor :
35°C D.B. [95°F D.B.]
Pipe length :
7.5 m [24-9/16 ft]
Level difference :
0 m [0 ft]
*3
10 to 52:, when connecting following models: PKFY-P10/15/20/25/32VLM, PFFY-P20/25/32VLEM, PFFY-P20/25/32VLRM(M),
PFFY-P20/25/32VKM, PFFY-P20/25/32VCM, PEFY-P40/63VMA3-E and M series, S series, and P series type indoor unit.
*4
−15 to 52:, when using an optional air protect guide [PAC-SH95AG-E]. However, this condition does not apply to the indoor unit listed in
*5
Liquid pipe diameter: 12.7 mm, when further piping length is longer than 60 m.
* 1
* 2
Note: 1. Nominal conditions
,
2. Due to continuing improvement, above specifications may be subject to change without notice.
OCH675E
*1
kW
*1
kcal/h
*1
Btu/h
kW
A
kW/kW
W.B.
D.B.
*2
kW
*2
kcal/h
*2
Btu/h
kW
A
kW/kW
D.B.
W.B.
CITY MULTI
Branch box
CITY MULTI
Branch box
mm (inch)
mm (inch)
m³/min
L/s
cfm
kW
%
kW
kW
mm
inch
kg (lb)
*2
Nominal heating conditions
20°C D.B. [68°F D.B.]
7°C DB/6°C W.B. [45°F D.B./43°F W.B.]
7.5 m [24-9/16 ft]
0 m [0 ft]
are subject to ISO 15042.
PUMY-P200YKM2, PUMY-P200YKM2-BS
3-phase 380-400-415 V, 50 Hz
22.4
19,300
76,400
6.05
9.88- 9.39- 9.05
3.70
15 to 24°C
−5 to 52°C
25.0
21,500
85,300
5.84
9.54- 9.06- 8.74
4.28
15 to 27°C
−20 to 15°C
50 to 130% of outdoor unit capacity
P10–P200/12
kW type: P15–P100/8
P10–P200/5
kW type: P15–P100/5
P10–P200/3
kW type: P15–P100/8
56/61
75/80
9.52 (3/8)
19.05 (3/4)
Propeller Fan × 2
139/141
2,317/2,350
4,909/4,979
DC control
0.20 + 0.20
0
Scroll hermetic compressor × 1
Siam Compressor Industry Co., Ltd.
Inverter
Cooling 25 to100
Heating 17 to 100
5.3
0
FVC68D (2.3litter)
Galvanized Steel Sheet
Munsell No. 3Y 7.8/1.1
1,338×1,050×330(+40)
52-11/16 × 41-11/32 × 13(+1-10/16)
High pressure Switch
Overcurrent detection, Overheat detection(Heat sink thermistor)
Compressor thermistor, Over current detection
Overheating, Voltage protection
R410A 7.3 kg
Linear Expansion Valve
141 (311)
Cross Fin and Copper tube
HIC circuit
Reversed refrigerant circuit
RK01B689
BH79N143
Installation Manual
Grounded lead wire ×1
Joint: CMY-Y62-G-E
Header: CMY-Y64/68-G-E
10
*3,*4
*3,*4
*5
Unit converter
kcal/h = kW × 860
Btu/h = kW × 3,412
cfm = m3/min × 35.31
lb = kg/0.4536
Above specification data is
* 3
.
subject to rounding variation.

Hide quick links: