Mitsubishi Electric CITY MULTI PQRY-P72-336ZLMU-A1 Data Book page 17

Table of Contents
1. SPECIFICATIONS
Heat Source Model
Indoor Model
Power source
Cooling capacity
(Nominal)
Power input
(575) Current input
(Rated)
Power input
(575) Current input
Temp. range of
Indoor
cooling
Inlet water
Heating capacity
(Nominal)
Power input
(575) Current input
(Rated)
Power input
(575) Current input
Temp. range of
Indoor
heating
Inlet water
Indoor unit
Total capacity
connectable
Model/Quantity
Sound pressure level (measured in anechoic room) dB
Refrigerant
High pressure
piping diameter
Low pressure
Set Model
Model
Minimum Circuit Ampacity
Maximum Overcurrent Protection
Circulating water
Water flow rate
Pressure drop
Operating volume
range
Compressor
Type x Quantity
Starting method
Motor output
Case heater
Lubricant
External finish
External dimension H x W x D
Protection devices
High pressure protection
Inverter circuit
Compressor
Refrigerant
Type x original charge
Control
Net weight
Heat exchanger
Water volume in plate
Water pressure Max.
HIC circuit (HIC: Heat Inter-Changer)
Pipe between unit and
High pressure
distributor
Low pressure
Drawing
External
Wiring
Standard
Document
attachment
Accessory
Optional parts
Remarks
Notes:
1.Nominal cooling conditions (Test conditions are based on AHRI 1230)
Indoor: 81°FD.B./66°FW.B. (27°CD.B./19°CW.B.), Inlet water temperature: 86°F (30°C)
2.Nominal heating conditions (Test conditions are based on AHRI 1230)
Indoor: 68°FD.B. (20°CD.B.), Inlet water temperature: 68°F (20°C)
MEES21K047
*1 BTU/h
kW
kW
A
BTU/h
kW
kW
A
W.B.
ºF
*2 BTU/h
kW
kW
A
BTU/h
kW
kW
A
D.B.
ºF
in. (mm)
in. (mm)
PQRY-P168ZLMU-A1
A
A
G/h
G/min (gpm)
3
m
/h
L/min
cfm
psi
kPa
G/h
G/min (gpm)
3
m
/h
Inverter scroll hermetic compressor x 1
kW
kW
Galvanized steel sheets
in.
57-1/8 x 34-11/16 x 21-11/16
mm
1,450 x 880 x 550
High pressure sensor, High pressure switch at 4.15 MPa (601
Over-heat protection, Over-current protection
Over-heat protection
R410A x 13 lbs + 4 oz (6.0 kg)
lbs (kg)
G
l
psi
MPa
in. (mm)
7/8 (22.2) Brazed
in. (mm)
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
The ambient temperature of the Heat Source Unit needs to be kept below 104°FD.B. (40°CD.B.)
The ambient relative humidity of the Heat Source Unit needs to be kept below 80%.
The Heat Source Unit should not be installed at outdoor.
Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
Be sure to provide interlocking for the unit operation and water circuit.
The Heat Source twinning kit (low pressure) should be connected to the low pressure side of the heat source unit.
Install the supplied insulation material to the unused drain-socket.
When installing insulation material around both water and refrigerant piping, follow the installation manual.
The cooling tower and the water circuit must be a closed circuit (water is not exposed to the atmosphere).
PQRY-P336ZSLMU-A1
Non-Ducted
3-phase 3-wire 575 V ±10% 60 Hz
336,000
98.5
26.84
29.9
320,000
93.8
24.76
27.6
59~75°F (15~24°C)
50~113°F (10~45°C)
378,000
110.8
20.77
23.1
361,000
105.8
19.16
21.3
59~81°F (15~27°C)
50~113°F (10~45°C)
50~150% of heat source unit capacity
P04~P96/2~50 (Connectable branch pipe number is max. 48.)
59.0
1-1/8 (28.58) Brazed
1-5/8 (41.28) Brazed
16
25
1,902 + 1,902
31.7 + 31.7
7.20 + 7.20
120 + 120
4.2 + 4.2
6.38
44
1,189 + 1,189 ~ 3,054 + 3,054
19.8 + 19.8 ~ 50.9 + 50.9
4.5 + 4.5 ~ 11.6 + 11.6
Inverter
11.0
-
MEL32
High pressure sensor, High pressure switch at 4.15 MPa (601
psi)
Indoor LEV and BC controller
512 (232)
plate type
1.32
5.0
290
2.0
-
-
KL94C252
KE94G421
Installation Manual
Details refer to External Drw
Heat Source Twinning kit: CMY-Q200CBK
joint: CMY-Y102SS-G2, CMY-Y102LS-G2, CMY-R160-J1
Main BC controller: CMB-P108,1012,1016NU-JA1, CMB-P1016NU-KA1
Sub BC controller: CMB-P104,108NU-KB1
WR2-Series-575V
Ducted
25.85
28.8
20.05
22.3
PQRY-P168ZLMU-A1
16
25
6.38
44
Inverter scroll hermetic compressor x 1
Inverter
11.0
-
MEL32
Galvanized steel sheets
57-1/8 x 34-11/16 x 21-11/16
1,450 x 880 x 550
psi)
Over-heat protection, Over-current protection
Over-heat protection
R410A x 13 lbs + 4 oz (6.0 kg)
512 (232)
plate type
1.32
5.0
290
2.0
-
7/8 (22.2) Brazed
1-1/8 (28.58) Brazed
KE94G421
Unit converter
BTU/h =kW x 3,412
3
cfm
=m
/min x 35.31
lbs
=kg/0.4536
*Above specification data is
subject to rounding variation.
15