Si01-982 Table of Contents 1. Removal of Outer Panels ................2 2. Removal of Outdoor Fan / Fan Motor .............4 3. Removal of Electrical Components ............7 4. Removal of Sound Blankets..............12 5. Removal of Capillary Tube..............13 6. Removal of Compressor ASSY.............14 Removal Procedure...
Removal of Outer Panels Si01-982 1. Removal of Outer Panels Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Appearance features (R10742) Take care not to cut your finger by the fins of the outdoor heat exchanger.
Page 5
Si01-982 Removal of Outer Panels Procedure Points Step Remove the 3 screws (left: 2 screws, right: 1 screw) and lift the top panel from the rear side Top panel at first. Remove the 6 screws of the front panel. Front panel (R15458) Lift up the left side and unfasten the hooks.
Removal of Outdoor Fan / Fan Motor Si01-982 2. Removal of Outdoor Fan / Fan Motor Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Remove the nut of the Nut size: M6 outdoor fan.
Page 7
Si01-982 Removal of Outdoor Fan / Fan Motor Procedure Points Step Pull out the terminal Terminal board (X1M) (black) from the terminal board X1M (2). to fan motor upper: black Pull out the 2 terminals (red, white) from the fan (R17184) capacitor (C2R).
Page 8
Removal of Outdoor Fan / Fan Motor Si01-982 Procedure Points Step Remove the fan motor When reassembling, fit the fixing frame. lower hooks into the bottom frame. (R10460) (R15206) Remove the 3 screws M4 × 16 and remove the fan Fan motor motor.
Si01-982 Removal of Electrical Components 3. Removal of Electrical Components Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Remove the 3 screws and disconnect the connecting wire.
Page 10
Removal of Electrical Components Si01-982 Procedure Points Step Remove the 4 screws on the right side. (R15222) Unfasten the hook of When reassembling, make the right side panel. sure to fit the hook. Right side panel (R10467) Remove the right side panel.
Page 11
Si01-982 Removal of Electrical Components Procedure Points Step Remove the screw of the terminal board. Terminal board (R15210) Detach the fixing plate. Fixing plate (R15211) Remove the screw of the earth wire. Earth wire (R17148) Cut the clamp. Clamp (R15213) Removal Procedure...
Page 12
Removal of Electrical Components Si01-982 Procedure Points Step Pull out the 3 terminals Compressor capacitor from the compressor capacitor (C1R). (R15225) Fan capacitor (C2R) Pull out the terminal (red) from the fan capacitor (C2R). to terminal board X1M(1): red (R16375) Fan capacitor (R15214) Pull out the harnesses...
Page 13
Si01-982 Removal of Electrical Components Procedure Points Step Remove the 2 screws to loosen the capacitor fixing band. Capacitor fixing band (R15374) Remove the compressor capacitor. (R15357) Layout of the electrical C1R: compressor capacitor components C2R: fan capacitor Earth wire Compressor (S terminal): yellow Compressor...
Removal of Sound Blankets Si01-982 4. Removal of Sound Blankets Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Untie the 2 strings and Preparation open the sound blanket Remove the outer panels (body).
Si01-982 Removal of Capillary Tube 5. Removal of Capillary Tube Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Before working, make sure that the refrigerant Warning gas is empty in the circuit.
Removal of Compressor ASSY Si01-982 6. Removal of Compressor ASSY Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Remove the nut. (R10482) Remove the terminal Terminal cover cover.
Page 17
Si01-982 Removal of Compressor ASSY Procedure Points Step Unscrew the 3 nuts of the compressor. Warning Be careful not to get yourself burnt with the pipes and other parts that are heated by the gas brazing machine. Before working, make Warning sure that the refrigerant If the refrigerant gas leaks...
Page 18
Revision History Month / Year Version Revised contents 02 / 2013 Si01-982 First edition...
Page 19
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.