Summary of Contents for Emerson SolaHD SPD200K Series

  • Page 1 Surge Protective Devices SPD200K/300K Series...
  • Page 2: Safety Information

    Safety Information Important Information Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
  • Page 3 SPD200K/300K Precautions DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, NOM-029-STPS or CSA Z462. • This equipment must only be installed and serviced by qualified electrical personnel. •...
  • Page 4: Unpacking And Preliminary Inspection

    SPD200K/300K DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • Do not energize the surge protective device until the electrical system is completely installed, inspected and tested. • Ensure all conductors are connected. • Verify the voltage rating of the device and system prior to energizing. •...
  • Page 5: Equipment Performance

    SPD200K/300K Surge Protective Device (SPD) Location Considerations Environment The device is designed to operate in an ambient temperature range of -25° C (-13° F) to +60° C (140° F) with a relative humidity of 0 to 95% non- condensing. Audible Noise The device background noise is negligible and does not restrict the location of the installation.
  • Page 6 SPD200K/300K Table 1: Part Number Construction 200K or 300K oooRC Surge Protective Device 200kA or 300kA Rating Per Phase Voltage Codes 10Y – 208Y/120V 27Y – 480Y/277V 24D – 240V Delta 48D – 480V Delta 34Y – 600Y/347V 60D – 600V Delta* *200K version only R = Internal Rotary Disconnect C = LED(s)/Audible Alarm/Relay/ Surge Counter...
  • Page 7 SPD200K/300K Terminals, Wire Size and Installation Torque Terminals are provided for phase (line), neutral, and equipment ground connections. Table 2: Terminal Torque Connection Torque Power Connection Torque AØ, BØ, CØ, N and Ground 40–50 lb-in. ( 4.5–5.6 N•m) Wire Size: 8 AWG to 1/0 AWG Copper Location of Surge Protective Device (SPD) Locate the SPD as close as possible to the circuit being addressed to minimize the wire length and optimize SPD performance.
  • Page 8 SPD200K/300K CAUTION SPD DAMAGE AND POWER SYSTEM OVERVOLTAGE • Ungrounded power systems are inherently unstable and can produce excessively high line-to-ground voltages during certain fault conditions. During these fault conditions any electrical equipment, including an SPD, may be subjected to voltages which exceed their designed ratings. This information is being provided to the user so that an informed decision can be made before installing any electrical equipment on an ungrounded power system.
  • Page 9: Installation

    SPD200K/300K Delta and Resistance-Grounded Power Systems DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • For resistance-grounded system maintain an over-damped state to limit voltage overshoot and duration during operation. • Verification and adjustment of correct power system damping should be done following power system modifica- tions and periodically, as part normal system maintenance.
  • Page 10 SPD200K/300K Module Rotation Feature Installation lead wire length must be minimized because longer leads hurt performance. Lead length may be reduced by rotating the module inside the enclosure. SPD ships with terminals pointing down. If installation lends itself toward other orientation, the module’s aluminum backplane can be unscrewed and reoriented. For example, if leads enter from top, rotate module assembly such that leads are shortest.
  • Page 11: Dimensions And Weights

    LED indicators on the display will be lit and the service LED extinguished. If you have any questions pertaining to the installation of this device, contact us at 1-800-377-4384 or [email protected]. Dimensions and Weights Model H/W/D (in.
  • Page 12 SPD200K/300K Wiring Diagrams With Disconnect Switch NOTICE HAZARD OF LOSS OF PROPERLY FUNCTIONING LED/ALARM/STATUS • Bond the ground and neutral lugs with a 10 AWG wire when connected to no-neutral power sources only. Failure to follow these instructions can result in equipment damage. SINGLE POLE TWO POLE Figure 4: Three-Phase, Three- or Four-Wire, Grounded Wye Installation with Integral Switch...
  • Page 13 SPD200K/300K Figure 5: Three-Phase, Three-Wire + Ground, Delta Installation The ground connection of the Delta SPD shall be connected to the system ground conductor. The neutral conductor is not present on Delta systems. Corner Grounded Delta Ungrounded Delta GLE POLE TWO POLE Phase A Phase A...
  • Page 14: Operation

    SPD200K/300K UL 1283 Required Language Concerning the Installation of EMI Filters (Standard on SPD200K/300K) A. An insulated grounding conductor that is identical in size and insulation material and thickness to the grounded and ungrounded circuit supply conductors, except that it is green with or without one or more yellow stripes, is to be installed as part of the circuit that supplies the filter.
  • Page 15: Audible Alarm

    SPD200K/300K Figure 6: Diagnostic Display Panel Phase A, B & C: Green LED indicators—one per phase. Green is good. Out indicates problem. Every suppression element in this SPD is monitored. (N-G indicates on Phase A) Service LED (Red): LED illuminates in the event of problems. This indicator is logic-connected to the Phase LEDs.
  • Page 16: Dry Contacts

    NO to COM Closed NC to COM Open The dry contacts are designed for a maximum voltage of 24 Vdc / 24 Vac and a maximum current of 2 A. For application questions, contact us at 1-800-377-4384 or [email protected]. Page: 14...
  • Page 17: Maintenance And Troubleshooting

    This surge protector has little to troubleshoot. If a phase LED in extinguished or the service light is on please contact us. For application questions, contact us at 1-800-377-4384 or [email protected]. Replacement Parts The module is field replaceable. Deenergize SPD, confirm with appropriate measurement equipment and discharge internal capacitance to ground.
  • Page 18 SPD200K/300K Page: 16...
  • Page 19: Technical Support

    SPD200K/300K Technical Support Website: www.solahd.com Technical Support E-Mail: [email protected] Toll-Free: (800) 377-4384 USA: (847) 268-6651 Warranty Please refer to the “Terms & Conditions of Sale” document. While every precaution has been taken to ensure accuracy and completeness in this manual, Appleton Grp LLC d/b/a Appleton Group assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
  • Page 20 The Emerson logo is a trademark and service mark of Emerson Electric Co. Appleton Grp LLC d/b/a Appleton Group. SolaHD is a registered trademark of Appleton Grp LLC. All other marks are the property of their respective owners. © 2020 Emerson Electric Co. All rights reserved. United States...