LG Multi F Series Installation Manual page 88

Outdoor unit
Hide thumbs Also See for Multi F Series:
Table of Contents
FINAL INSTALLATION PROCEDURES
Wiring Error Check
Use to verify if wiring is properly installed.
1. Shut power down to the system.
2. Set DIP Switch 2 to ON.
3. Turn power on to the system.
4. Check if the Red and Green LEDs on the outdoor unit PCB are ON (indicate indoor units are in forced
operation mode).
5. If the wiring is correctly installed, the Green LED will light up. If the wiring is incorrectly installed, the
Red and Green LEDs will blink, indicating which part of the system is in error.
• Red LED = Piping Number
• Green LED = Wiring Number (Room)
Example: If the Red LED blinks twice and the Green LED blinks three times, the second
piping to the third room is in error (see at right).
• If the indoor unit(s) are not communicating properly to the outdoor unit, the Wiring
Error Check cannot operate correctly.
• Only the part of the system in error will be displayed. System will operate correctly
after the error is fixed.
• If outdoor and indoor temperatures are too low (ex.: winter), the wiring error check function will not operate (Red LED is ON).
• Turn DIP Switch 2 to OFF after finishing (Normal Operation setting).
• Only the first four DIP switches are functional on the LMU480, 540, 600HV.
Reducing Power Consumption
Enables more efficient system operation by reducing the maximum power consumption
value (reducing the MCA).
1. Shut power down to the system.
2. For Step 1, set only DIP Switch 3 to ON. For Step 2, set only DIP Switch 4 to ON.
3. Turn power on to the system.
Table 39: Reducing Power Consumption Current Levels.
Phase
Model
Multi F
LMU18CHV,
LMU24CHV
Step 1 (A)
9
Step 2 (A)
8
• Reduced Power Consumption reduces outdoor unit capacity.
• Only the first four DIP switches are functional on the LMU480, 540, 600HV.
88
Multi F
Multi F MAX
LMU30CHV,
LMU480HV,
LMU36CHV
LMU540HV,
LMU600HV
13
22
11
21
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Figure 115: Wiring Error Check Example.
LED 1
(Red)
LED 2
(Green)
Figure 116: Reducing Power Consumption Chart.
Power
Consumption
and Current
Figure 117: Reducing Power Consumption DIP Switch Settings.
Step 1
ON
OFF
1 2
3
4
1 2
3
4
F
MULTI
F
MULTI
MAX
Figure 114: Wiring Error Check
3
DIP Switch Setting.
ON
OFF
1 2
3
4
1 2
3
4
Two (2)
Three (3)
Blinks
Blinks
One (1)
One (1)
Second
Second
Two (2)
Three (3)
Blinks
Blinks
One (1)
Second
Normal
Step 2
ON
OFF
1 2
3
4
1 2
3
4
One (1)
Second
Time
Table of Contents
loading

This manual is also suitable for:

Multi f max seriesLmu18chvLmu24chvLmu30chvLmu36chv

Table of Contents