important safeguards Warning – This is a class A product. In a domestic environment this product may cause radio interference, in which case the user may be required to take adequate measures. Warning Read the Instructions – We recommend that you read ...
internal view For spare parts, please call your nearest Dynalite Customer Service Centre, and specify: DLE1210 DLE1210 Installation Manual Rev G.docx...
mounting Select a Suitable Location This device is designed for indoor use only. If installing in an external location, the DLE1210 must be housed in a suitable well ventilated enclosure. Choose a dry location that will be accessible after the installation is complete.
supply & load cable connections Supply Cables The supply input terminals are located toward the top of the enclosure and consists of Earth, Neutral, and Phase, all of which will accept up to 25mm cables. The supply cables should have a capacity of 40A per phase, to allow the device to be loaded to its maximum capacity.
connecting serial control cables Connect Data Cable in a ‘Daisy Chain’ Determine Your Requirements Serial ports are used to interconnect other dimmers, smart control panels, sensors and AV controllers. Serial port devices can be identified by 4 terminals, labelled: GND, DATA+, DATA-, +VE. Serial Cable Connections There is one RS485 port for DyNet signals, in the form of a RJ12 socket, on the front panel, which is...
Hold Down Programming Of Presets AUX Input - This is a dry contact interface that is active low. The dry contact is connected between the AUX and GND terminals on the DyNet connector strip. The function of the AUX input is programmable. Ensure that the cable length between the dry contact and terminal strip is no longer than 2 metres.