8-2. TROUBLESHOOTING
Check method of indoor fan motor (fan motor / controller board)
Notes
· High voltage is applied to the connecter (FAN)(CNMF1, 2) for the fan motor. Pay attention to the service.
· Do not pull out the connector (FAN)(CNMF1, 2) for the motor with the power supply on, doing so may result in damage
to the board.
(FAN)
PMFY-P20/25/32/40VBM-E
(CNMF1, 2)
PMFY-P20/25/32/40VBM-E#2
Self check
Symptom : The indoor fan can not rotate.
Indoor controller board fuse check
Is the fuse normal?
Yes
Wiring contact check
Contact of fan motor connector (FAN) (CNMF1,2)
Is there contact failure?
No
Turn ON the power supply.
Power supply check
Check the voltage of the indoor
Approx. 310~340V DC between the connecter < (FAN)
Is the voltage normal?
No
Replace the indoor controller board.
Check the operation
NG
Replace the fan motor.
OC307E
PMFY-P20/25/32/40VBM-E
PMFY-P20/25/32/40VBM-ER3
Is the resistance
between the terminals of
drain pump normal?
No
Replace the drain pump.
Yes
Wiring recovery
controller board with the connector (FAN)
Yes
Check the operation
Replace the the indoor controler board.
OK
END
25
1
PMFY-P20/25/32/40VBM-ER4
(CNMF1, 2)
(+) and
(–) > < (CNMF1) (+) and (CNMF2) (-) >
Replace
the fan motor.
OK
NG
Replace the fan motor.
Replace the indoor controller board.
connected to the board.
END