DeviceNet Explicit Messages
The command data is written in words starting from D01000 in the PLC and the response data is stored in
words starting from D02000.
If the command does not end normally, the end code is stored in D00006 and the send command is re-exe-
cuted.
Command Details
• [CMND S
D
S: D01000
D (first response word): D02000
C: D00000
Contents of S
Address
D01000
28 01
D01001
0B 0E
D01002
00 97
D01003
00 04
66 **
D01004
Contents of C
Address
D00000
00 09
D00001
00 09
D00002
00 00
D00003
05 FE
D00004
00 00
D00005
00 3C
Response
Contents of D
Address
D02000
28 01
D02001
00 00
D02002
00 02
D02003
0B 8E
D02004
00 00
224
C]
Contents (Hex)
Command code
Smart Slave node address: 11
Service code: 0E Hex
Class ID: 0097 Hex
Instance ID: 0004 Hex
Attribute ID: 66 ** Hex (Set any value for the blank boxes.)
Contents (Hex)
Number of bytes of command data
Number of bytes of response data
Destination DeviceNet Unit network address: 0
Destination DeviceNet Unit node address: 5
Destination DeviceNet Unit unit address: FE Hex (or 10 Hex)
Response required
Communications port number: 0
Number of retries: 0
Response monitoring time: 6 s
Contents (Hex)
Response source node address: 11 (0B Hex)
Normal completion: 8E Hex
Operation time monitor result (0000: Within range)
Result is stored.
Meaning
Meaning
Meaning
0000
Not used.
Appendix A