Alarm Menu; List Of Error Display With Details - Honeywell VPI Series Installation Instruction

Pressure independent control valves and actuators
Table of Contents

Alarm Menu

To enter the alarm menu, simultaneously press  and  for 6 seconds. The alarm menu is only accessible if an alarm
is present (i.e. when the icon
For fast menu exit press  and  simultaneously for 6 seconds. The actuator will automatically return to normal
operation mode if no action is detected on arrow keys for 1 minute.
If the actuator is still functioning (= warning code 01, 04, 05 with failsafe and 07 with failsafe), the
the actuator is NOT functioning (=error code 01, 03, 05, 06 with failsafe and 08), the
be shown in the information part of the actuator display.
Display
Code
Display
01
02
03
04
05
06
07
is displayed). Press
Description
Alarm.
Enter password.
Table 9. List of Error display with details
Icon
Valve/actuator is over-torqued.
FULL ON
Actuator has reached its torque
limit in the past
BLINKING
Critical – over temperature.
FULL ON
High temperature.
BLINKING
No Failsafe: Power supply not
in range
FULL ON
With Failsafe: Power supply not
detected / not in range.
BLINKING
Control signal not detected.
FULL ON
Battery error.
BLINKING
VPI PRESSURE INDEPENDENT CONTROL VALVES & ACTUATORS
to go to the next alarm display and press
If enabled in programming menu step 11 Disabled by
default. Password: 3569266.
Description
21
to go to previous.
icon is fully on. Error codes will
Action
Details
Operation is stopped. Actuator will retry
operation every.
Actuator is functioning.
To reset the alarm simultaneously press
and
for 6 seconds.
Critical: Temperature in actuator is at least
70ºC, motor operation is stopped. If
temperature is decreasing operation will
resume.
Actuator is still functioning. Temperature in
actuator is at least 50ºC as limited
according to tech note. If temperature is
decreasing, operation will resume.
Operation is stopped. Alarm will
automatically reset when voltage is back in
range.
Failsafe is activated. Alarm will
automatically reset when voltage is back in
range.
Operation is stopped. Alarm will
automatically reset when control signal is
back in range.
Battery is not properly connected. Alarm will
reset when battery is properly connected.
Only valid for failsafe actuators.
icon will blink. If
31-00383-01