Emerson Bristol 392951-01-0 Instructions Manual
Emerson Bristol 392951-01-0 Instructions Manual

Emerson Bristol 392951-01-0 Instructions Manual

Expansion transmitter interface board

Quick Links

Product Information Package
PIP-EXPTIBS
Mar., 2007
Expansion Transmitter Interface
Board Part No. 392951-01-0
For The Following Bristol Instruction Manuals:
CI-3530-20B & CI-3530-25B
www.EmersonProcess.com/Bristol
TeleFlow Plus & TeleRTU Plus
Table of Contents
loading

Summary of Contents for Emerson Bristol 392951-01-0

  • Page 1 Product Information Package PIP-EXPTIBS Mar., 2007 TeleFlow Plus & TeleRTU Plus Expansion Transmitter Interface Board Part No. 392951-01-0 For The Following Bristol Instruction Manuals: CI-3530-20B & CI-3530-25B www.EmersonProcess.com/Bristol...
  • Page 2 IMPORTANT! READ INSTRUCTIONS BEFORE STARTING! Be sure that these instructions are carefully read and understood before any operation is attempted. Improper use of this device in some applications may result in damage or injury. The user is urged to keep this book filed in a convenient location for future reference.
  • Page 3 WARRANTY Bristol warrants that goods described herein and manufactured by Bristol are free from defects in material and workmanship for one year from the date of shipment unless otherwise agreed to by Bristol in writing. Bristol warrants that goods repaired by it pursuant to the warranty are free from defects in material and workmanship for a period to the end of the original warranty or ninety (90) days from the date of delivery of repaired goods, whichever is longer.
  • Page 4 How to return material for Repair or Exchange Before a product can be returned to Bristol for repair, upgrade, exchange, or to verify proper operation, form (GBU 13.01) must be completed in order to obtain a RA (Return Authorization) number and thus ensure an optimal lead time. Completing the form is very important since the information permits the Bristol Repair Dept.
  • Page 5 Bristol Repair Authorization Form (off-line completion) (Providing this information will permit Bristol to effectively and efficiently process your return. Completion is required to receive optimal lead time. Lack of information may result in increased lead times.) Date___________________ RA #___________________SH Line No.____________ Standard Repair Practice is as follows: Variations to this is Please be aware of the Non warranty standard charge: •...
  • Page 6 Bristol Training GET THE MOST FROM YOUR BRISTOL BABCOCK INSTRUMENT OR SYSTEM • Avoid Delays and problems in getting your system on-line • Minimize installation, start-up and maintenance costs. • Make the most effective use of our hardware and software. •...
  • Page 7 A Few Words About Bristol Inc. For over 100 years, Bristol has been providing innovative solutions for the measurement ® and control industry. Our product lines range from simple analog chart recorders, to sophisticated digital remote process controllers and flow computers, all the way to turnkey SCADA systems.
  • Page 8 For technical questions regarding ACCOL products, OpenBSI Utilities, UOI and all other software except for ControlWave and OpenEnterprise products, call (860) 945-2286. For technical questions about Network 3000 hardware, call (860) 945-2502. You can e-mail the Application Support Group at: [email protected] The Application Support Group maintains an area on our web site for software updates and technical information.
  • Page 9: Table Of Contents

    PIP-EXPTIBS EXPANSION TRANSMITTER INTERFACE BOARD PT. Number 392951-01-0 Product Information Package TABLE OF CONTENTS SECTION TITLE PAGE # Section 1 - INTRODUCTION DESCRIPTION........................1 1.1.1 Transmitter Operation......................1 LED INDICATORS......................2 JUMPER JP1 ........................2 Section 2 – INSTALLATION & SERVICE REMOVAL/REPLACEMENT &...
  • Page 10: Section 1 - Introduction

    Section 1 INTRODUCTION 1.1 DESCRIPTION Expansion Transmitter Interface Boards (ETIBs) allow up to two (2) Bristol, Series 3508C Transmitters to communicate with an ACCOL loaded host TeleFlow Plus Electronic Gas Measurement Computer (EGMC) (3530-20B) or TeleRTU Plus (3530-25B). The EGMC/RTU polls and stores data from each transmitter and communicates with the network.
  • Page 11: Led Indicators

