Slant/Fin VSL Series Manual

Dhw settings

Quick Links

Use the following step to adjust parameter 3012, this parameter enables and controls
how DHW is controlled on the boiler. The table below lists all the possible settings for
parameter 3012. When setting up the boiler for use with the Slant/Fin DAWG parameter
3012 should be programmed to 2.
3012
DHW mode
1.
Turn the main electrical supply Off;
2.
Press and hold, at the same time,
the RESET button and
3.
Keeping the two buttons pressed,
turn the power on;
4.
Wait until the word "init" is displayed
or until display start to show the
3000 parameters;
5.
Let go of the RESET button and
after the
button;
6.
Parameters 3000 start to be
displayed;
0 = no DHW
1 = DHW store with sensor
2 = DHW store with thermostat
3 = N/A
4 = N/A
5 = N/A
7.
Press and release
buttons to scroll through the list of
parameters;
button;
8.
Once the parameter has been selected,
it can be changed pressing the RESET
button (value start to blinking) and using
the
change the value;
9.
Press RESET button to save the
changed parameter;
10. Wait 10 seconds;
11. Turn the main electrical supply Off;
12. Turn the main electrical supply On to
leave the Factory menu.
VSL II DHW Settings
and
buttons you can
and
loading

Summary of Contents for Slant/Fin VSL Series

  • Page 1 Use the following step to adjust parameter 3012, this parameter enables and controls how DHW is controlled on the boiler. The table below lists all the possible settings for parameter 3012. When setting up the boiler for use with the Slant/Fin DAWG parameter 3012 should be programmed to 2.
  • Page 2 Slant/Fin VSLII DHW Settings After adjusting parameter 3012 the following parameter should be reviewed and adjusted if needed. These parameter can be found in the installers menu follow the steps below to access the installer menu. To access the “Installers Menu” (see also section...
  • Page 3 Slant/Fin VSLII DHW Settings VSL II Water Connections CAUTION!!! This is a concept drawing only. It is up to the system design or to determine the necessary components, including the additional equipment and any safety devices which in the judgment of the designer...

This manual is also suitable for:

Vsl ii