In case of low priority alarms (see 3.4.2.2) the buzzer will not immediately sound but only after a certain
delay in order to avoid frequent buzzer activity during momentary alarm situations (e.g. overload,
temperature, weak mains). The buzzer delay time does not affect buzzer operation during alarms with
high priority.
.@7IJ@I>
$7I=6EH
Changes the language of the screen messages: you can select English (default), German, French,
Spanish, Italian.
*F'=F@R'EHJARFO7
Setting 'ON' means that the function is activated: the UPS will switch off during a mains failure when the
load is < 5% of the maximum load. Be careful with very small loads: e.g. a fax machine in stand-by mode
could be recognised by the UPS as a no-load situation.
!@AA>BC'K@D@K6AC
'''''''''''''W"H
In order to generate reliable runtime predictions the UPS needs to be informed about the total battery
capacity. The Ah value shown in the display is the programmed capacity and should indicate the capacity
of the standard internal battery plus the capacity of the battery extension pack(s).
!CD@EE'>7@?=>
'''''&$(
If the NetPro is supplied by a generator set, and the generator's frequency is often out of the UPS's input
tolerances, frequently occurring 'bypass error' alarms (see 3.4.2.2) will be the result. During these alarms
bypass operation is inhibited. To avoid this situation the bypass function can be disabled: the UPS
functions as a UPS without automatic bypass switch.
If NO is selected, i.e. if the bypass function is disabled, the default screen alternates every 10 seconds
with the following message, displayed during 2 seconds:
/"%*M*Z
!CD@EE'R6E@?=>R
+JADJA'QF=A@I>
'''''0123
The output voltage can be set to 220/230/240 Vac.
+JADJA'LB>^J>7KC
'''''82S]
The output frequency can be set to 50/60 Hz.
NOTE: The unit can be used as a frequency converter: the input frequency range is 45-66Hz, the output
frequency is selectable 50/60Hz. If the unit is used as a frequency converter, the bypass function is no
longer available. As a result an audible alarm will be generated continuously (see 3.4.2.2 'Bypass error').
To avoid this, we advise to disable the bypass (see above).
WARNING:
Changing of the output frequency can cause severe damage of equipment connected to
the appliance outlets of the UPS: Be sure that the new frequency is suitable for the
connected equipment!