    1.2 LED INDICATORS The ETIB contains two LEDs which have the following functions: Carrier Detect (CD) and Request to Send (RTS). When the board is sending a Request To Send, LED DS2 (RTS) will be ON and LED DS1 (CD) will be OFF. Conversely, when the ETIB is receiving data from a 3508 Transmitter, LED DS2 (RTS) will be OFF and LED DS1 - Carrier Detect (CD) will be 1.3 JUMPER JP1 Jumper JP1 is used to configure the ETIB for operation with one or two 3508 Transmitters.
  • Page 12: Section 2 - Installation & Service

    Section 2 INSTALLATION & SERVICE 2.1 REMOVAL/REPLACEMENT & INSTALLATION OF THE ETIB 2.1.1 Removal/Replacement of the Expansion Transmitter Interface Bd. An installed ETIB option will contain the following parts: 1. Expansion Transmitter Interface Board (ETIB) (with removable Terminal Blocks) 2. Three #8-32 x 1/4” SEM Screws 3.
  • Page 13 Figure 3 - Expansion TIB Mounted on TeleRTU CPU Board To remove the optional Expansion Transmitter Interface Board, follow steps 1 through 7 below. To replace the ETIB Board follow steps 2 and 6 below in reverse order, installing rather than removing the item in question and then perform step 7 (see Figures 4 & 5). Note: Any PC Board is not to be removed under any circumstances unless the TeleFlow/TeleRTU has been moved to an ESD safe area (see ESDS Manual S14006).
  • Page 14 1. Open the Instrument Front Cover (Door). 2. Disconnect power by removing harness connector plug (P8 for TeleFlow - P2 for TeleRTU) from the CPU Board edge connector (J8 for TeleFlow - J2 for TeleRTU). 3. Unplug the remaining removable Terminal Blocks (with wiring harnesses installed) from the CPU Board’s front edge connectors.
  • Page 15: Installation Of The Expansion Transmitter Interface Board Option

    Note: If a replacement Expansion Transmitter Interface Board is available follow steps 2 through 6 in reverse order (after configuring Jumper JP1 (see Section 1.3), installing rather than removing the item in question. 7. Close and Secure the Door. Figure 6 - Bottom View of TeleRTU Plus (Similar to TeleFlow Plus) 2.1.2 Installation of the Expansion Transmitter Interface Board Option 1.
  • Page 16: Field Wiring

    2.2 FIELD WIRING The device uses compression-type terminals that accommodate up to #14 AWG wire. A connection is made by inserting the bared end (1/4 inch Max.) into the clamp beneath the screw and then securing the screw. Insert the bared end fully to prevent short circuits. Allow some slack in the wires when making terminal connections.
  • Page 17 TABLE 1 - ETIB BOARD TERMINAL DESIGNATIONS CONNECTION 3530-20B 3530-25B LPTIB LPTIB if PDB. CONNECTION CONNECTION TB NAME Is Present If no PDB. If no PDB. TB1-1 XMTR1- 3508- 3508- 3508- TB1-2 XMTR1+ 3508+ 3508+ 3508+ TB2-1 XMTR2- 3508- 3508- 3508- TB2-2 XMTR2+...
  • Page 18: Section 3 - Specifications

    Section 3 SPECIFICATIONS 3.1 GENERAL SPECIFICATIONS Communication Interface: RS-232 (± 3V minimum) 3508-10C/30C Interface: FSK Modem - Bell 202 Compatible (1200 Hz/2200 Hz modulation) ESD Susceptibility: Field connected circuits are designed to meet the requirements of IEC 801-2 for ESD withstand capability up to 10KV. EMI Compatibility: Designed to coexist within a shielded enclosure with the TeleFlow (3530-20B)
  • Page 19: Special Instructions For Class I, Division 2 Hazardous Locations

    Expansion Transmitter Interface Board Special Instructions for Class I, Division 2 Hazardous Locations 1. The Bristol Expansion Transmitter Interface Board (ETIB) is listed by Underwriters Laboratories (UL) as nonincendive and is suitable for use in Class I, Division 2, Groups A, B, C and D hazardous locations or non-hazardous locations only.
  • Page 20 Phone: 905-362-0880 Fax: 905-362-0882 TeleFlow™ is a trademark of Bristol, Inc. The Emerson logo is a trade mark and service www.EmersonProcess.com/Bristol mark of Emerson Electric Co. Other trademarks or copyrighted products mentioned in this document are for information only, and belong to their respective companies, or Emerson Process Management trademark holders.
  • Page 21 This page provides links that allow you to go to a specific manual’s Table of Content (T.O.C.), return to document PIP-EXPTIBS’ Table of Content or return to the first page of the Main Menu. Links are provided by selecting the appropriate Link Text Box.

Table of Contents